Pressure  Range  Conversion: 

The controller pressure range can be set in the field to either: 
  

 

 

0” to +2”  or  0” to -2” 

  

Changing the Control Range:    0  to -2”wc   versus   0 to + 2”wc   

1) 

Disconnect all electrical power sources, multiple disconnects many be 
required.

 

2) 

Disconnect the external sample line.

 

3) 

Remove the two mounting screws next to sample line connection.

 

4) 

Remove the Controller and un-plug the cable connected to the board.

 

5) 

Connect the sample line and set the DIP switch as follows:

 

 
For   0  to  

-2”

   operation 

Attach the sample tube to:  sensor port  

P1

 

Set DIP switch 4 to:  

OFF

 

 

For  0  to  

+2”

   operation 

Attach the sample tube to:  sensor port  

P2

 

Set DIP switch 4 to:  

ON 

 

6) 

Reverse steps 4 thru 1 to re-assemble.

 

 

P2

TRANSFORMER

P1

PRESSURE 

SENSOR

DIP SWITCH

PRESSURE PID CONTROLLER BOARD

(REAR VIEW)

0" TO 

-2"

RANGE IS SHOWN

(FACTORY CONFIGURATION)

OFF

ON

1 2 3 4

Содержание JC-22-PL2-1006

Страница 1: ...u uf f fa a ac c ct t tu u ur r ri iin n ng g g C C Co o or r rp p po o or r ra a at t ti iio o on n n J J JC C C 2 2 22 2 2 P P PL L L2 2 2 1 1 10 0 00 0 06 6 6 D D DR R RA A AF F FT T T R R RE E EG...

Страница 2: ...turing Corp Phone 203 743 6741 Fax 203 798 7313 www preferredinstruments com Installation and Operation Manual JC 22 PL2 1006 rev 6 6 5 17 Page 2 of 12 Table of Contents A Description 5 B Specificatio...

Страница 3: ...he burner and all applicable burner boiler safety codes should install configure and commission the JC 22 PL2 1006 Incorrect installation can result in equipment damage injury or death Note All rights...

Страница 4: ...erred Instruments Div of Preferred Utilities Manufacturing Corp Phone 203 743 6741 Fax 203 798 7313 www preferredinstruments com Installation and Operation Manual JC 22 PL2 1006 rev 6 6 5 17 Page 4 of...

Страница 5: ...ur miniature dials for adjusting the set point proportional band damping and dead band Base on the inputs the microcomputer activates two solid state relays one for opening the damper and the other fo...

Страница 6: ...table from 0 100 corresponds to 0 to 2 0 w c or 0 to 2 0 w c see pg 12 to change Dampening Adjustable from 0 100 corresponds to 1 5 to 15 seconds For 90 response to a step change Dead Band Adjustable...

Страница 7: ...ice panel not intermediate sub panels to the damper controller The ground path needs to be low impedance less than 1 ohm to the equipment frame which in turn needs low impedance to earth ground For a...

Страница 8: ...Operating Limit switch type Burner Flame Safeguard Typical Wiring Diagram for JC 22 PL2 1006 Draft Controller with JC 22 xDPCO 8 Draft Cutout NOTE Burner Boiler wiring diagrams vary significantly fro...

Страница 9: ...n dry contact Contacts make when damper is fully open Consult burner mfg for proper flame safeguard interface connection Typically wired in series with flame safeguard Start Ignition interlocks D Oper...

Страница 10: ...The factory set range 0 to 2 or 0 to 2 is indicated on the label near the adjustment pots The range can be changed by following the directions on page 12 2 Damping Turn clockwise to reduce actuator hu...

Страница 11: ...erredinstruments com Installation and Operation Manual JC 22 PL2 1006 rev 6 6 5 17 Page 11 of 12 LED Indicators INCREASE yellow The ram tube is extending which opens the damper DECREASE yellow The ram...

Страница 12: ...le disconnects many be required 2 Disconnect the external sample line 3 Remove the two mounting screws next to sample line connection 4 Remove the Controller and un plug the cable connected to the boa...

Отзывы: