Model PD6300 Pulse Input Rate/Totalizer
Instruction Manual
11
DECIMAL POINT
Up to five decimal places or none:
d.ddddd
,
d.dddd
,
d.ddd
,
d.dd
,
d.d
,
or
dddddd
CALIBRATION
May be calibrated using K-factor, internal calibration, or by
applying an external calibration signal.
K-FACTOR
Field programmable K-factor converts input pulses to rate in
engineering units. May be programmed from 0.00001 to
999,999 pulses/unit.
CALIBRATION
RANGE
Input 1 signal may be set anywhere in the range of the
meter; input 2 signal may be set anywhere above or below
input 1 setting.
Minimum input span between any two inputs is 10 Hz.
An Error message will appear if the input 1 and input 2
signals are too close together.
FILTER
Programmable contact de-bounce filter: 40 to 999 Hz max-
imum input frequency allowed with low speed filter.
TIME BASE
Second, minute, hour, or day
GATE
Low gate: 0.1-99.9 seconds
High gate: 2.0-999.9 seconds
Rate/Totalizer
DISPLAY
ASSIGNMENT
The main (Big) and small (Little) displays may be assigned
to rate, total, grand total, alternate R & T, units, and set
point.
RATE DISPLAY
INDICATION
-99999 to 999999, lead zero blanking. “R” LED illuminates
while displaying rate or frequency.
TOTAL DISPLAY
& TOTAL
OVERFLOW
0 to 999,999; automatic lead zero blanking. “T” LED is illumi-
nated while displaying total or grand total.
Up to 999,999,999 with total-overflow feature. “
oF
” is dis-
played to the left of total overflow and
▲
LED is illuminated.
ALTERNATING
DISPLAY
Either display may be programmed to alternate between
rate and total or rate and grand total every 10 seconds.
TOTAL
DECIMAL POINT
Up to five decimal places or none:
d.ddddd
,
d.dddd
,
d.ddd
,
d.dd
,
d.d
,
or
dddddd
Total decimal point is independent of rate decimal point.
TOTALIZER
Calculates total based on rate and field programmable mul-
tiplier to display total in engineering units. Time base must
be selected according to the time units in which the rate is
displayed.
TOTALIZER
ROLLOVER
Totalizer rolls over when display exceeds 999,999,999.
Relay status reflects display.