PD663 Loop-Powered Meter
Instruction Manual
28
Maximum & Minimum Readings (
HI
&
LO
)
The maximum and minimum (peak & valley) readings reached by the process
are stored in the meter since the last reset or power-up. The meter flashes
HI
or
LO
to differentiate between run mode and max/min display.
Press
Up
to Display and to
Toggle Between Max & Min
10 Sec Time Out
16.62
Run Mode
HI
LO
Press
Enter
to Hold Max/Min
Press
Right
to Reset Max/Min
Press
Menu
to Exit Max/Min
19.45
5.34
Press
Up
arrow button to display maximum reading since the last reset/power-
up.
Press
Up
arrow again to display the minimum reading since the last reset/power-
up.
Press
Enter
to continue to display the Max or Min display reading by disabling
the Max/Min timeout. The meter will continue to track new Max/Min readings.
Press MENU to exit the Max/Min reading.
If
Enter
is not pressed, the Max/Min display reading will continue to flash and
time out after ten seconds. The meter will return to display the actual reading.
Press
Right
arrow button while in Max/Min Mode to reset both Max and Min.
Max/Min display readings are reset to the current reading.