Process Input
Inputs
Field selectable: 0-20, 4-20 mA
10 V (0-5, 1-5, 0-10 V)
Modbus PV (Slave)
Isolated
Transmitter
Power Supply
Terminals P+ & P-: 24 VDC
10%.
All models selectable for 24, 10, or 5 VDC
supply (internal jumper J4). 85-265 VAC
models rated @ 200 mA max, 12-24 VDC
powered models rated @ 100 mA max.
5 & 10 VDC supply rated @ 50 mA max. Refer
to
Figure 4. Transmitter Supply Voltage
on page
When the Light / Horn is powered by the
transmitter power supply, see MOD-LH Light
/ Horn's transmitter power supply
specification in MOD-LH manual for
additional details. Light / Horn power not
available for 5 or 10 VDC supplies.
Accuracy
±0.03% of calibrated span ±1 count,
square root & programmable exponent
accuracy range: 10-100% of calibrated span
Temperature
Drift
0.005% of calibrated span/
C max from
0 to 65
C ambient, 0.01% of calibrated
span/
C max from -40 to 0
C ambient
Input Signal
Conditioning
Linear, square root, or programmable
exponent
Multi-Point
Linearization
2 to 32 points
Programmable
Exponent
User selectable from 1.0001 to 2.9999 for
open channel flow
Low-Flow
Cutoff
0.1 to 999,999 (0 disables cutoff function).
Point below at which the display always
shows zero.
Decimal Point
Up to five decimal places or none:
d.ddddd
,
d.dddd
,
d.ddd
,
d.dd
,
d.d
, or
dddddd
Calibration
Range
Input Range
Minimum Span
Input 1 & Input 2
4-20 mA
0.15 mA
10 V
0.10 V
An error message will appear if the input 1
and input 2 signals are too close together.
Input
Impedance
Voltage ranges: greater than 500 k
Current ranges: 50 - 100
(depending on
resettable fuse impedance)
Input Overload
Current input protected by resettable fuse,
30 VDC max. Fuse resets automatically
after fault is removed.
HART
Transparency
The controller does not interfere with
existing HART communications; it displays
the 4-20 mA primary variable and it allows
the HART communications to pass through
without interruption. The controller is not
affected if a HART communicator is
connected to the loop. The controller does
not display secondary HART variables.
Relays
Rating
2 or 4 SPDT (Form C) internal and/or
4 SPST (Form A) external; rated 3 A
@ 30 VDC and 125/250 VAC resistive load;
1/14 HP (
≈
50 W) @ 125/250 VAC for
inductive loads
Noise
Suppression
Noise suppression is recommended for
each relay contact switching inductive
loads; see
Relay
Assignment
Relays may be assigned to batch control
total, sampling, rate, or grand total alarms.
Pre-Close
0-100% of batch size, individually user
programmable for each additional batch
control relay beyond the first.
Alarm
Deadband
0-100% of span, user programmable
High or Low
Flow Alarm
User may program any alarm for high or
low trip point. The alarm detection is active
only while the batch is running. Unused
alarm LEDs and relays may be disabled
(turn off).
Relay
Operation
•
Manual or automatic batch control
•
Automatic (non-latching)
1
and/or manual
alarm reset (acknowledge)
•
Latching (requires manual
acknowledge) with or without clear
•
Pump alternation control (N/A to batch)
•
Sampling (based on set point and time)
•
Off (disable unused relays and enable
Interlock feature)
•
Manual on/off control mode
Relay Reset
(Acknowledge)
User selectable via front panel buttons, F4
terminal at back of controller, external
contact closure on digital inputs,
automatically via user selectable preset
value and time delay, or through serial
communications.
Alarm Time
Delay
0 to 999.9 seconds, on & off relay time
delays. Programmable and independent for
each relay.
Fail-Safe
Operation
Programmable and independent for each
relay.
Note: Relay coil is energized in non-alarm
condition. In case of power failure, relay will
go to alarm state.
Alarm Auto
Initialization
When power is applied to the controller,
relays will reflect the state of the input to
the controller.
1
Additional
Relays
An external module, model
, is
available to add 4 SPST 3 A relays to the
controller.
1. Alarms are active only when the batch is running.