5.0 aPP - application selection
5.1 Fun - Funktion selection.
On.a.function.change,.the.unit.resets.and.the.display.returns.to.default,.
menu.0.0.
Possible.functions.are:
001.=.f/I.converter.
002.=.f/f.converter.
003.=.Frequency.generator
Entering.of.example.=.001.
Valid.selections.are.001,.002.and.003
5.2 InP - Sensor type selection.
PnP. =.PNP.proximity.switch.open.collector.or.switch.to.+24.VDC.
nPn. =.NPN.proximity.switch.open.collector.or.switch.to.Gnd.
ttL.
=.TTL,.standard.TTL.signals.at.5.VDC.level.
nUr. =.NAMUR.in.accordance.with.DIN.19234.
S0.
=.S0.interface.in.accordance.with.DIN.43864.
tAC. =.AC.Tacho.
Entering.of.example.=.nUr.
Possible.selections.are:.PnP,.nPn,.ttl,.nUr,.SO.and.tAC
5.3 FLt - Input filter setting.
On. contact. input. the. LO. filter. should. be. used. to. eliminate. bounce.
input..
Entering.of.example.=.Hi.
Possible.selections.are.LO.-.50.Hz.or.HI.-.20.kHz..
5.4 PaS - Password selection.
When.the.password.is.040,.changes.may.be.made.in.all.menu.points..
When. the. password. is. <>. 040,. programming. is. locked. in. all. menu.
points,.but.open.for.reading.the.value.
Entering.of.example.=.040.
Valid.selections.are.0...999.
5.5 Pud - Power-up delay setting.
The.power-up.delay.time..is.the.period.of.time.in.which.the.digital.output.
is.out.of.function.after.power.connection.
Entering.of.example.=.10.0.
Valid.selections.are.0...999.seconds.
4.0 dOu - Digital setting of output
4.1 dLO - Setting of setpoint / limit frequency in % of the
frequency span.
This.value.corresponds.to.the.setpoint,.when.menu.4.4.dOA.=.{.InC.or.
dEC.},.and.it.corresponds.to.the.low.limit.frequency.of.a.setpoint.win-
dow.when.menu.4.4.dOA.=.{.UOn.or.UOF.}.
Entering.of.example.=.7.97.(1000./.12550.5.*.100.[%]).
Valid.selections.are.0.0...99.9%.
4.2 dHI - setting of limit frequency in % of the frequency span.
This.value.corresponds.to.the.high.limit.frequency.of.a.setpoint.win.dow.
and.is.only.valid.when.menu.4.4.dOA.=.{.UOn.or.UOF.}.
Entering.of.example.=.87.6.(11000./.12550.5.*.100.[%])..
Valid.selections.are.0.0...99.9%.
4.3 HYS - Setting of hysteresis in % of the frequency span.
If. 4.4. dOA. =. {. UOn. or. UOF. }. the. hysteresis. is. outside. the. window..
(4.1.and.4.2)
If.4.4.dOA.=.{.InC.}.the.hysteresis.is.below.setpoint.(4.1).
If.4.4.dOA.=.{.dEC.}.the.hysteresis.is.above.setpoint.(4.1).
Entering.of.example.=.0.16.(20./.12550.5.*.100.[%]).
Valid.selections.are.0.0...99.9%.
4.4 dOa - Digital output action setting.
For.InC.or.dEC.the.digital.output.action.will.respectively.be.increasing.
or.decreasing..The.setpoint.and.the.hysteresis.must.be.set.in.menu.4.1.
and.4.3.
For.UOn.the.digital.output.is.activated.within.the.window.
For.UOF..the.digital.output.is.activated.outside.the.window.
The.low.and.the.high.limit.frequency.in.the.window.are.set.in.menu.4.1.
and.4.2.respectively,.and.the.hysteresis.is.set.in.menu.4.3.
Entering.of.example.=.UOn.
Possible.selections.are.InC,.dEC,.UOn.or.UOF.
4.5 dOF - Digital output function setting.
If.L.(Limit).is.selected,.the.digital.output.will.work.as.a.trip.amplifier.
If.LC.(Limit,.Cable).is.selected,.the.digital.output.will.act.as.both.a.trip.
amplifier. and. as. a. sensor. error. monitor.. If. C. (Cable). is. selected,. the.
digital.output.will.act.as.a.sensor.error.monitor.
Sensor. error. monitoring. is. performed. only. by. NAMUR. sensor. when.
submenu.5.2.InP.=.nUr
Entering.of.example.=.LC.
Possible.selections.are.L,.LC.or.C.
Содержание 2255
Страница 10: ...16 17 ...
Страница 13: ...22 23 ...
Страница 15: ...26 27 ...
Страница 25: ...46 47 ...
Страница 28: ...52 53 ...
Страница 30: ...56 57 ...
Страница 40: ...76 77 ...
Страница 43: ...82 83 ...
Страница 45: ...86 87 ...
Страница 55: ...106 107 ...
Страница 58: ...112 113 ...
Страница 60: ...116 117 ...