PQ Plus – CMD 68-54/104 V2

Quick-Start Manual

8

EN

M-Bus Interface 

Default settings ex-factory

Secondary address:  Serial number 

Primary address: 

Baud rate:  

2400

Configuration via M-Bus

Primary and secondary address, baud rate and read-out data can be con-

figured by the free EMU MB-Connect software or with the arrow keys. 

Configuration of primary-/ secondary address and Baud

1. 

Arrow right to Settings

2. 

Arrow down to primary-/secondary adress/ Baudrate

3. 

Arrow right to choose digit, Arrow down to change digit

4. 

Save: Push service key for 5 seconds, until LCD flashes

 

Modbus RTU RS485 Interface

Configuration similar to M-Bus Primary Address.

Содержание CMD 68-104

Страница 1: ... Quick Start Manual CMD 68 54 104 V2 English ...

Страница 2: ...n instruction 3 Inbetriebnahme 4 Menu Navigation 4 Commissioning Check up 4 Tariff control 5 Current transformer ratio 6 Date Time 6 S0 pulse output 7 M Bus Interface 8 Modbus RTU RS485 Interface 8 TCP IP interface 9 Error messages 9 Technical data 10 Safety instruction 10 Maintenance 11 Disclaimer Liability exclusion 11 ...

Страница 3: ... 0 005 A 0 05 A 0 25 A 5 A 5 A Current 1A Ist Imin Itr Iref Imax 0 002 A 0 01 A 0 05 A 1 A 1 A Installation instruction Torque Connection Flexible wire Direct max 25mm2 strand Current transformer max 6mm2 strand Input lead L1 L2 L3 2 3 Nm 1 3 1 6 Nm Neutral conductor 2 3 Nm 1 3 1 6 Nm S0 pulse output Cage clamp up to max 2 5mm2 strand Tariff control Cage clamp up to max 2 5mm2 strand ...

Страница 4: ...vice key on the right side below the red terminal cover Change save configurations Commissioning Check up To check before operation Phase rotation Current per phase Negative energy direction Sequence of phase L1 L2 L3 Current Transformer ratio and Read out interface Correct address Connections D Lx for Current N for Neutral Connections CT S1 2 for Current Lx for Voltage N for Neutral ...

Страница 5: ...PQ Plus CMD 68 54 104 V2 5 EN Tariff control Tariff changeover takes place by 230V to corresponding terminal Doppeltarif Tarif E2 E1 NE T1 0 0 0 T2 0 1 0 T3 1 0 0 T4 1 1 0 0 No voltage 1 230V ...

Страница 6: ...former ratio 1 Arrow right to Settings 2 Arrow down to CT Ratio 3 Arrow right to choose digit Arrow down to change digit 4 Save Push Service key for 5 seconds until LCD flashes Date Time Configuration 1 Arrow right to Settings 2 Arrow down to Realtime Clock 3 Arrow right to choose digit Arrow down to change digit 4 Save Push service key for 5 seconds until LCD flashes ...

Страница 7: ...minal 6 7 Indirect CT meter 10 Impulse kWh Direct meter 1000 Impulse kWh Rate per kWh kvarh 1 10 100 1000 10 000 Pulse length Adjustable 2 10 30 40 120ms Configuration of pulse rate pulse length 1 Arrow right to Settings 2 Arrow down to S0 pulse rate pulse length 3 Arrow right to choose digit Arrow down to change digit 4 Save Push service key for 5 seconds until LCD flashes ...

Страница 8: ...ad out data can be con figured by the free EMU MB Connect software or with the arrow keys Configuration of primary secondary address and Baud 1 Arrow right to Settings 2 Arrow down to primary secondary adress Baudrate 3 Arrow right to choose digit Arrow down to change digit 4 Save Push service key for 5 seconds until LCD flashes Modbus RTU RS485 Interface Configuration similar to M Bus Primary Add...

Страница 9: ... right to Settings 2 Arrow down to IP Adress 3 Arrow right to choose digit Arrow down to change digit 4 Save Push service key for 5 seconds until LCD flashes Error messages If an internal error appears an error message is displayed F F 0 00000000 No error meter ok For a list of all errorcodes please contact us per e mail at info pq plus de ...

Страница 10: ...ination DE MTP 21 B 002 M Maximal air humidity Average 75 Short term 95 Non condensing Safety instruction The CMD 68 54 104 should only be used for measuring electrical energy and can not be operated outside the specified technical data When installing or replacing the meter the conductors to which the meter is connected have to be dead power voltage off Touching live components voltage or power i...

Страница 11: ... connection or storage repairs may only be done by PQ Plus GmbH Disclaimer Liability exclusion The choice of the CMD 68 54 104 and determination of the suitability of the meter type for a particular purpose are solely the responsibility of the buyer PQ Plus GmbH takes no responsibility for this Data information in catalogs and data sheets do not promise special prop erties but are determined by ex...

Страница 12: ... 49 9133 60640 100 Mail info pq plus de Web http www pq plus de Managing Director Daniel Fierus Beyer VAT identification number DE 301 767 284 Further information and the current catalogue can be found on our website http www pq plus de Release 2022 03 Subject to technical changes ...

Отзывы: