 Model PF845411/PF845412

I n s t a l l a t i o n ,   O p e r a t i o n ,   &   M a i n t e n a n c e   M a n u a l

8

Preferred Products

is too large for the load, you may change the DIP switch 

position to ON.  It is not necessary in most cases.

• 

DIP #3 = Temperature Check - If you are installing this 

humidifier on a system that will have duct temperatures 

regularly below 100°F, set this DIP switch to the OFF po-

sition.  Typical furnace bonnet temperature is nominally 

120°F.

• 

DIP  #4  =  Furnace  Runs  Fan/Humidifier  Runs  Fan  -  In 

most systems the HVAC system operates the main blow-

er.  The PF845412 has a 24VAC output that may be used 

to start the main blower if you would like to be able to get 

some humidfication while the furnace is off.

• 

DIP #5 = Temperature Override - This DIP switch is fac-

tory set to OFF.  In the event of a T1 thermistor failure, 

this switch may be set to ON.  This will allow the humidi-

fier to operate temporarily with a single thermistor until a 

replacement is aquired.  

5.1 Preliminary Checkout and Start-up Sequence

1.  Check that unit drain plumbing is properly connected and 

drained.

2.  Ensure that the supply plumbing is installed properly.

3.  Open cold water supply and insure water is reaching the 

unit.  Incoming water line should be filtered.

4.  Ensure that the unit’s line cord is plugged into an appro-

priate power source.

5.  With the unit powered and the humidistat has a “call for 

humidity”, the indicator LED (if equipped) will illuminate 

Green and the unit will begin operation. 

6.  If at any point the indicator LED illuminates red or blinks 

red/green alternating, a fault has been detected; service 

will be required and the fault must be reset. Refer to the 

Maintenance & Troubleshooting section.

7.  Refer to the humidistat manual for “call for humidity” per-

centage settings.

5.2 Starting/Stopping the unit

In order to start and stop the unit you must only raise or lower 

the humidistat setting to a point at which the contacts are closed 

or open.  When the humidistat contacts are closed, the unit will 

start.  When the humidistat contacts are open, the unit will stop.  

Unplugging the line cord may not remove all sources of power 

to the unit.

6. Maintenance & Troubleshooting

!

DANGER - RISK OF ELECTRIC SHOCK

Before cleaning, servicing, or parts replacement, the unit must 

be disconnected from all sources of electricity.

6.1 Pad Replacement

It  will  become  necessary  to  replace  the  pad  inside  your  Pre-

ferred

TM

  PF845411/PF845412  humidifier  as  time  goes  on.     A 

solid red LED Service indicator light may light up.  This will tell 

you that it is time to service your humidifier.  Please refer the 

following procedure.

1.  Adjust Humidistat to the lowest setting to ensure that 

• 

DIP Switch #4: Off

• 

Air Proving Switch: Recommended but not required.  

If no air proving switch is used, install a jumper across 

the AP1/AP2 terminals

• 

Go Terminal: No Connection

• 

W/G Terminal: Connected to System “W”

Multi Stage/Modulating Furnace: Humidifier operates upon 

call-for-humidity only during a call-for-heat.

• 

DIP Switch #3: Off

• 

DIP Switch #4: Off

• 

Air Proving Switch: Required

• 

Go Terminal: No Connection

• 

W/G Terminal: No Connection

Single or Multi Stage Furnace: Humidifier operates upon a 

call-for-humidity and will start the HVAC blower.

• 

DIP Switch #3: Off

• 

DIP Switch #4: On

• 

Air Proving Switch: Recommended but not required.  

If no air proving switch is used, install a jumper across 

the AP1/AP2 terminals

• 

Go Terminal: Connected to System “G”

• 

W/G Terminal: No Connection

Although the capacity of the humidifier may be reduced by 

more than 40%, the PF845412 may be installed on a heat 

pump system and configured to operate only when there is a 

call-for-heat OR the humidifier may be configured to start the 

HVAC blower whenever there is a call-for-humidity.

Heat Pump System: Humidifier operates upon call-for-

humidity only during a call-for-heat.

• 

DIP Switch #3: Off

• 

DIP Switch #4: Off

• 

Air Proving Switch: Required

• 

Go Terminal: No Connection

• 

W/G Terminal: No Connection

Heat Pump System: Humidifier operates upon a call-for-

humidity and will start the HVAC blower.

• 

DIP Switch #3: Off

• 

DIP Switch #4: On

• 

Air Proving Switch: Recommended but not required.

If no air proving switch is used, install a jumper across 

the AP1/AP2 terminals

• 

Go Terminal: Connected to System “G”

• 

W/G Terminal: No Connection

5. Operation

Once the PF845411/PF845412 is installed and ready to be start-

ed, the humidistat and DIP switches on the control board within 

the humidifier unit must be confirgured.  The PF845411 without 

the water saving controls does not have any DIP switches to 

configure.  You may skip to the Preliminary Checkout and Start-

up Sequence.

DIP Switches/Settings:

• 

DIP #1 = Bypass or Motorized (Factory Set)

• 

DIP  #2  =  High  Capacity/Low  Capacity  - This  is  factory 

set to High Capacity.  If you determine that the humidfiier 

Содержание PF845411

Страница 1: ...PreferredTM Fan Powered Evaporative Humidifier PF845411 PF845412 READ AND SAVE THESE INSTRUCTIONS...

Страница 2: ...pecifications Table 4 3 3 What s in the Box 4 4 Installation 4 4 1 Clearances 4 4 2 Mounting 4 4 3 Plumbing 6 4 4 Electrical Wiring 7 4 4 1 Wiring PF845411 without water saving controls 7 4 4 2 Wiring...

Страница 3: ...talling contractor or distributor Normally the installing contractor from whom the unit was purchased will be able to take the necessary corrective action by ob taining through his Preferred distribut...

Страница 4: ...in the recommended range of 30 40 relative humidity assures automatic humidity control during the heating season A lower setting may be necessary to prevent condensation on windows An electronic humi...

Страница 5: ...at range is 30 40 relative hu midity If condensation occurs on windows the humidistat setting must be lowered to prevent condensation damage DO NOT install the humidifier where freezing temperatures m...

Страница 6: ...at may have accumulated in the line during the in stallation process Once this is complete close the saddle valve 3 Attach the line to the humidifier by simply pushing the line into the push to lock f...

Страница 7: ...o vide means of overload protection as required SOLENOID VALVE YEL YEL BLK WHT GRN MOTOR DUCT THERMISTOR UNIT THERMISTOR MANUAL HUMIDISTAT SWITCH AIR PROVING HUMIDISTAT ELECTRONIC OR TERMINALS SEE FRO...

Страница 8: ...be disconnected from all sources of electricity 6 1 Pad Replacement It will become necessary to replace the pad inside your Pre ferredTM PF845411 PF845412 humidifier as time goes on A solid red LED Se...

Страница 9: ...rcuit board if equipped or disconnect the 3 wire connector 7 Lift the entire dome from the base of the unit by pulling the bottom of the dome away from the base and then lifting it off of the base See...

Страница 10: ...l continue to op erate and the LED may be cleared by pressing the reset button on the control board 6 3 Motor Replacement 1 Follow steps 1 7 in the pad replacement section in order to separate the dom...

Страница 11: ...ailed fuse is blown Replace circuit board Motor will not operate turn Motor internal thermal protective device is open Remove power and allow motor to cool Restart unit and ensure proper operation If...

Страница 12: ...PreferredTM Model PF845411 PF845412 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 12 Preferred Products 11 10 3 13 22 12 Figure 17...

Страница 13: ...PreferredTM Model PF845411 PF845412 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 13 Preferred Products 29 7 8 14 6 21 16 15 1 16 18 17 20 20 4 Figure 18...

Страница 14: ...PreferredTM Model PF845411 PF845412 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 14 Preferred Products 29 7 9 14 6 25 19 16 15 1 16 17 2 Figure 19...

Страница 15: ...11 266371 001 MOTOR MAIN DOME 1 1 12 265462 001 MOTOR CAP 1 1 13 265463 001 DOME ACCESS DOOR 1 1 14 265470 001 PAD EVAPORATOR 1 1 15 265471 001P PAINT BRACKET SOLENOID VALVE 2 2 16 265698 001 PNEUMATI...

Страница 16: ...Form No 265817 004 rev 10182012 2011 All Rights Reserved Preferred Products 4744 Island Ford Rd Randleman NC 27317 www askpreferred com...

Отзывы: