ProtEX-MAX PD8-7000 Explosion-Proof Temperature Meter Instruction Manual
18
Figure 12: RS-485 Two-Wire Multi-Drop Wiring
Notes:
1. Termination resistors are optional and values depend on the cable length and characteristic im-
pedance. Consult the cable manufacturer for recommendations.
2. Refer to RS-232 to RS-485 Converter documentation for further details.
3. Use shielded cable, twisted-pair plus ground. Connect ground shield only at one location.
WARNING
Observe all safety regulations. Electrical wiring should be performed
in accordance with all agency requirements and applicable national,
state, and local codes to prevent damage to the meter and ensure
personnel safety.
When using more than one instrument in a multi-drop or multi-point mode, each meter must be provided
with its own unique address.
Using
P
RO
V
U
Serial Adapters
NOTICE
P
RO
V
U
expansion modules and serial adapters are not included in
the hazardous area approvals of the ProtEX-MAX. The PDA1232
may be used only while the ProtEX-MAX is in a safe area, and will
disable some features while installed.
P
RO
V
U
expansion modules and serial adapters are not recommended for use with the ProtEX-MAX. It is
recommended that any serial protocol conversion required on the RS-485 communications connection be
performed using a PDA7485 RS-232 to RS-485 or PDA8485 USB to RS-485 serial converter located in a
safe area.
!