Section V Parameter Function Table
114
Sect
io
n
V
PID regulation fault.
P12
PID display range
0.00~100.00
-
1.00
Y
A09 PID set value
=
PID set value(%)*P12
A10 PID feedback value
=
PID feedback value(%)*P12
If PID feedback 10V corresponding 4.0Mpa pressure, if need A09, A10 to display actual
value, only need to set P12 = 0.04.
5-2-9.Expanding Parameters:E00-E23(0x0600-0x0617)
Code
Description / LCD
Setting Range
Unit
Factory
Setting
Change
Limited
E00
Load type
General
0
-
0
N
Pump
1
Fan
2
Injection machine
3
Textile machine
4
Hoist machine
5
Kowtow machine
6
belt conveyor
7
Variable frequency power
8
Multi-pumps constant
pressure water supply
9
Reserved
10
Reserved
11
Torque control
12
Voltage regulation power
13
Current regulation power
14
Extruding machine
15
Details, see Appendix IV.
E01
Starting pressure deviation
0.0~100.0
%
10.0
Y
E02
Starting delay time
0.0~3200.0
s
5.0
Y
Feedback pressure <given pressure –starting pressure deviation.
Continuously exceed E02 start delay time, the inverter will restart under in the standby mode
This parameter is used to prevent the inverter from frequent start-stop.
E03
Stop frequency
0~50.00
Hz
5.00
N
E04
Stop delay time
0.0~3200.0
s
5.0
Y
If the set frequency is less than or equal to E03 stop frequency, exceeding E04 stop delay
time, the inverter will change from running to the stop standby state.
The bigger E03 parameter setting, the easier to stop, E03 parameter is set to 0, indicating the