Loop Leader PD6620 Series Loop-Powered Flow Rate/Totalizers
Instruction Manual
10
I.S. Equipment
Entity
Parameters
Required
Relationship
Between Entity
Parameters
I.S. Barrier Entity
Parameters
V max (or Ui)
≥
Voc or Vt (or Uo)
I max (or Ii)
≥
Isc or It (or Io)
P max, Pi
≥
Po
Ci + Ccable
≤
Ca (or Co)
Li + Lcable
≤
La (or Lo)
•
For Division 2 and Zone 2 Applications:
Division 2 and Zone 2 installations do NOT require
the use of an intrinsically-safe barrier or
intrinsically-safe entity parameters. Class I,
Division 2, Groups A, B, C, and D T4 and Class I,
Zone 2, Group IIC T4, -40C <= Ta <= +70C.
Ratings: V = 30 V dc, I = 30 mA; Relay Ratings:
250V ac/dc 1A
For North American Community:
Installation and service of this device and/or
associated apparatus (barrier) should be performed
only by trained service personnel
and must be installed in accordance with the
manufacturer’s control drawing, Article 504 of the
National Electric Code (ANSI/NFPA 70) for installation
in the United States, or Section 18 of the Canadian
Electrical Code for installations in Canada.
•
EXPLOSION HAZARD
– Do not disconnect
equipment unless power has been removed or the
area is known to be non-hazardous
•
RISQUE D’EXPLOSION
– NE PAS BRANCHER NI
DÉBRANCHER SOUS TENSION.
Year of Construction
This information is contained within the serial number
with the first four digits representing the year and
month in the YYMM format.
Safety Information
• Read complete instructions prior to installation and
operation of the meter.
• Risk of electric shock or personal injury.
• Hazardous voltages exist within enclosure.
Installation and service should be performed only
by trained service personnel.
• Service requiring replacement of internal
components must be performed at the factory.
• Control room equipment must not use or generate
more than 250 VRMS or VDC.
• Hazardous location installation instructions for
associated apparatus (barrier) must be followed
when installing this equipment.
• For safe installation of an ATEX approved
transmitter in series with PD6626/PD6628 loop-
powered meters, the hazardous location installation
instructions for the transmitter, PD6626/PD6628
loop-powered meter, and associated apparatus
(barrier) must be compatible.
• PD6626/PD6628 Series Loop-Powered meters do
not add capacitance or inductance to the loop
under normal or fault conditions.
• Substitution of components may impair hazardous
location safety.
• Equipment contains non-metallic materials and
therefore special care and consideration should be
made to the performance of these materials with
respect to chemicals which may be present in a
hazardous environment.