speciFications

Except where noted all specifications apply to operation at +25°C.

General

ModeL pd684 & pd689 Loop-powered rate/totaLizers

YoUr LocaL distriBUtor is: 

Display:

  5  digit  LCD  (-99999  to  99999),  0.60"  (15.2  mm)  high, 

7-segment, automatic lead zero blanking. 

 

Engineering Units: 

0.25

"

 (6.4 mm) high, 14-segment

 Bargraph

: 20-segment, 0-100% indication

 Trend Arrows: 

Up and down trend indication

 Backlight: 

Bright orange LED (intensity varies with signal)

Front Panel: 

FM Type 4X, IP65; panel gasket provided

Display Update Rate: 

2.5/second

Overrange:

 Display flashes 99999

Underrange:

 Display flashes -99999

Programming Method:

 Four front panel buttons

Noise Filter:

 Programmable from 1 to 199

Recalibration: 

Recommended at least every 12 months

Max/Min  Display: 

Max/min  readings  reached  by  the  process  are 

stored until reset by the user or until power to the meter is turned off. 

Password: 

Programmable  password  restricts  modification  of 

programmed settings.

Non-Volatile  Memory: 

All  programmed  settings  are  stored  in 

non-volatile memory for a minimum of ten years if power is lost.

Voltage Drop:

 2.0 V max w/o backlight, 5.7 V max with backlight

Equivalent Resistance:

 125 Ω @ 20 mA without backlight,    

315 Ω @ 20 mA with backlight. 

Normal Mode Rejection:

 64 dB at 50/60 Hz

Operating Temperature Range:

 -20 to 65°C

Allowable Temperature Range:

 -40 to 65°C* (see note below)  

Storage Temperature Range:

 -40 to 85°C

 Relative Humidity:

 0 to 90% non-condensing

Connections: 

Screw terminals accept 12 to 22 AWG wire

Enclosure: 

1/8 DIN, high impact plastic, UL 94V-0, color: gray

Mounting:

   1/8  DIN  panel  cutout  required.  Two  panel  mounting 

bracket assemblies provided.

Tightening Torque:

 4.5 lb-in (0.5 Nm) Screw terminal connectors

Overall  Dimensions: 

4.68"  x  2.45"  x  3.79"  (119  x  62  x  96  mm) 

Weight:

 5.7 oz (162 g)

Warranty:

 3 years parts and labor

Extended Warranty:

 1 or 2 years, refer to Price List for details

* Below -20°C the LCD becomes less readable. See application note AN-1005.

Input

Input Range: 

4-20 mA

Accuracy:

 ±0.03% of span ±1 count, square root and 

programmable exponent: 10-100% FS.

Calibration:

 Scale without signal or calibrate with signal source

Calibration Range:

 User programmable over entire range of meter 

Minimum Span:

 0.40 mA between input 1 and input 2

 

Note:

 An Error message will appear if input 1 and input 2 signals are too close together.

Input Overload:

 Over current protection to 2 A maximum

Decimal Point:

 Up to 4 places 

(d.dddd, dd.ddd, ddd.dd, dddd.d, or ddddd)

Function:

 Linear, square root, or programmable exponent

Low-Flow Cutoff:

 -99999 to 99999 

(-99999 disables cutoff function)

Temperature Drift:

 50 PPM/°C from -40 to 65°C ambient

Totalizer Features

Total Display:

 0 to 99,999 main total display plus 0 to 999 total 

overflow for a combined 8 digit total of 99,999,999.

Alternating Display: 

Totalizer may be programmed to alternate 

between rate and total every 10 seconds.

Time Base: 

Seconds, minutes, hours, or days

Totalizer Conversion Factor: 

0.0001 to 99999

Totalizer: 

Calculates  total  based  on  rate,  time  base  of  second, 

minute, hour, or day, and field programmable multiplier; stored in 

non-volatile memory upon power loss.

Totalizer Rollover: 

Total rolls over when total exceeds 99,999,999.

Totalizer  Reset: 

Manual  reset  or  automatic  with  time  delay,  or 

disabled for non-resettable total applications.

Open Collector Output

Rating:

 Isolated open collector, 30 VDC @ 175 mA max

imum

Alarm Output:

 Assign to rate or total, high or low rate alarm.

Deadband:

 0-100% FS, user selectable

Acknowledge

: ACK button resets output and screen indication.

Automatic Reset:

 Alarm resets automatically when signal reaches 

the reset point.

Pulse Output:

 250 pulses/sec max; pulse width: 3 ms, fixed. If the 

pulse  output  exceeds  250  pulses/sec,  counts  are  accumulated  as 

pending and are not lost. One pulse per total increment, programmable 

from 0.0001 to 99999 (decimal point based on total selection).

PD689 Approvals for Hazardous Locations

FM Approved & CSA Certified as intrinsically safe with entity for 
use in Class I, Div 1, Groups ABCD; Class II, Div 1, Groups EFG; 

Class III, Div 1; Class I, Zone 0, Group IIC; T-code = T4.

Non-incendive: Suitable for use in Class I, Div 2, Groups ABCD; 

Class II, Div 2, Groups FG; Class III, Div 2.

Entity Parameters:

 

U

i

: 30 V;

 I

i

: 175 mA; 

C

i

: 0; 

L

i

: 0; 

P

i

: 1.0 W

 

Note:

 Installation must be performed in accordance with Control Drawing LIM688-2

ordering inForMation

Model

Description

PD684-0K1

Loop Leader™ PRT

Rate/Totalizer for Safe Area

PD689-0K1

Loop Leader™ PTH

Rate/Totalizer FM & CSA 

Enclosures

Model

Meters Description

Mounting

PDA24

XX

1 - 4 *

Plastic NEMA 4X

Inside Cover

PDA26

XX

 

1 - 6 *

Stainless Steel NEMA 4X 

Through Door 

PDA27

XX

 

1 - 6 *

Steel NEMA 4X 

Through Door

PDA2801

1

Low-Cost NEMA 4X

Through Cover

Note: 

XX

 = the last two digits of the model number.

* Go to 

www.predig.com

 to find individual model numbers

Disclaimer

The  Information  contained  in  this  document  is  subject  to  change  without  notice.  Precision  Digital 

Corporation  makes  no  representations  or  warranties  with  respect  to  the  contents  hereof,  and 

specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.  

©2006 Precision Digital Corporation. all rights reserved

Отзывы: