PPI neuro 102 Скачать руководство пользователя страница 6

4

Table 2.1

              PV above Max. Range

           PV below Min. Range

Message

 Error Type

Cause

Thermocouple / RTD broken

Sensor Open          

Under-range

Over-range

CONTROL / ALARM STATUS UNDER PV ERROR CONDITIONS

a)  The tuning, if in progress, is aborted.

b)   The Profile Cycle, if in progress, enters in HOLD state. 

c)  Under 

Over-range 

or 

Under-range

 error condition, all the control outputs are switched off. However, under 

Sensor Open

  

error, the PID control output power is maintained at the value set for the parameter “Sensor Break Output Power” on 

PAGE-12. 

d)  For Alarm activation, the under-range condition is treated as minimum PV, whereas the over-range and open conditions  

are treated as maximum PV. Thus, Process High, positive Deviation Band and Window Band alarms activate under 

Over-

range/Open error

. Similarly, Process Low, negative Deviation Band and Window Band alarms activate under 

Under-range 

error

•    

MANUAL MODE OPERATION

     This  operation  mode  is  available  only  if  the  control  action  is  PID  and  if  the  manual  mode  operation  is  permitted  at 

supervisory level. In this mode, the controller operates in Open loop mode wherein the % Output Power is manually 

adjusted  by  the  operator. This  mode  is  often  used  for  process  start-up  to  make  sure  that  the  process  equilibrium  is 

achieved  before  the  control  is  transferred  for  subsequent  automatic  (closed  loop)  control.  The  controller  ensures  a 

bumpless

 Auto / Manual transfer. 

The manual mode can be activated or de-activated using ENTER key. While in manual mode, the Upper Readout shows PV 

while the Lower Readout shows % Power that can be adjusted using UP/DOWN keys.

Follow the steps below to enter (Activate) into Manual Mode and to revert to (De-activate) Automatic Mode.

1.   Hold ENTER key pressed for approximately 2 seconds until front panel indicator M (Manual Mode) turns on. 

2. 

Release Enter key. The controller is now placed in Manual mode. The Upper Readout displays the PV and the Lower 

Readout  displays  the  %Output  Power  (with  the  leftmost  digit  indicating  either  P  (Unidirectional  control)  or  H  /  C 

(Bidirectional control)). 

3.    Adjust the Output Power using the UP and DOWN keys. Note that in Unidirectional mode, the Output Power is adjustable  

between the set Power Low and Power High limits. However, in Bi-directional mode, the Output Power is adjustable from 

-100% to +100%.The power range from -100% to 0 is Cool Power (with the leftmost digit indicating C) and 0 to +100% is 

Heat Power (with the leftmost digit indicating H).

To de-activate the Manual mode; Hold the ENTER key pressed for approximately 2 seconds until the front panel indicator M 

turns off. The controller now enters into Auto control mode with the first power same as that was adjusted last while in Manual 

mode. 

 User Manual

neuro 102

Содержание neuro 102

Страница 1: ...neuro 102 User Manual Universal Single Loop Process Controller M C AL2 neuro 102 AL1...

Страница 2: ...ARAMETERS 12 6 CONFIGURATION PARAMETERS 14 7 SUPERVISORY PARAMETERS 17 8 19 PROFILE PARAMETERS 9 OP2 OP3 FUNCTION PARAMETERS 22 10 HARDWARE ASSEMBLY CONFIGURATIONS 24 11 MECHANICAL INSTALLATION 31 12...

Страница 3: ...ht green LED display and usually displays Setpoint Value or Output Power In Set up Mode the Lower Readout displays parameter names prompts INDICATORS The front panel indicators are red LED s that show...

Страница 4: ...e value by one count keeping pressed speeds up the change Press to decrease the parameter value Pressing once decreases the value by one count keeping pressed speeds up the change PAGE AL2 Flashes whi...

Страница 5: ...s upon completion ofTuning procedure Profile Mode Indications While a Profile Cycle is in progress the front panel indicator PRF flashes or glows steadily The steady glowing indicates that though the...

Страница 6: ...before the control is transferred for subsequent automatic closed loop control The controller ensures a bumplessAuto Manual transfer The manual mode can be activated or de activated using ENTER key Wh...

Страница 7: ...er is switched off or a Power failure occurs while the controller is operating in Standby mode upon resumption of power the controller continues to operate in Standby mode OPERATOR PAGEAND PARAMETERS...

Страница 8: ...Auxiliary Setpoint No Yes Default No This is the Setpoint value that the controller respects for the control purpose while it is not running a profile or not in standby tuning mode CONTROL SETPOINT N...

Страница 9: ...m 2 Setpoint ALARM 2 SETPOINT The setpoint Band value depending upon the type of Alarm for Alarm 2 This parameter is not available if the selectedAlarm type is None Throughout the range for the select...

Страница 10: ...st parameter 5 Use UP DOWN keys to adjust the parameter value The display flashes if UP key is pressed after reaching the maximum value or DOWN key is pressed after reaching the minimum value 6 Press...

Страница 11: ...tep through the following sequence Locking 1 Press and release PAGE key while the controller is in the MAIN Display Mode The Lower Readout shows PAGE and the Upper Readout shows 0 2 Use UP DOWN keys t...

Страница 12: ...to 0 cuts off the derivative action 0 5 to 120 0 Seconds in steps of 0 5 secs Default 20 0 sec CYCLE TIME Available for PID Control only Sets the total On Off time in seconds for time proportional pow...

Страница 13: ...100 Default 100 COOL POWER LOW Available for PID Control with bi directional that is Heat Cool mode Sets the minimum output power limit for OP2 0 to Power High Default 0 COOL POWER HIGH Available for...

Страница 14: ...rocess High or Process LowAlarm 1 Type SetsAlarm limit independent of control setpoint ALARM 1 DEVIATION BAND Available for Deviation BandAlarm 1 Type Sets positive or negative deviation offset limit...

Страница 15: ...ow BandAlarm 2 Type Sets symmetrical positive and negative deviation offset limits from control setpoint for both High and LowAlarm 2 activation 1 to 999 Default 2 ALARM 2 HYSTERESIS Sets differential...

Страница 16: ...Thermocouple RTD Inputs Selects temperature measurement units in C or F RESOLUTION FOR PV NotAvailable for Thermocouple Inputs Sets the process value indication resolution decimal point All the resolu...

Страница 17: ...the controller outputs this power value under open loop condition 100 to 100 Default 0 0 DIGITAL FILTER FOR PV Sets the time constant in seconds for the low pass digital filter applied to the measured...

Страница 18: ...age 0 to 5 0V DC voltage 0 to 10 0V DC voltage 1 to 5 0V DC voltage 3 wire RTD Pt100 1999 to 9999 units 199 to 600 C 328 to 1112 F 199 9 to 600 0 C 199 9 to 999 9 F or User settable 1 C 1 F or 0 1 C 0...

Страница 19: ...s parameter adjusts the effectiveness of the Overshoot Inhibit feature Increase the value if the overshoot is curbed but the PV takes longer to reach the SP Decreases the value if the overshoot persis...

Страница 20: ...free contact closure of external switch Relay or a TTL compatial voltage level below 0 5 Volts by the Hardware module When the Serial Communication option is selected the Following parameters are avai...

Страница 21: ...ed to ensure that the PV follows the set Ramp Rate within allowable limits as far as possible Set this value to 0 if Ramp hold back function is not required This parameters is expressed in the same un...

Страница 22: ...99 99 Default 0 00 TARGET SETPOINT 2 This parameter sets the target level for the second ramp segment The Setpoint ramps to this level with Ramp Rate 2 from target Setpoint 1 This parameter is expres...

Страница 23: ...e Setpoint start ramping to Target Setpoint 4 as soon as it reaches to target Setpoint 3 This parameter is expressed in minutes and settable in 1 minute resolution This parameter sets the rate at whic...

Страница 24: ...eter Description OUTPUT 2 FUNCTION SELECTION Applicable for OP2 hardware module if fitted Select the function feature to which the OP2 module is to be logically attached for activation Default Alarm A...

Страница 25: ...ecorder output signal level 0mA or 4 mAor 0V Default 200 Min to Max Range Specified for the Selected Input Type RECORDER HIGH Available if OP3 function is recorder Set the maximum parameter value SP o...

Страница 26: ...SERIAL COMMS SSR DC Linear RELAY N O N C C P P I L N AC DC SUPPLY GND A B AUXILIARY SP SELECTION ALM The Figure 10 1 below shows the controller outer case viewed with front label upright Section 10 Us...

Страница 27: ...the bezel Pull the bezel outward The assembly comes out with the bezel Placing Assembly Back into Enclosure With the controller upright the UP inscribed on the Enclosure is on the topside insert the...

Страница 28: ...26 Figure 10 4 CPU PCB Pins Shorting Link 1 2 3 B C 1 2 3 4 P P I n e u ro 1 0 2 B A C User Manual neuro 102 P P I Power Supply Board CPU Board Display Board Bezel V I E W ur ne o102 Figure 10 3...

Страница 29: ...B Jumper Setting A 4 3 2 1 1 2 3 4 3 2 1 4 3 2 1 1 2 3 Pins Shorted DC Linear Current mA a All Other Input Types Link Parked b Figure 10 5 Input Jumper Settings The Input type and the Output 1 type a...

Страница 30: ...into the 2 slots provided on the Power Supply CPU PCB for proper electrical contacts and secured fitting For plugging out the module s follow the steps below 1 Gently pull apart the Power supply boar...

Страница 31: ...Output 3 Module PI P Plug Socket Connector Projected Parts Slots Output Module Power Supply Board Front Label Upright n ro 102 eu Output Module Projections P P I Plug Socket Connector Slots CPU Board...

Страница 32: ...Serial Communication Auxiliary SP module To plug or unplug the module simply insert or remove the socket into or from the plug Mounting Serial Communication Auxiliary SP Selection Module Figure 10 10...

Страница 33: ...c or electromagnetic interference 4 The controller should not be subject to direct vibration or shock 5 The controller should not be exposed to dust salt air direct sunlight or radiant heat OUTER DIME...

Страница 34: ...d until it is firmly in contact with the rear face of the mounting panel and the tongues of the clamp engage in the ratchets on the controller enclosure as shown in Figure 11 3 Ensure that the springs...

Страница 35: ...not to over tighten the terminal screws while making connections 6 Make sure that the controller supply is switched off while making removing any connections or removing the controller from its enclo...

Страница 36: ...r with the shield grounded at the signal source for connecting mV V source Connect common to terminal 2 and the signal to terminal 1 as shown in Figure 12 2 C The DC Current source is also connected i...

Страница 37: ...l insulated copper 2 conductor wire of the size not smaller than 0 5mm for power supply connections Connect Line Phase supply line to terminal 12 and the Neutral Return supply line to terminal 13 as s...

Страница 38: ...istance Typically 24 AWG or thicker Connect the terminating resistor Typically 100 to 150 ohm at one end to improve noise immunity DIGITALINPUT FORAUXILIARYSPSELECTION Terminals 14 15 The Option plug...

Страница 39: ...37 User Manual neuro 102 96X96 neuro 102 96X96...

Страница 40: ...digit 7 segment bright green LED display and usually displays Setpoint Value or Output Power In Set up Mode the Lower Readout displays parameter names prompts INDICATORS The front panel indicators are...

Страница 41: ...by one count keeping pressed speeds up the change Press to decrease the parameter value Pressing once decreases the value by one count keeping pressed speeds up the change PAGE User Manual AL2 Flashes...

Страница 42: ...CB is to the right and the Display PCB is behind the bezel The electronic assembly can be removed from the plastic enclosure and placed back as described and illustrated in Figure 2 1 Section 2 User M...

Страница 43: ...arameter settings the Output 1 configuration requires jumper settings marked B C for different output type selections as shown in theTable 2 2 below neuro 102 96X96 Table 2 1 Input Jumper Settings The...

Страница 44: ...gh proper jumper selection Two jumper settingsAand B as shown in Figure 2 3 are required for Relay or SSR selection ReferTable 2 3 for appropriate jumper setting positions B A Relay SSR Module Figure...

Страница 45: ...nts shown in figure to help locate the plugs for the modules Figure 2 4 The plug for the Serial Communication or Remote Alarm Acknowledgment module is located on the Power supply PCB The Figure 2 5 be...

Страница 46: ...not to over tighten the terminal screws while making connections 6 Make sure that the controller supply is switched off while making removing any connections or removing the controller from its enclo...

Страница 47: ...twisted pair with the shield grounded at the signal source for connecting mV V source Connect common to terminal 2 and the signal to terminal 1 as shown in Figure 3 2 c Figure 3 2 c 3 2 1 DC Linear Cu...

Страница 48: ...5 The indicator is designed for installation in an enclosure which provides adequate protection against electric shock Local regulations regarding electrical installation should be rigidly observed Co...

Страница 49: ...sistance Typically 24 AWG or thicker Connect the terminating resistor Typically 100 to 150 ohm at one end to improve noise immunity DIGITALINPUT FORAUXILIARYSPSELECTION Terminals 14 15 The Option plug...

Страница 50: ...a n e t Process Precision Instruments 101 Diamond Industrial Estate Navghar Vasai Road E Dist Palghar 401 210 Maharashtra India 0250 2391722 33 37 42 07498799226 09321985369 support ppiindia net sales...

Отзывы: