PPI HumiTherm-i Pro Скачать руководство пользователя страница 10

 User Manual

HumiTherm-i Pro 

8

Reverse

Direct

(Default : Direct)

Table 4.1

PAGE-10 : TEMPERATURE - ALARM PARAMETERS 

Parameter Description

Settings

(Default Value)

-50.0 to 150.0°C or

-58.0 to 302.0°F

(Default : 

For Process Low : -50.0

For Process High : 150.0)

(Default : 0.2)

0.1 to 25.0 °C or °F

 TEMPERATURE ALARM TYPE

None

 

Alarm activation is disabled.

Process Low

The Alarm activates when the Temperature Value equals or falls 
below the ‘Alarm Setpoint’ value. 

Process High

The  Alarm  activates  when  the  Temperature  Value  equals  or 
exceeds the ‘Alarm Setpoint’ value.

 TEMPERATURE ALARM SETPOINT 
 

This  parameter  sets  the  Process  High  or  Process  Low  limit  for 
Alarm. 

TEMPERATURE 

ALARM HYSTERESIS

This parameter sets a differential (dead) band between the ON 
and  OFF Alarm  states.  Keep  it  large  enough  to  avoid  frequent 
switching of the Alarm relay.

(Default : Yes)

No

Yes

Section 4

 TEMPERATURE 

ALARM INHIBIT 

No

The Alarm is not suppressed during the start-up Alarm conditions. 

Yes

The Alarm activation is suppressed until the

 

Temperature Value

 

is 

within Alarm limits from the time the indicator is switched ON. This 
allows  suppressing  the  Alarm  during  the  start-up  Alarm 
conditions.

(Default : None)

Process High

None

Process Low

 TEMPERATURE 

ALARM LOGIC

Direct

 

Alarm Relay is energized when the alarm is active; remains de-
energized otherwise. 

Reverse

Alarm Relay remains energized as long as the alarm is not active. 
The relay de-energized upon alarm activation.

Содержание HumiTherm-i Pro

Страница 1: ...User Manual HumiTherm i Pro Enhanced Temperature Humidity Indicator with Dry Wet RTD Input Selection User Manual HumiTherm i Pro...

Страница 2: ...SS AND OPERATION 6 4 PAGE 10 TEMPERATURE ALARM PARAMETERS 8 5 PAGE 11 RELATIVE HUMIDITY ALARM PARAMETERS 9 6 PAGE 12 INPUT CHANNEL CONFIGURATION PARAMETERS 10 7 PAGE 13 SUPERVISORY PARAMETERS 13 8 PAG...

Страница 3: ...Mode the Lower Readout displays prompts for the parameters Table 1 2 Figure 1 1 FRONT PANEL LAYOUT CA RHA DHO L2 HumiTherm i Pro L1 L3 L4 COM Upper Readout Lower Readout ENTER Key UP Key DOWN Key PAGE...

Страница 4: ...e associated function Table 1 2 Symbol Key Function Press to enter or exit set up mode DOWN UP ENTER Press to store the set parameter value and to scroll to the next parameter on the PAGE Press to inc...

Страница 5: ...ature In case of Dry Bulb Temperature exceeding the specified Minimum or Maximum Range or in case of input sensor RTD Pt100 open broken the Upper Readout flashes the Error Messages as listed inTable 2...

Страница 6: ...AND PARAMETERS The indicator provides a separate page called Operator Page for the purpose of viewing and or resetting the stored Min Max values for Dry Bulb Temperature and RH The parameters on this...

Страница 7: ...Only MAXIMUM RH VALUE This parameter indicates the Maximum value attained by the Relative Humidity This is a read only value View Only MINIMUM RH VALUE This parameter indicates the Minimum value attai...

Страница 8: ...st rolls back to the first parameter 5 Use UP DOWN keys to adjust the parameter value The display flashes if UP key is pressed after reaching the maximum value or DOWN key is pressed after reaching th...

Страница 9: ...operator parameters still available for any editing For enabling disabling the Lock step through the following sequence Locking 1 Press and release PAGE key while the indicator is in the MAIN Display...

Страница 10: ...Process Low limit for Alarm TEMPERATURE ALARM HYSTERESIS This parameter sets a differential dead band between the ON and OFF Alarm states Keep it large enough to avoid frequent switching of theAlarm...

Страница 11: ...Value equals or falls below the Alarm Setpoint value Process High The Alarm activates when the RH Value equals or exceeds the Alarm Setpoint value RH ALARM SETPOINT This parameter sets the Process Hi...

Страница 12: ...nding to the Signal Low value from the temperature transmitter Refer Appendix A DC Linear Signal Interface for details Available if temperature input type is mV V mA The transmitter output signal valu...

Страница 13: ...esponding to the Signal High value from the humidity transmitter Refer Appendix A DC Linear Signal Interface for details RH RANGE HIGH Default 0 0 99 0 to 99 0 Available for Dry Wet RTDAssembly only T...

Страница 14: ...Max 199 9 to 999 9 units 199 9 to 600 0 C 199 9 to 999 9 F 0 1 C F 0 1 units Option What it means 0 to 20mA DC current 4 to 20mA DC current 0 to 1 25V DC voltage 0 to 5 0V DC voltage 0 to 10 0V DC vol...

Страница 15: ...NG UNIT SELECTION FOR TEMPERATURE SelectTemperature Units in C or F Parameter Description Settings Default Value C F Default C Default 0 0 to 250 Default No No Yes Section 7 Yes No Default Yes BAUD RA...

Страница 16: ...sured RH value is compared with the set value and a relay output is switched DE HUMIDIFIER SETPOINT If the measured RH value becomes equal or exceed this setpoint value the de humidifier control outpu...

Страница 17: ...troller outer dimensions Figure 9 1 Figure 9 2 94mm 3 70in 7mm 0 276in Side View 48mm 1 89in 48mm 1 89in Front View CA RHA L1 DHO L3 HumiTherm i Pro L2 COM L4 PANELCUTOUT The Figure 9 2 shows the pane...

Страница 18: ...the mounting panel 3 Hold the controller gently against the mounting panel such that it positions squarely against the panel wall see Figure 9 3 Apply pressure only on the bezel and not on the front l...

Страница 19: ...cables are run through conduits use separate conduits for power supply cable and low level signal cables 4 Use appropriate fuses and switches wherever necessary for driving the high voltage loads to p...

Страница 20: ...hielded twisted pair with the shield grounded at the signal source for connecting Voltage source Connect common to terminal 16 13 and the signal to terminal 17 14 as shown in Figure 10 2 b The DC Curr...

Страница 21: ...ground for excitation output 2 wire Current Transmitter 5 12 24VDC Supply 5 EXC 5 12 24V 4 to 20mA Output 16 17 mA 13 14 3 wire Voltage Transmitter 5 12 24VDC Supply Supply 1 to 3 6 V Output 5 EXC 5...

Страница 22: ...tor 2 wire of the size not smaller than 0 5mm for power supply connections Connect Line Phase supply line to terminal 1 and the Neutral Return supply line to terminal 2 as shown in Figure 10 5 below T...

Страница 23: ...n d i a n e t Jan 2022 Process Precision Instruments 101 Diamond Industrial Estate Navghar Vasai Road E Dist Palghar 401 210 Maharashtra India Sales 8208199048 8208141446 Support 07498799226 08767395...

Отзывы: