2.3

  Downloading data to PC

 

Connect  the  instrument  to  the  PC  and  run    ENVIS.Daq    application.    Select    the    appropriate  

communication  option and connect to the instrument.  In the next screen press 

Refresh All

.  This 

will load and display the actual  status  of  each  supported  archive. 

 

Device  Information 

section  contains  editable  description  and  name  under  which  the  actual  record  is 

stored. 

Time Frame for Other Archives 

tab allows you to limit the date ranges of all archives by the time 

interval of the  main  archive. In  the 

Destination 

section  the  actual  storage  can  be  selected  -  either  to 

the  SQL  database  or  to  the  file.  The  check  boxes in 

Archives to  Download 

determines  which  specific 

archive(s) you want to download. 

The actual download will start by pressing the 

Download All 

button.  progress is displayed on screen. 

When  finished the  archive  can  be  viewed in the  ENVIS application. User can  open the downloaded  file 

directly  from  ENVIS.Daq. 

 
 

2.4

  Energy meter readings

 

UMD  705 has an embedded three phase, four-quadrant energy meter with automatic meter reading 

functions  and 

multiple  programmable  tariffs  (Time-of-Use,  TOU).  The  instrument  registers  active 

energy (EP, EP+, EP-) and  reactive energy (EQL, EQC or EQC+, EQC-, EQL+, EQL-).  According to 

the  configuration  of  meter  readings  are  shuffled  to  the  respective  tariffs.  It  automatically  provides 

summaries  per  phase.  For  star  connections  and 

single phase  measurements it  can also register 

energy for each phase separately. 

Meter  data  readings  can  be  downloaded  and  analyzed  in  ENVIS  or  via  the  standard  ModBus  protocol 

in  any  other  system. 

 
 

3

 

Technical Specifications 

 

3.1 

Basic Parameters 

 

 

 

 

Auxiliary Voltage 

 

model 

„230V“ 

model 

„24V" 

aux. voltage range 

85 ÷ 510 VAC 
85 ÷ 350 VDC 

 

20 ÷ 75 VDC 

power supply 

7 VA / 3 W 

3,5 VA / 3,5 W 

overvoltage category 

III (300V) 

II (100V) 

pollution degree 

connection 

isolated, polarity free 

 
 

Содержание UMD 705

Страница 1: ...1 Operating Manual for UMD 705E CBM ...

Страница 2: ...llation of the instrument 2 2 2 1 Supply voltage 3 2 2 2 Measured voltage 3 2 2 3 Measured currents 3 2 2 4 Communication peripherals 4 2 2 5 Outputs and inputs 6 2 3 Downloading data to PC 6 2 4 Energy meter readings 7 3 Technical Specifications 7 3 1 Basic Parameters 7 3 2 Measured Quantities 9 3 3 Inputs and Outputs 12 4 Maintenance Service Warranty 13 ...

Страница 3: ...ed data each instrument can be locked by a custom pin It uses standard RS 485 serial line for communication with remote control systems Optionally it can be equipped with other communication peripherals such as Ethernet USB It is equipped with three voltage inputs and three current inputs 1 1 Improvements and advanced functions new front panel display and control new power supply option U with 85 ...

Страница 4: ...uipped with and must use personal protective clothing and tools If the analyzer is used in a manner not specified by the manufacturer the protection provided by the analyzer may be impaired If the analyzer or its accessories appear to be impaired or not functioning properly do not use it and send it in for repair 2 2 Installation of the instrument Natural air circulation should be provided inside ...

Страница 5: ...C EN 61010 1 Internal power supply is galvanically isolated from internal circuits 2 2 2 Measured voltage The measured voltages are connected to the terminals L1 L2 and L3 Connect the neutral wire to the terminal N With delta or Aaron connections terminal N remains unused Voltage measurement inputs are connected with internal circuits over high impedance It is suitable to protect the measured volt...

Страница 6: ...nstruments provide RS485 serial line 2 2 4 Communication peripherals All peripherals stated below are galvanically isolated from the rest of the instrument and from each other Ethernet interface variant E 100 Mbit Ethernet interface with RJ 45 connector 100Base TX labeled as ETH is situated on a top panel of the device Ethernet interface can be used as substitution for the primary RS 485 for conne...

Страница 7: ...hive downloading and device configuration Serial RS 485 line uses terminals A B with shielding at terminal G of COM1 block fig 4 The end point of the communication line must be properly terminated with 120n resistor Figure 4 Typical wiring of the RS 485 communication line terminals in UMD 705 ...

Страница 8: ...or C2 with external power supply in the following way the current flows from positive terminal of the supply through the external input contact to a DI terminal D1 or D2 and than from the common terminal C1 or C2 back to the negative terminal of the external power supply DI O as a digital output DO is connected to the selected I O terminal D1 or D2 and a common terminal C1 or C2 with external powe...

Страница 9: ...en finished the archive can be viewed in the ENVIS application User can open the downloaded file directly from ENVIS Daq 2 4 Energy meter readings UMD 705 has an embedded three phase four quadrant energy meter with automatic meter reading functions and multiple programmable tariffs Time of Use TOU The instrument registers active energy EP EP EP and reactive energy EQL EQC or EQC EQC EQL EQL Accord...

Страница 10: ... 4 8 100 A 1000 A EN 61000 4 11 250 periods EMC emissions EN 55011 class A EN 55022 class A not for home use communicationports RS 485 2400 921600 Bd optional USB Ethernet 10Base T communication protocols KMB Modbus RTU and TCP web server DHCP accuracy of RTC 2 seconds per day capacity of RTC backup battery 5 years without supply voltage applied protection class front panel whole instrument IP 40 ...

Страница 11: ...mperature drift 0 03 of rdg 0 01 of rng 10 ºC measurement category 300V CAT III permanent overload 1820 VAC UL N peak overload 1 second 2730 VAC UL N burden power impedance 0 05 VA Ri 3 78 MΩ VoltrageUnbalance measuring range 0 10 measuring uncertainty 0 3 of rdg or 0 3 THDU measuring range 0 20 measuring uncertainty 0 5 Harmonics up to 50th order referenceconditions other harmonics up to 200 of c...

Страница 12: ...nutes 10 AAC 90 AAC burden power impedance 0 001 VA Ri 0 1 Ω 0 5 VA Ri 10mΩ CurrentUnbalance measuring range 0 100 measuring uncertainty 1 of rdg or 0 5 Harmonics Interharmonics up to 50th order referenceconditions other harmonics up to 1000 of class 3 acc to IEC 61000 2 4 ed 2 measuring range 500 of class 3 acc to IEC 61000 2 4 ed 2 measuring uncertainty Ih 10 INOM 1 INOM Ih 10 INOM 1 of rdg THDI...

Страница 13: ...rtainty 0 005 reference conditions B ambient temperature tA U I for active power PF cos φ for reactive power 23 2 ºC U 80 120 UNOM I 2 120 INOM PF 0 5 PF 0 87 act react power uncertainty 1 of rdg 0 01 PNOM PF cos φ uncertainty 0 005 temperature drift of powers 0 05 od rdg 0 02 PNOM 10 ºC Energy measuring range corresponds to U I measuring ranges 4 quadrant energy counters for both active and react...

Страница 14: ...ating 35 VDC 30 mADC dynamic parameters pulse output pulse duration gap duration maximumfrequency S0 compatible 50 ms 50 ms 10 Hz Digital Inputs type Opticaly isolated unipolar Cx Dx maximum voltage 30 VDC voltage for logical 1 7 VDC voltage for logical 0 3 VDC input current 5 mA 12V 13 mA 24V dynamic par pulse counter pulse gapduration maximumfrequency 0 5 0 5 ms 1 kHz ...

Страница 15: ...PQ PLUS GmbH Hagenauer Str 6 91094 Langensendelbach info pq plus de 49 9133 60640 0 www pq plus de The product must be in proper packaging to prevent damage during transit A description of the problem or its symptoms must be delivered together with the product If a warranty repair is claimed the warranty certificate must be sent in In case of an out of warranty repair you have to enclose an order ...

Отзывы: