9106QF01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2016-11-30
Version Revision
V4 R0
Prepared by:
PB
Page:
1/5
FM Installation drawing
For safe installation of 9106B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
For Installation in Div2/Zone2 the following must be observed.
The 4501 programming module is to be used solely with PRelectronics modules. It is important
that the module is undamaged and has not been altered or modified in any way. Only 4501
modules free of dust and moisture shall be installed.
9106B1A: 1 channel HART
®
-transparent repeater (27.5 V Barrier)
9106B1B: 2 channel HART
®
-transparent repeater (27.5 V Barrier)
9106B2A: 1 channel HART
®
-transparent repeater (25.3 V Barrier)
9106B2B: 2 channel HART
®
-transparent repeater (25.3 V Barrier)
Supply terminal
(31,32)
Voltage:
19.2 – 31.2VDC
Status Relay
. terminal (33,34)
Zone 2 installation
Voltage max:
125 VAC / 110 VDC
32 VAC / 32 VDC
Power max:
62.5 VA / 32 W
16 VA / 32 W
Current max:
0.5 A AC / 0.3 ADC
0.5 A AC / 1 ADC
Installation notes:
In Class I, Division 2 installations, the subject equipment shall be mounted within a tool-secured
enclosure which is capable of accepting one or more of the Class I, Division 2 wiring methods
specified in the National Electrical Code (ANSI/NFPA 70) or Canadian Electrical Code (C22.1).
The equipment shall be installed in an enclosure with a minimum ingress protection rating of IP54
unless the apparatus is intended to be afforded an equivalent degree of protection by location.
The module is galvanically isolated and does not require grounding.
Install in pollution degree 2, overvoltage category II.
Use 60 / 75 ºC copper conductors with wire size AWG: (26-14)
Warning
: Substitution of components may impair intrinsic safety.
Warning
: To prevent ignition of the explosive atmospheres, disconnect power before servicing
and do not separate connectors, install or remove module from Power Rail when energized and
an explosive gas mixture is present.
Warning:
The Loop Supply and Current Input terminals for the same channel shall not be applied
at the same time. The wiring of unused terminals is not allowed.
FM Installation Drawing
9106 - Product version 9106-002
31