PD6310 Pulse Input Batch Controller Instruction Manual
15
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the connector terminals labeled MA OUT.
The 4-20 mA output may be powered internally or from an external power supply.
Figure 17: 4-20 mA Output Connections
Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be used to power other devices, if the
analog output is not used. The I+ terminal is the +24 V and the R terminal is the return.
External Relay & Digital I/O Connections
The relay and the digital I/O expansion modules PDA1004 & PDA1044 are connected to the controller
using a CAT5 cable provided with each module. The two RJ45 connectors on the expansion modules are
identical and interchangeable; they are used to connect additional modules to the system.
Note: The jumper located between the RJ45 connectors of the PDA1044 must be removed on the second
digital I/O module in order for the system to recognize it as module #2.
Warning!
Do not connect or disconnect the expansion
modules with the power on!
More detailed instructions are provided with each
optional expansion module.
Figure 18: Expansion Modules & DIN Rail
Mounting Kit
Figure 19: External Relays Module
Connections
Figure 20: Digital I/O Module Connections
12-35 VDC
Power
Supply
+
4-20 mA
Input Meter
-
+
R
I-
I+
1
3
2
RELAY1
3
2
1
24 V
-
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
-
+
R
I-
I+
MA OUT
1
3
2
RELAY1
3
2
1
24 V
MA OUT
1
2
RLY5
RLY6
RLY7
RLY8
3
4
5
6
7
8
NO
C
NO
C
NO
C
NO
C
1
2
3
4
5
6
+5
I1
I2
I3
I4
O1
7
8
O2
O3
9
10
O4
G
DI 1-4
DO 1-4
5 VDC
GND
www.
GlobalTestSupply
.com
Find Quality Products Online at: