PD2-6210
Helios Large Display Analog Input Batch Controller Instruction Manual
13
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12-24 VDC power option, are shipped from the factory
configured to provide 24 VDC power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the switch labeled P+/P- must be configured
accordingly.
To access the voltage selection jumper:
1. Unplug the meter power.
2. Unscrew and open the front door panel.
3. Locate the P+/P- switch located in the center of the connections board (see diagram below).
4. Flip this switch into the appropriate position for the required transmitter excitation.
Figure 6. Transmitter Supply Voltage Selection
Connections
All connections are made to screw terminal connectors located under the front door panel. Remove the
single securing screw in order to access the wiring terminals.
Caution
Use copper wire with 60°C or 60/75°C
insulation for all line voltage connections.
Observe all safety regulations. Electrical
wiring should be performed in accordance
with all applicable national, state, and local
codes to prevent damage to the meter and
ensure personnel safety.
MENU
START
F1
BATCH
F2
STOP
F3
www.calcert.com
1.888.610.7664
0
5
10
15
20
25
30