when the gate is still; this way only the input and RF receiver 
commands are energized directly through the battery.
The communication cable length used to connect the PPA UPS and 
the ECU must be a 20-meter (65.62 f) cable or shorter.

WARNING

This connection is mandatory on the swing models DZ 
1500, 2500 IND and DZ Condominium. 

4.3. Connecting the 2-lead communication cable 

between the UPS and the ECU

The PPA's Volt Gate UPS electronic board can also be connected 

to the operator ECU (TRIFLEX TOP) through the 2-lead INFO 
connector. This way, the UPS tells the tells the ECU it is working 
by battery operation; thus the PPA ECU  reduces the energy 
consumption during operation in order to increase the operational 
capacity (autonomy). 

The connection does not interfere on the ECU operation, even 

if it is connected to a terminal (borne) used by it, since the data is 
sent simultaneously to the commands. When using the TRIFLEX 
ECUs, one must connect it to the ABR + GND terminals (bornes) 
and when using automatic door's INVERTER ECUs, one must 
connect it to the RECEPTOR connector (two pins to the right of the 
receiver).

WARNING

This connection is mandatory on the swing models DZ 

2500 IND, DZ 1500 IND and DZ Condominium, in case 

the ECU does not have the 4-lead connected previously 

addressed. 

4.4. Cross Section of the Power and 

Communication Cables

EThe cables gauge must be larger when the distance between the 
Volt Gate UPS and the ECU increases, according to the next chart:

Distance

Minimum Section of the 

Signal Cable

Minimum Section of the ECU 

Power Cable

Up to 10m (32.8f)

0.3mm²

1.5mm²

From 10m (32.8f) up 

to 20m (65.7f)

0.5mm²

2.5mm²

5. ELECTRICAL SPECIFICATIONS

UPS Model

VOLT GATE 

127V

VOLT GATE 

220V

Input Voltage

127V / 60Hz 

+/- 20%

220V / 60Hz 

+/- 20%

Output Voltage

127V / 60Hz 

+/- 20%

220V / 60Hz 

+/- 20%

Battery voltage

24V

24V

Battery minimum recommended 

capacity

7Ah

7Ah

Maximum current of the built-in 

Battery charger

1.5A

1.5A

Output voltage of the battery 

charger

27.6V

27.6V

Maximum permitted power (for 5 

seconds  maximum)

700VA

700VA

Nominal Power (use until the 

battery is discharged)

350VA

350VA

Input fuse current

10A

10A

Battery fuse current

30A

30A

UPS Model

VOLT GATE 

IND 127V

VOLT GATE 

IND 220V

Input Voltage

127V / 60Hz 

+/- 20%

220V / 60Hz 

+/- 20%

Output Voltage

127V / 60Hz 

+/- 20%

220V / 60Hz 

+/- 20%

Battery voltage

12V

12V

Battery minimum recommended 

capacity

45Ah

45Ah

Maximum current of the built-in 

Battery charger

1.5A

1.5A

Output voltage of the battery 

charger

13.8V

13.8V

Maximum permitted power (for 5 

seconds  maximum)

1000VA

1000VA

Nominal Power (use until the 

battery is discharged)

550VA

550VA

Input fuse current

10A

10A

Battery fuse current

60A

60A

6. SIGNALING

6.1. Visual Signaling

PPA UPS is endowed with two LEDs for operation signaling. See chart 
below:

GREEN LED

RED LED

BLUE LED

ON: 

UPS ON

ON: 

BATTERY OPERATION

ON: 

BATTERY CHARGED

OFF: 

UPS OFF

OFF: 

POWER GRID OPERATION

OFF: 

NO ENERGY.

SLOWLY BLINKING: 

ENERGY 

SAVING MODE ON

SLOWLY BLINKING: 

CHARGING BATTERY

RAPIDLY BLINKING: 

PROTECTION AGAINST 

OVERHEATING OR 

OVERCHARGE ON.

6.2. Sound Signaling

PPA UPS also warns that is working by battery operation through a 
beep. The frequency of the beeps increases as the battery voltage 
decreases.