Accessing Operator Page & Adjusting Parameters
Step through the following sequence to open the operator page and to adjust the operator parameter values.
1. Press and release PAGE key. The Lower Readout shows (PAGE) and Upper Readout shows (0).
2. Press ENTER key. The Lower Readout shows prompt for the first available operator parameter and the Upper Readout
shows value for the parameter.
3. Use UP / DOWN keys to adjust the value and then press ENTER key to store the set value and scroll to next parameter.
The controller automatically reverts to MAIN Display Mode upon scrolling through the last operator parameter. Alternatively,
use PAGE key to return to MAIN Display Mode.
The operator parameters are described in Table 2.2. Note that the parameters presented on operator page depend upon the
functions selected/enabled and supervisory level permissions.
ACTIVATE / DE-ACTIVATE STANDBY MODE
Set the parameter value to ‘Yes’ or ‘No’ for entering and exiting the
Standby mode, respectively.
This is the Main Setpoint value that the controller respects for the
control purpose. This value is not applicable if running a profile or if
the controller is tuning or in standby mode.
CONTROL SETPOINT
Parameter Description
Settings
ALARM-1 WINDOW BAND
The Alarm setpoint for Alarm-1 if the Alarm Type is the Window
Band value for Alarm-1.
ALARM-1 DEVIATION BAND
The Alarm setpoint for Alarm-1 if the Alarm Type is the Deviation
Band value for Alarm-1.
ALARM-1 SETPOINT
The Process High or Process Low limit for Alarm-1.
Table 2.2
Setpoint Low Limit
to Setpoint High Limit
(Default : -1999)
No
Yes
(Default : No)
Min. to Max. Range
specified for the
selected Input Type
(Default : Min or Max Range)
For DC mA/mV/V
: 3 to 9999 counts
:
For Thermocouples/RTD
3 to 999 or 0.3 to 999.9
(Default : )
0
For DC mA/mV/V
:
-1999 to 9999 counts
:
For Thermocouples/RTD
-999 to 999 or -1.999 to 999.9
(Default : )
0
The parameters in Operator Page are editable only if permission is enabled in Supervisory Page (PAGE-13)