ProtEX-MAX PD8-6001 Explosion-Proof Feet & Inches Meter Instruction Manual
49
Select Menu (
SElect
)
The
Select
menu is used to select the signal input conditioner applied
to the input (linear or round horizontal tank), low-flow cutoff, and analog output programming. The multi-
point linearization is part of the linear function selection.
Signal Input Conditioning (
Functn
)
The
Function
menu is used to select the signal input conditioner
applied to the input: linear or round horizontal tank volume calculation. Multi-point linearization is part of
the linear function selection.
Meters are set up at the factory for linear function with 2-point linearization. The linear function provides a
display that is linear with respect to the input signal.
Multi-Point Linearization (
Linear
)
Meters are set up at the factory for linear function with 2-point linearization. Up to 32 linearization points
can be selected for PV1 under the linear function. The multi-point linearization can be used to linearize
the display for non-linear signals such as those from level transmitters used to measure volume in odd-
shaped tanks or to convert level to flow using weirs and flumes with complex exponent.
If the dual-scale level feature has been selected, the menus for PV1 & PV2 are enabled. PV2 can be
programmed with up to 8 linearization points.