30 4116V105-UK

Relay latched

OFF delay

ON delay

Input 

signal

Hysteresis

Setpoint 

(increasing)

Time

Closed

Open

Relay contact 

(N.O.)

Release not possible (setpoint still exceeded)

Release not possible (setpoint-hysteresis still exceeded)

Release not possible (OFF delay still exceeded)

Release possible (manual deactivation)

Graphic depiction of latch function setpoint

Содержание 4116

Страница 1: ...PERFORMANCE MADE SMARTER R Product manual 4116 Universal transmitter TEMPERATURE I S INTERFACES COMMUNICATION INTERFACES MULTIFUNCTIONAL ISOLATION DISPLAY No 4116V105 UK From serial no 121524001 ...

Страница 2: ...nsive easy to use future ready communication interfaces that can access your PR installed base of products All the interfaces are detachable have a built in display for readout of process values and diagnostics and can be configured via push buttons Product specific functionality includes communication via Modbus and Bluetooth and remote access using our PR Process Supervisor PPS application avail...

Страница 3: ...cal specifications 11 Visualisation in the 45xx of sensor error detection and input signal outside range 15 Sensor error dete ction limits 15 Error indications 16 Connections 17 Block diagram 18 Configuration operating the function keys 19 Routing diagram 23 Routing diagram advanced settings ADV SET 26 Routing diagram manual deactivation of the latch function 27 Help text overview 28 Graphic depic...

Страница 4: ...d by the equipment may be impaired Warning Until the device is fixed do not connect hazardous voltages to the device The following operations should only be carried out on a disconnected device and under ESD safe conditions General mounting connection and disconnection of wires Troubleshooting the device Repair of the device and replacement of circuit breakers must be done by PR electronics A S on...

Страница 5: ...ed by way of ventilation The device must be installed in pollution degree 2 or better Mounting Only technicians who are familiar with the technical terms warnings and instructions in the manual and who are able to follow these should connect the device Should there be any doubt as to the correct handling of the device please contact your local distributor or alternatively PR electronics A S www pr...

Страница 6: ...ns there is no electrical shock hazard and the device is easily accessible Cleaning When disconnected the device may be cleaned with a cloth moistened with distilled water Liability To the extent the instructions in this manual are not strictly observed the custom er cannot advance a demand against PR electronics A S that would otherwise exist according to the concluded sales agreement ...

Страница 7: ...ous measurement of the outgoing current is carried out on a 4 20 mA and 20 4 mA output signal If the current output signal is different from the internal calculated output value or the current output is 0 due to e g an open circuit breakage an error mode switches on the red front LED and disables the relays This function is not a default option but must be actively selected via the programming men...

Страница 8: ...ding to strict safety requirements and is thus suitable for application in SIL 2 installations Technical characteristics When 4116 is used in combination with the 45xx display programming units all operational parameters can be modified to suit any application As the 4116 is designed with electronic hardware switches it is not necessary to open the device for setting of DIP switches A green red fr...

Страница 9: ...4116V105 UK 9 Applications Supply 21 6 253 VAC or 19 2 300 VDC Output signals Input signals Current Volt age RTD and lin R TC Connect wires Relays Analog 0 4 20 mA and voltage Order separately 5910 CJC connector See the connection drawing on page 17 Potentio meter ...

Страница 10: ...out of process data and status Technical characteristics LCD display with 4 lines Line 1 H 5 57 mm shows the input signal Line 2 H 3 33 mm shows the selected engineering unit Line 3 H 3 33 mm shows analog output or TAG no Line 4 shows status for communication and relays Programming access can be blocked by assigning a password The password is saved in the device in order to ensure a high degree of...

Страница 11: ...51x 109 x 23 5 x 116 131 mm Weight approx 175 g Weight incl 4501 451x approx 190 g 205 g DIN rail type DIN EN 60715 35 mm Wire size 0 13 2 08 mm2 AWG 26 14 stranded wire Screw terminal torque 0 5 Nm Vibration IEC 60068 2 6 2 13 2 Hz 1 mm 13 2 100 Hz 0 7 g Common electrical specifications Supply voltage universal 21 6 253 VAC 50 60 Hz or 19 2 300 VDC Fuse 400 mA SB 250 VAC Max required power 2 5 W ...

Страница 12: ...max RTD 50 Ω Sensor current RTD Nom 0 2 mA Effect of sensor cable resistance 3 4 wire RTD 0 002 Ω Ω Sensor error detection RTD Yes Short circuit detection RTD 15 Ω EMC immunity influence 0 5 of span Extended EMC immunity NAMUR NE 21 A criterion burst 1 of span General values Input type Absolute accuracy Temperature coefficient All 0 1 of span 0 01 of span C Basic values Type Basic accuracy Tempera...

Страница 13: ...se 0 μA Current input Measurement range 0 23 mA Programmable measurement ranges 0 20 and 4 20 mA Input resistance Nom 20 Ω PTC 50 Ω Sensor error detection Loop break 4 20 mA Yes Voltage input Measurement range 0 12 VDC Programmable measurement ranges 0 1 0 2 1 0 5 1 5 0 10 and 2 10 VDC Input resistance nom 10 MΩ Output specifications Current output Signal range span 0 23 mA Programmable signal ran...

Страница 14: ...elay 30 VDC 2 ADC Urelay 30 VDC 1380 x U 2 relay x 1 0085 Urelay ADC Graphic depiction of 1380 x U 2 relay x 1 0085 Urelay Observed authority requirements EMC 2014 30 EU LVD 2014 35 EU RoHS 2011 65 EU EAC TR CU 020 2011 Approvals c UL us UL 508 E231911 FM 3025177 DNV GL TAA0000101 EU RO Mutual Recognition Type Approval MRA000000Z Functional Safety Hardware assessed for use in SIL applications FMED...

Страница 15: ... the polynomial is exceeded Input Range Readout Limit VOLT 0 1 V 0 2 1 V IN LO 25 mV IN HI 1 2 V 0 10 V 2 10 V IN LO 25 mV IN HI 12 V CURR 0 20 mA 4 20 mA IN LO 1 05 mA IN HI 25 05 mA LIN R 0 800 Ω IN LO 0 Ω IN HI 1075 Ω 0 10 kΩ IN LO 0 Ω IN HI 110 kΩ POTM IN LO 0 5 IN HI 100 5 TEMP TC RTD IN LO temperature range 2 C IN HI temperature range 2 C Sensor error detection SE BR SE SH Input Range Readou...

Страница 16: ... test 45xx 4116 NO CO Connection error Check that input signal matches input configuration IN ER 1 Error levels on input Check that saved configuration in 45xx matches device TY ER Configuration is not 4116 All error indications in the display flash once per second The help text explains the error If the error is a sensor error the display backlight flashes as well this is acknowledged stopped by ...

Страница 17: ...1 42 44 43 41 42 44 43 41 42 44 43 41 42 44 43 Tx 41 42 44 43 41 42 44 43 41 42 44 CJC Outputs Voltage 1 V Current Relays Voltage 10 V TC internal CJC sensor Resistance 2 wire RTD 3 4 wire RTD 2 wire Inputs Supply 2 wire transmitter Current Potentiometer Resistance 3 4 wire TC CJC connector Voltage Order separately CJC connector 5910 ...

Страница 18: ...A Vloop 14 13 12 31 33 22 21 23 11 24 2 4 3 V V 18 4116V105 UK Block diagram Potentiome t er 2 wire transmitter Voltage Current RTD og lin R connection wires Supply Supply 21 6 253 VAC or 19 2 300 VDC I I V Out I Out V Out TC Relay 2 Relay 2 Relay 1 Relay 1 Green Red Yellow Yellow Order separately CJC connector 5910 ...

Страница 19: ...figured password is not known please contact PR electronics support www prelectronics com contact Signal and sensor error info via display front 45xx Sensor error see limits in the table is displayed as SE BR sensor break or SE SH sensor short Signals outside the selected range not sensor error see table for limits are displayed as IN LO indicating low input signal or IN HI indicating high input s...

Страница 20: ... 31 Manual deactivation of the latch function If the relay outputs are activated and thereby latched it will be indicated in the display The backlight flashes and the scrolling help text tells you how to deactivate the output Manual deactivation is carried out by way of the front buttons on the 45x Use 1 and 2 to navigate in the menu and 3 to validate your selection If the password protection has ...

Страница 21: ...figuration in 45xx does not match this product type Selection of units After choosing the input signal type you can choose which process units should be displayed in text line 2 see table By selection of temperature input the process value is always displayed in Celsius or Fahrenheit This is selected in the menu point after selection of temperature input Safety readback When the device is delivere...

Страница 22: ...i SENSOR Txt 10 3 TC SENSOR Txt 10 3 100 Pt TYPE Txt 16 3 3W CONNEC Txt 6 100 Ni TYPE Txt 17 3 3W CONNEC Txt 6 TC K TC TYPE Txt 18 3 INT CJC Txt 63 10 1000 2W 3W 4W 1 2 1 2 50 1000 2W 3W 4W 1 2 1 2 22 4116V105 UK Fast setpoint adjustment and relay test 1 Increase setpoint 2 Decrease setpoint 3 Save and exit the menu 1 and 2 simultaneously change relay state 1 0 Default state Line 1 shows input sig...

Страница 23: ... R1 FUNC Txt 19 1 3 C UNIT Txt 9 C F 1 2 3 3 C F A bar cm ft ft h ft min ft s g gal h gal min GW hp hPa Hz in in h in min in s ips K kA kg kJ kPa kV kW kWh l l h l min l s m m h m min m s m s2 m3 m3 h m3 min mA mbar mils min mm mm s mol MPa mV MW MWh N Ohm Pa pH rpm s S t t h uA um uS V W Wh yd blank 3 3 3 3 3 3 4116V105 UK 23 Routing diagram If no key is activated for 1 minute the display will re...

Страница 24: ...1 2 50 0 R2 SETP Txt 21 100 0 0 0 1 2 3 INCR ACT DIR Txt 22 INCR DECR 1 2 3 1 0 R2 HYST Txt 23 100 0 0 0 1 2 SETP R2 FUNC Txt 19 SETP WIND ERR POW OFF 1 2 3 O I W R2 CONT Txt 27 3 O I W C I W 1 2 60 0 SETP LO Txt 29 100 0 0 0 1 2 3 70 0 SETP HI Txt 28 100 0 0 0 1 2 3 1 0 R2 HYST Txt 30 100 0 0 0 1 2 WIND R2 FUNC Txt 19 3 OPEN ERR ACT Txt 34 CLOS OPEN 1 2 ERR R2 FUNC Txt 19 3 POW R2 FUNC Txt 19 OFF...

Страница 25: ...EL Txt 33 3600 0000 1 2 3 3 CURR ANA OUT Txt 36 VOLT CURR 1 2 3 4 20 O RANGE Txt 37 S20 4 20 4 20 0 S4 20 4 20 0 20 3 VOLT ANA OUT Txt 36 3 0 10 O RANGE Txt 39 10 2 10 0 5 1 5 0 1 0 2 1 0 2 10 0 10 1 5 0 5 0 2 1 0 1 1 2 3 23mA OUT ERR Txt 38 23mA 0 3 5mA NONE 1 2 3 0 0 OUT LO Txt 41 850 200 1 2 3 150 0 OUT HI Txt 42 850 200 1 2 3 1 3 1 4 1 4 1 3 1 3 1 2 3 4116V105 UK 25 To default state 1 0 ...

Страница 26: ...YES USE CAL Txt 60 3 YES NO 1 2 SIM SETUP Txt 43 3 YES EN SIM Txt 51 3 YES NO 1 2 25 0 Txt 52 3 100 0 0 0 1 2 NO REL SIM Txt 53 3 LANG SETUP Txt 43 3 UK LANGUA Txt 59 DE DK ES FR IT SE UK PASS SETUP Txt 43 3 3 YES EN PASS Txt 54 YES NO 1 2 NO 0000 NEW PAS Txt 55 3 9999 0000 1 2 YES EN FAST Txt 56 3 YES NO 1 2 2 0 LATC SETUP Txt 43 3 NO R1 LATC Txt 64 3 3 NO R2 LATC Txt 64 3 YES NO 1 2 YES NO 1 2 1...

Страница 27: ... NO 1 2 NO R2 RLSE Txt 66 3 YES NO 1 2 0000 9999 1 2 0000 9999 1 2 40 0 R1 LATC Txt 65 40 0 R2 LATC Txt 65 1 2 NO ENT SET Txt 67 40 0 Rx LATC Txt 65 3 3 YES NO 1 2 3 1 1 1 5 1 1 1 5 4116V105 UK 27 To default state 1 0 R1 reset R2 reset To setup menu Routing diagram manual deactivation of the latch function ...

Страница 28: ...sensor type Select TC T as sensor type Select TC U as sensor type Select TC W3 as sensor type Select TC W5 as sensor type Select TC Lr as sensor type Select OFF function relay is permanently off Select POWER function relay indicates power status OK Select ERROR function relay indicates sensor error only Select WINDOW function relay controlled by 2 setpoints Select SETPOINT function relay controlle...

Страница 29: ... line 3 Device TAG is shown in display line 3 Calibrate input low to process value Calibrate input high to process value Enable simulation mode Set the input simulation value Relay simulation use 1 and 2 to toggle relay 1 and 2 Enable password protection Set new password Enable Fastset functionality Relay setpoint press 3 to save Relay setpoint Read only Select language Use process calibration val...

Страница 30: ...int increasing Time Closed Open Relay contact N O Release not possible setpoint still exceeded Release not possible setpoint hysteresis still exceeded Release not possible OFF delay still exceeded Release possible manual deactivation Graphic depiction of latch function setpoint ...

Страница 31: ...losed Open Relay contact N O Release not possible still inside window Release not possible inside hysteresis Release not possible OFF delay still active Release possible Time Window ON delay OFF delay Setpoint low Graphic depiction of latch function window Hysteresis Hysteresis ...

Страница 32: ...1 2 2 On On On 32 4116V105 UK Relay units Relay units Setpoint 50 Hysteresis 10 Hysteresis 10 Setpoint 50 Relay action Increasing Relay action Decreasing Relay units Setpoint High 60 Hysteresis 5 Hysteresis 5 Setpoint Low 40 Relay function Window shown for increasing signal Contact Closed inside window Contact Open inside window Relay units Setpoint High 60 Hysteresis 5 Hysteresis 5 Setpoint Low 4...

Страница 33: ...05 UK 33 Document history The following list provides notes concerning revisions of this document Rev ID Date Notes 105 1948 Relay data updated graph with resistive loads inserted EU RO marine approval added ...

Страница 34: ...entation We are headquartered in Denmark and have offices and authorized partners the world over We are a local business with a global reach This means that we are always nearby and know your local markets well We are committed to your satisfaction and provide PERFORMANCE MADE SMARTER all around the world For more information on our warranty program or to meet with a sales representative in your r...

Страница 35: ...andards for products communicating monitoring and connecting our customers process measurement points to their process control systems Our innovative patented technologies are derived from our extensive R D facilities and from having a great understanding of our customers needs and processes We are guided by principles of simplicity focus courage and excellence enabling some of the world s greates...

Отзывы: