24
Effect of supply voltage
change (24...250 VAC / VDC) ...................... < ±10
µA
Max. wire size .............................................. 1 x 2.5 mm
2
stranded wire
Screw terminal torsion ................................ 0.5 Nm
Relative humidity ......................................... < 95% RH (non-cond.)
Dimensions (HxWxD) ................................... 109 x 23.5 x 130 mm
DIN rail type ................................................. DIN 46277
Protection degree ........................................ IP20
Weight ......................................................... 260 g
Current inputs:
Measurement range .................................... 4...20 mA
Min. measurement range (span).................. 16 mA
Input resistance:
Supplied unit ........................................... 10
Ω
+ PTC, V
DROP
< 1.3 V
Non-supplied unit ................................... R
SHUNT
=
∞
, V
DROP
< 3.5 V
Current outputs:
Signal range (span) ...................................... 4...20 mA
Min. signal range (span) .............................. 16 mA
Load (max.) .................................................. 20 mA / 800
Ω
/ 16 VDC
Load stability ...............................................
≤
0.01% of span / 100
Ω
Current limit .................................................
≤
28 mA
EEx / I.S. approval:
DEMKO 01ATEX127484 ..............................
II (1) GD
[EEx ia] IIC
Applicable for zone ..................................... 0, 1, 2, 20, 21 or 22
Ex / I.S. data:
Um ............................................................... : 250 V
Uo ................................................................ : 28 VDC
I o ................................................................ : 93 mADC
Po ................................................................ : 0.644 W
Lo ................................................................ : 3 mH
Co ................................................................ :
0.08 µF
EMC immunity influence ..................................... < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst ....................... < ±1% of span
Содержание Hart 5107B
Страница 10: ...8 I P mA I P Konverter Strøm mA Indgang Indgang Forsyning Forsyning Applikationer ...
Страница 16: ...14 ...
Страница 24: ...22 I P mA Input Input Supply Supply Current mA I P Converter Applications ...
Страница 30: ...28 ...
Страница 38: ...36 I P mA Alimen Courant mA Alimen Convertisseur I P Entrée Entrée Applications ...
Страница 44: ...42 ...
Страница 52: ...50 I P mA Versorgung Versorgung Strom mA I P Konverter Eingang Eingang Anwendungen ...
Страница 58: ...56 ...
Страница 59: ...57 Appendix UL Control Drawing No 5107QU01 ...