Foreword 

Thank  you  very  much  for  purchasing  PI8600  Family  Frequency  Inverters.  This  family  is 

designed  based  on  the  experience  of  POWTRAN  Company  in  the  professional  manufacture  and 
sale of the products, and suitable for general-purpose load machine. 

This product adopts the advanced sensorless vector control technology, combined with China 

local  frequency  inverter  application  features  to  achieve  high-performance  V/F  control  (dead-time 
compen auto-torque u Slip Compensation) and high-performance non-sense vector 
control, and high-performance speed sensorless vector control. 

This  product  adopts  the  advanced  sensorless  vector  control  technology,  combined  with  the 

application  of  inverter  technology  in  China  features  to  achieve  high-performance  V/F  control 
(dead-time compen auto-torque u Slip Compensation) and high-performance non-
sense vector control, and high-performance speed sensorless vector control. 

This User‟s Manual includes PI8600, the general purpose control F and G series. 

F: 

FLOW LOAD 

G: 

GENERAL LOAD 

Please contact the local dealers or directly contact our company. 

Please  keep  this  user‟s  manual  in  good  condition,  for  it  will  be  helpful  to  the  repair, 

maintenance, and applications in the future. 

For information about other product, please visit our website: http://www.powtran.com. 

Содержание PI8600 F Series

Страница 1: ...peed sensorless vector control This product adopts the advanced sensorless vector control technology combined with the application of inverter technology in China features to achieve high performance...

Страница 2: ...0137 69 5 2 5 IO Function System o00 o68 0x0200 0x0244 81 5 2 6 Multi speed PLC Group H00 H55 0x0300 0x0337 101 5 2 7 V Fcurve Group U00 U15 0x0400 0x040F 110 5 2 8 PID Parameter P00 P12 0x0500 0x050C...

Страница 3: ...00 400 0Hz 1 220V 50 60Hz POWTRAN TECHNOLOGY CO LTD PI8600A1 R75G1 AC Motor Drivers Model Serial No Bar Code Output Spec Input Spec 1 1 2 Model description 2 type code A normal elided B inhanced D si...

Страница 4: ...of the frequency inverter must be grounded to the earthing connections correctly and securely according to the national electrical safety specifications and other applicable standards Please don t shu...

Страница 5: ...lid exists 2 2 Installation The frequency inverter must be installed by wall hooking in the indoor room with adequate ventilation with enough space left between it and the adjacent objects or damper w...

Страница 6: ...Section II Installtion Standby Circuit 4 Section II 2 3 1 PI8600 Diagram ALARM V A Hz FWD REV s PRG FWD MF1 ESC STOP RESET SET C ALARM FWD R232 R485 PICOM RS485 RS232...

Страница 7: ...rminal Description Functions Input signal DI1 DI1 input terminal Multi functions input terminal For details Please read o36 o46 Enter a valid polarity can be controlled by o47 DI1 DI4 Drive model can...

Страница 8: ...o02 o03 can set input voltage current arrange o08 o09 Set the input signal corresponding to set value DA1 Multifunction Analog output signal 1 JP1 1 2 0 20mA JP1 2 3 0 10VDC o15 set analog output ana...

Страница 9: ...the distance between the frequency inverter and motor must not be greater than 50 meters maximum When it is above 4kHz this distance should be reduced The cable for this connection had better be laid...

Страница 10: ...ction A43 A44 1 MF defined as minus function A43 A44 2 MF defined as free stop function A43 A44 3 MF defined as forward function A43 A44 4 MF defined as reverse function A43 A44 5 MF defined as Punctu...

Страница 11: ...fault confirmation Forward running key drive forward running ENTER have the same function with PRG refer to explaination of key PRG Invalid in the monitoring state Monitor Select 1 Numerical Display d...

Страница 12: ...us 4 Through potentiometerSwitch to F01Fre Set by K 5 Press PRG or ENTER enter into F01 Fre Set by K parameter modify status 6 Through PRG or ENTER adjust the value is modified bit 7 Through potentiom...

Страница 13: ...yboard 1 Under monitoring status press PRG into parameter group to check status 2 Through potentiometerSwitch to y00 23 System FG 3 Press ENTER enter into y00 23 System FG parameter group to check sta...

Страница 14: ...1 to reset system parameter 1 Under monitoring status press PRG into parameter group to query status 2 Through potentiometerSwitch to y00 23 System FG 3 Press PRG enter into y00 23 System FG parameter...

Страница 15: ...status 4 Through potentiometerSwitch to y01 Upload To Keyboard 5 Press PRG enter into y01 Upload To Keyboard parameter modify status 6 Through potentiometer adjust to 5 7 Finish the adjustment press...

Страница 16: ...range A45 A46 A48 keyboard potentiometer setting X1 correspond to Y1 Keyboard potentiometer setting the starting point for the corresponding value Setting range 100 100 A49 keyboard potentiometer sett...

Страница 17: ...tting range 0 100 o08 AI2 input X1 correspond to Y1 Keyboard potentiometer setting the starting point for the corresponding value Setting range 100 100 o09 AI2 input X2 correspond to Y2 Keyboard poten...

Страница 18: ...to the motor power reset the factory value of y00 5 Select motor parameters motor parameters set in accordance with motor nameplate set of parameters rated power rated current rated voltage the number...

Страница 19: ...nd test running finish Upper torque setting C13 C14 Set PG pulses C28 PG directions C30 running Observe motor speed S06 Observe the motor current excitation component torque fluctuation component Stop...

Страница 20: ...H Multi speed PLC group Multi speed running PLCrunning 03 101 U V F parameter group User defined V Fcurve 04 110 P PID function group Internal PID parameter setting 05 111 E Extend function froup Cons...

Страница 21: ...set excitation heft percentage N 54 S13 Excitation heft actual value Motor actual excitation heft percentage N 54 S14 Torque heft Set value Motor set torque percentage N 54 S15 Torque heft actual valu...

Страница 22: ...setting 5 Digital Pulse Set 6 PID regulation mode 7 F04 The relationship between main and auxiliary setting frequency The main setting individual control 0 0 Y 57 The auxiliary setting individual con...

Страница 23: ...110 100 Y 60 F12 Maximum frequency 10 00 320 00 50 00 N 60 F13 Lower frequency 0 00 Upper frequency 0 00 N 61 F14 Upper frequency Lower frequency Upper frequency 50 00 N 61 F15 Basic frequency 5 00 M...

Страница 24: ...p when the DC braking current 0 135 100 Y 64 F29 Stop and braking wait time 0 0 60 0 0 0 Y 64 F30 Brake time stop 0 0 60 0 0 0 Y 64 F31 Stop and brake starting frequency 0 00 Max frequency 0 00 Y 64 F...

Страница 25: ...et frequency working time 0 0 60 0 0 0 Y 67 F45 Motor running direction 1 bit Direction command forward command FWD let motor forward running 0 0000 N 67 Direction command forward command FWD let moto...

Страница 26: ...min 1 Acceleration time h 2 Acceleration time day 3 1000bit Deceleration time s 0 Deceleration time min 1 Deceleration time h 2 Deceleration time day 3 F49 Running configuration word 1 bit Running dir...

Страница 27: ...ard DC bus voltage 70 Y 72 A10 Power down tracking options N 0 0 Y 72 Power off tracking mode 1 Startup tracking mode 2 A11 Power down tracking time 0 0 20 0 0 0 Y 73 A12 Power down frequency drop poi...

Страница 28: ...Y 75 A26 Fault reset time 0 5 20 0 1 0 Y 75 A27 Fan startup temperature 0 0 60 0 0 0 Y 75 A28 This inverter communication address 1 128 8 Y 76 A29 Baud rate Baud rate is 1200 0 4 Y 76 Baud rate is 240...

Страница 29: ...0 0FF 0FF Y 77 A38 UP DN control 1 bit Power down to save 0 0000 Y 78 Power down to clear saving 1 10 bit Saving after stopping 0 Stop command to clear saving 1 Cleared at the end of stopping 2 100 b...

Страница 30: ...5 A40 UP DN adjustment value 300 00 300 00 0 00 N 80 A41 UP adjustment ratio 0 01 20 00 0 01 Y 80 A42 DN adjustment ratio 0 01 20 00 0 01 Y 80 A43 A44 The definition of multifunction keys MF1 and MF2...

Страница 31: ...82 A50 Keyboad potentiometer control 1bit Saving after power down 0 0000 Y 82 Cleared after power down 1 10bit Saving after stoppoing 0 Clear saving after stopping command 1 Clear saving at end of st...

Страница 32: ...t X2 corresponding value Y28000 83 o08 AI2 input X1 corresponding Value Y1 100 0 100 0 0 0 Y 83 o09 AI2 input X2 corresponding value Y2 100 0 100 0 100 0 Y 84 o10 AI3 input X1 corresponding value Y180...

Страница 33: ...O4output signal select 48000 No function 0 0 0 1 8 Y Y Y Y 86 Fault warning 1 Over current inspection 2 Over load inspection 3 Over voltage inspection 4 Less voltage inspection 5 Low load inspection 6...

Страница 34: ...er limitation 30 Arrival of current lower limitation 31 Time to reach limit time 1 32 Time to reach limit time 2 33 Inverter ready to run operation 34 o25 Output signal delay 1 0 32 000 0 Y 89 o26 Out...

Страница 35: ...minalfunction selection 8000 DI6 inputterminalfunction selection 8000 DI7 inputterminalfunction selection8000 DI8 inputterminalfunction selection8000 AI1 inputterminal functionselection8000 AI2 inputt...

Страница 36: ...unning control mode switch 3 25 FWD torque upper limit switch 1 26 FWD torque upper limit switch 2 27 FWD torque upper limit switch 3 28 REV torque upper limit switch 1 29 REV torque upper limit switc...

Страница 37: ...ue loading 49 Out fault signal input level 50 1 pump start 51 1 pump stop 52 2 pump start 53 2 pump stop 54 3 pump start 55 3 pump stop 56 4 pump start 57 4 pump stop 58 Manual rotate command 59 Time...

Страница 38: ...bit Reload after power on 0 Be cleared after powter on 1 Keep count after power on 2 1000bit Counting period 0 Output signal valid time 20ms 1 Output signal valid time 100ms 2 Output signal valid tim...

Страница 39: ...t Time 1 0 0 3200 0 2 0 Y 103 o68 Limit Time 2 0 0 3200 0 2 0 Y 103 5 1 6 Multi speed PLC Group H00 H55 0x0300 0x0337 Code Description LCD Setting Range Factory Setting Change Limited Reference page H...

Страница 40: ...1 1000 bit Running at the speed when start up segment 0 Running at the speed before the machine stopped 1 H03 1 Segment speed setting 1X Lower frequency upper frequency 3 00 Y 106 H04 2 Segment speed...

Страница 41: ...ent running time T3 0 0 3200 0 2 0 Y 108 H22 4 Segment running time T4 0 0 3200 0 2 0 Y 108 H23 5 Segment running time T5 0 0 3200 0 2 0 Y 108 H24 6 Segment running time T6 0 0 3200 0 2 0 Y 108 H25 7...

Страница 42: ...ites 1 Running time hours 2 Running time days 3 100 bit Acceleration time seconds 0 Acceleration time munites 1 Acceleration time hours 2 Acceleration time days 3 1000bit Deceleration time seconds 0 D...

Страница 43: ...V F setting voltage 4 U05 U09 40 N 112 U08 V F setting frequency5 U06 U10 25 00 N 112 U09 V F setting voltage 5 U07 U11 50 N 112 U10 V F setting frequency6 U08 U12 30 00 N 112 U11 V F setting voltage...

Страница 44: ...rnal analogy giving 2 AI3 external analogy giving8000 3 Keyboard potentiometer giving 4 Multi step digital voltage giving 5 Digital pulse set 6 P04 Keyboard set signal 0 0 100 0 50 0 Y 114 P05 PID int...

Страница 45: ...ation power 13 Current regulation power 14 Extruding machine 15 E01 Starting pressure deviation 0 0 100 0 10 0 Y 115 E02 Starting delay time 0 0 3200 0 5 0 Y 115 E03 Stop frequency 0 50 00 5 00 N 115...

Страница 46: ...0000 Y 118 Variable frequency pump stop 1 Free stop 2 Water supply pump stop 3 10 bit all pumps status when fault occur Keep current situation 0 All pumps stop 1 100 bit Altern ation shift mode Variab...

Страница 47: ...bit Pump 2 stop 0 Pump 2 run invariable frequency 1 Pump 2 run inworking frequency 2 100bit Pump 3 stop 0 Pump 3 run invariable frequency 1 Pump 3 run in working frequency 2 1000bit Pump 4 stop 0 Pump...

Страница 48: ...1 C01 Speed loop low speed Ti 0 01 100 00 0 25 Y 122 C02 Speed loop low speed Td 0 000 1 000 0 000 Y 122 C03 Speed loop low speed P 0 150 100 Y 122 C04 Speed loop low speed shift frequency 0 0 C08 7 0...

Страница 49: ...ting mode 1 bit Setting mode Set by keyboard or RS485 0 0000 Y 123 AI1 external analogy8000 1 AI2 external analogy giving 2 AI3 external analogy giving8000 3 Keypad potentiometer giving 4 Multi step d...

Страница 50: ...eration time 0 0 200 0 1 0 Y 123 C23 Low speed excitation compensation 0 100 30 Y 123 C24 Current loop Ti 0 9999 500 Y 123 C25 Current loop P 0 1000 100 Y 123 C26 PG electronic gear A 1 5000 1 Y 123 C...

Страница 51: ...inductance 0 0 3200 0 Y 127 b09 Motor 1 mutual inductance 0 0 3200 0 Y 127 b10 Motor selection Motor 1 0 0 N 127 Motor 2 1 b11 Motor parameter measurement No measurement 0 0 N 127 Calculate by label...

Страница 52: ...y01 Parameter upload to keyboard No action 0 0 N 129 Reset system parameter with keyboard memory area1 1 Reset system parameter with keyboard memory area2 2 Reset system parameter withb keyboard memor...

Страница 53: ...5 2 Functional parameter specification 5 2 1 Menu Group Code Description LCD Function Discription Group ID Reference page S Monitor function group Monitor frequency current and other 16 monitor objec...

Страница 54: ...50 00Hz Gain Speed surveillance A35 100 0 the pole of the motor b03 b16 2 the real speed of the motor 1500rpm When stop based Residual voltage test motor speed renew speed 500ms The real speed 60 resi...

Страница 55: ...verter driving a motor occasions suitable for a inverter driving multiple motors occasions suitable for the inverter as a variable frequency power supplies 1 Sensorless vector control High performance...

Страница 56: ...ent digital voltage setting o36 o46 IO input terminal function set to 11 12 13 switch H47 H54 Multi digital voltage setting 100 Corresponding to the maximum frequency 6 Digital pulse setting Digital p...

Страница 57: ...minal and DI8 terminal reseting After use digital pulse input o43set to 0 Otherwise the function settings will take effect can check the pulse input status o58 be limited to low speed pulse 7 PID regu...

Страница 58: ...n auxiliary setting frequency main auxiliary setting frequency f f f The relationship between main give and auxiliary given Main Auxiliary f f f t f f f f f max f t max f auxiliary main setting freque...

Страница 59: ...the keyboard terminal Rs485 the slave unit will not run the proportion liknge host unit s command it needs once again to respond to host commands through the keyboard terminal RS485 or the proportion...

Страница 60: ...e torque curve torque boost Cut off frequency Constant torque curve torque boost motor rated voltage Enhance voltage Basic frequency Voltage Cut off frequency Frequency Frequency Torque increase is ma...

Страница 61: ...frequency Start the motor that in the status of stopping the inverter outputs accelerate starting from 0Hz accordance with the step 1 acceleration time towards the upper or the setting frequency to a...

Страница 62: ...ric disturbance Switch dissipation is expressed as following Carrier frequency Motor noise Electric disturbance Switch dissipation 1 0KHz Big Small Small Big Small Big 8 0KHz 16 0KHz The relationship...

Страница 63: ...t the slope of the output frequency at constant segment 3 Indicate that the slope of the output frequency is reduced to 0 from the max Such as setting the S curve acceleration and deceleration acceler...

Страница 64: ...ncy set frequency Minimum frequency lower limit frequency lower limit frequency lower limit frequency actual frequency set frequency Minimum frequency lower frequency Minimum frequency Minimum frequen...

Страница 65: ...orque and can not exceed the motor rated current braking frequency time time Stop braking RUN STOP STOP OFF stop braking time RUN ON setting frequency output frequency stop brake wait time setting fre...

Страница 66: ...time before jog 0 Jog end and acceleration deceleration time save the set acceleration and deceleration time before jog 1 F36 Jog frequency setting Lower frequency upper frequency Hz 6 00 Y Jog accel...

Страница 67: ...y area F43 Preset frequency 0 00 Max frequency Hz 0 00 Y F44 Preset frequency working time 0 0 60 0 s 0 0 Y After inverter startup it firstly run with preset frequency running time is preset frequency...

Страница 68: ...parameter to achieve the motor forward to reverse or from reverse running to forward the waiting time of motor speed being zero F47 output frequency running time F47 Frequency multiple setting 1 0 0 N...

Страница 69: ...4 Adjustment of keyboard potentiometer giving Actual acc time Acc time keyboard potentiometer giving percentage 5 Adjustment of multi steps digital voltage giving Actual acc time Acc time multi steps...

Страница 70: ...05 0 1 2 control direction of 0 step speed When running control mode F05 3 Setting the value and terminal FWD REV jointly decide the direction of 0 step speed FWD priority FWD 1runningdirection REV 1r...

Страница 71: ...0B00 0B01 0B02 Y Y Y X1000 X100 X10 bit 00 0B 0 63 0x00 0x3F Code Keyboard display Parameter group N Function spec Parameter N 16 hexadecimal input S Monitor function group 0B S 0 16 0x00 0x10 F Basi...

Страница 72: ...fluctuate the output voltage fluctuation is very small the V F curve characteristic has always been close to setting state of rated input voltage 0 Function invalid 1 Function Valid 2 Function Valid...

Страница 73: ...tracking from 0 Hz 1 Power down tracking When the inverter instantaneous power off and re start the motor will continue running with current speed and direction If the power off time is longer than A...

Страница 74: ...drop speed In operation process when the motor current surpass value A16 set motor will decelerate according to deceleration time A15 set until current below value A16 set In operation process when th...

Страница 75: ...n Series Electronic Thermal Protection Level Parameters F 120 A24 G 150 A24 A24 set the electronic thermal protection level When the current is the rated motor current multiples the parameter the driv...

Страница 76: ...ation The proportion of linkage function The proportion of linkage host inverter This inverter communication address 128 Communication interface A is set as host inverter communication interface for p...

Страница 77: ...inverter running accumulating or not 0 Auto clear to 0 after power on 1 Continue to accumulate running time after power on A34 Unit of total running time hour 0 0 Y Day 1 The set for unit of accumulat...

Страница 78: ...FWD key 1 0 Unlock STOP key 1 Lock STOP key 2 0 Unlock PRG key 1 Lock PRG key 3 0 unlock SET key 1 Lock SET key 4 0 Unlock ESC key 1 Lock ESC key 5 0 Unlock MF1 key 1 Lock MF1 key 6 0 Unlock MF2 key...

Страница 79: ...P DN control validity of adjustment 0 UP DN invalid adjustment 1 UP DN valid adjustment A39 UP DN time 1 bit UP fix speed 0 0000 N UP fix times 1 10 bit DN fix speed 0 DN fix times 1 100 bit UP N adju...

Страница 80: ...rcentage given by A41 multi steps digital voltage 1000 bit DN adjustment mode of adjusting speed ratio 0 N adjustment of acceleration time No adjustment 1 AI1 adjustment of the external analog giving8...

Страница 81: ...unction keys adjust the parameter values 2 MF is defined as a freedom stop function key Monitoring the menu Parameter select a menu of the key to effectively frequency inverter parking stopped parking...

Страница 82: ...d potentiometer set 0 0 100 00 Y Displaying value potentiometer set which can be revised by potentiometer under monitor menu Value potentiometer set can be regarded as analog of frequency giving set v...

Страница 83: ...isplaying value of motor temperature A5 surpassed value A52 inverter will warn and react according to reaction for motor over heat A53 set A54 Display of motor temperature8000 50 0 300 0 N Shows the m...

Страница 84: ...100 0 Y o10 AI3 input X1 corresponding value Y18000 100 0 100 0 0 0 Y o11 AI3 input X2 corresponding value Y28000 100 0 100 0 100 0 Y Max frequency 50 00hz X1 0 Y1 0 potentiometer 0V corresponding set...

Страница 85: ...00 X2 Y2 100 10V X1 Y1 5V 50 AI2 AI3jump as JP6 JP7 instruction as o12 AI1 input filter time 8000 o13 AI2 input filter time 0 00 2 00 s 0 10 Y o14 AI3 input filter time8000 0 00 2 00 s 0 10 Y Filter t...

Страница 86: ...0 max frequency Actual current 3 0 200 corresponding parameter S03 percentage of output curent Output voltage 4 0 200 corresponding parameter b02 b15 rate voltage of motor DC bus voltage 5 0 1000VDC D...

Страница 87: ...Fault warning 1 Over current inspection 2 Over load inspection 3 Over voltage inspection 4 Less voltage inspection 5 Low load inspection 6 Over heat inspection 7 Running state with command 8 Abnormal...

Страница 88: ...or after fault with unconfirmed status 2 Over current inspeciton Inverter met fault of over current 3 Over load inspeciton Inverter met fault of over load of heat protection 4 Over voltage inspeciton...

Страница 89: ...l at low pressure 27 Arrival of inverter rate current Arrival at inverter rate current 28 Arrival of motor rate current Arrival at motor rate current 29 Arrival of input frequency lower limitation Pre...

Страница 90: ...ct After terminal reaction inverter will inspect FDT set frequency 2 When inverter output frequency is below of frequency 2 FDT set the corresponding signal output terminal will not react o31 frequenc...

Страница 91: ...ning control 2 5 10bit Power on terminal running command invalid 0 Power on terminal running command valid 1 Setting terminal running mode by this parameter 1 bit set terminal running mode The polarit...

Страница 92: ...level Falling edge Falling edge Falling edge Up edge Low level Falling edge Up edge Up edge X High level Up edge X 2 Two ware running control 1 FWD REV REV RUN STOP COM STOP FWD F05 1 F05 3 F05 4 Com...

Страница 93: ...command invalid when power on Only run 3S later after power on and set terminals invalid 1 Terminal run command valid when Power on Terminal status is effective when power on inverter will run immedia...

Страница 94: ...11 Multi digital voltage 2 12 Multi digital voltage 3 13 Frequency setting main way 1 14 Frequency setting main way 2 15 Frequency setting main way 3 16 Frequency setting assist way 1 17 Frequency se...

Страница 95: ...2 switch 38 Free stop 39 Up command 40 Down command 41 Automatic program running function cancel 42 Automatic program running stop 43 Program running start mode 44 Program running stop mode 45 Pulse c...

Страница 96: ...can set to edge trigger or level trigger 3 Three wire running STOP o35 set three wire running STOP function 4 Multistage speed command 1 Combine 16 step multi step setting Detail H parameter system 5...

Страница 97: ...t switch Detail read C parameter system C16 30 REV torque up limit switch 2 31 REV torque up limit switch 3 32 Torque speed switch Vector control mode speed control mode and torque control mode switch...

Страница 98: ...rt or stop Soft start control must use 2 terminal control stop priority Need to set E01 load model 9 E12 1pump is soft start control pump 52 1 pump stop 53 2 pump soft start Electric leverl spring con...

Страница 99: ...0000 Y This parameter is used to select each IO pin polarity in which the effective 0 10 Input terminal polarity 12 15 Output terminal polarity 0 Low level valid closed 0 Low level valid closed Falli...

Страница 100: ...id time 20ms 1 Output signal valid time 100ms 2 Output signal valid time 500ms 3 0 bit Counting mode of control 0 Recycle count the count value reaches maximum Pulse output to reach output terminal to...

Страница 101: ...r status 0 9999 0 Y o54 Preset count value for a given 0 o55 0 Y o55 Max count value for a given o54 9999 9999 Y The correspondind indication of Yi terminal when input pulse signal count reach the pre...

Страница 102: ...o63 SPA pulse output rate 1 1000 1 Y o64 SPB pulse output rate 1 1000 1 Y SPA SPB provide two isolated pulse output signal can be analogical multiple analog output signals SPA SPB provide high speed p...

Страница 103: ...erved 100bit Reserved 1000bit Reserved 1 bit Timing mode 0 Boot time timing of runnig and breaking 1 Running timing only timing of running 10 bit Reserved 100 bit Reserved 1000 bit Reserved o67 Limit...

Страница 104: ...t speed running 0 deceleration time decided by the H26 H39 1 The acceleration and deceleration time determined by terminal 1000 bit Set running time of defined program running 0 Running time decided b...

Страница 105: ...t Single cycle 0 0000 Y Continuous cycle 1 One cycle command running 2 10 bit The zero speed running when pause 0 Fixed speed running when the suspension 1 100 bit Stop with the parameters set when st...

Страница 106: ...0 bit Running condition when pause 0 Speed run when pause 1 Fixed Segment Speed operation when pause 100 bit Running Segment when stop 0 Set stopping according to the parameters of stop segment 1 Set...

Страница 107: ...ed setting 2X Lower frequency upper frequency Hz 6 00 Y H05 3 Segment speed setting 3X Lower frequency upper frequency Hz 9 00 Y H06 4 Segment speed setting 4X Lower frequency upper frequency Hz 12 00...

Страница 108: ...inal speed command 2 OFF OFF ON ON OFF OFF ON ON Multiterminal speed command 3 OFF OFF OFF OFF ON ON ON ON Multiterminal speed command 4 OFF OFF OFF OFF OFF OFF OFF OFF Speed Terminal 8X 9X 10X 11X 12...

Страница 109: ...eleration time dt3 0 0 3200 0 s 10 0 Y H31 4 Segment acceleration time at4 0 0 3200 0 s 10 0 Y H32 4 Segment deceleration time dt4 0 0 3200 0 s 10 0 Y H33 5 Segment acceleration time at5 0 0 3200 0 s...

Страница 110: ...me seconds 0 Running time munites 1 Running time hours 2 Running time days 3 100 bit Acceleration time seconds 0 Acceleration time munites 1 Acceleration time hours 2 Acceleration time days 3 1000bit...

Страница 111: ...ent digital voltage giving 100 0 100 0 50 0 Y H53 6 Segment digital voltage giving 100 0 100 0 60 0 Y H54 7 Segment digital voltage giving 100 0 100 0 70 0 Y Digital voltage set function can analogy g...

Страница 112: ...he third frequency value of V F curve corresponding to V3 U05 V F setting voltage 3 U03 U07 30 N User defined the third voltage percentage of V F curve on the base of rated output voltage 100 of frequ...

Страница 113: ...ge Limited P00 PID configuration 1 bit Unidirectional regulation 0 0000 N Bidirectional regulation 1 10 bit Negative effect 0 Positive effect 1 100 bit PID fault No action 0 Warning continuous running...

Страница 114: ...lection can select keyboard Rs485 potentiometer digital voltage digital pulse for feedback signal P03 Setting signal selection Set frequency by keyboard or RS485 0 2 Y AI1 external analogy giving 8000...

Страница 115: ...n defines regulation intensity of PID regulator the larger the P is the more the intensity is When proportion gain is 100 and the difference between PID feedback and getting value is 100 PID regulator...

Страница 116: ...sure water supply 9 Reserved 10 Reserved 11 Torque control 12 Voltage regulation power 13 Current regulation power 14 Extruding machine 15 Details see Appendix IV E01 Starting pressure deviation 0 0 1...

Страница 117: ...nal select 25 then it will output arrival signal E06 Low pressure arrival value 0 100 0 10 0 Y When feedback pressure less than the low pressure of the reached value of this parameter the I O output t...

Страница 118: ...ternation ways and time of pump When Timing Shift Alternation Time is set to 0 0 hour and cancel Timing Shift Alternation function When the Timing Shift Alternation Time between 0 1 3 200 after corres...

Страница 119: ...No 2 pump No 3 pump If the current No 1 pump frequency No 2 pump frequency No 3 pump convert frequency after reduce pump No 1 pump frequency No 2 pump convert frequency after add pump 1 pump frequency...

Страница 120: ...ault 13 E OHt Motor over heated fault 14 E OL2 Motor over loading fault 15 E PG PG fault 16 E PHo Inverter output Phase lost 17 E COA RS485 communication A fault 18 E COb RS485 communication B fault T...

Страница 121: ...quency 1 Pump 1 run in working frequency 2 10 bit Pump 2 stop 0 Pump 2 run invariable frequency 1 Pump 2 run inworking frequency 2 100bit Pump 3 stop 0 Pump 3 run invariable frequency 1 Pump 3 run in...

Страница 122: ...s unstable So it is necessary to consider the stability and the response speed at the same time when setting the value C01 Speed loop low speed Ti 0 01 100 00 s 0 25 Y It defines the integral time of...

Страница 123: ...ibration if the gain is small the reaction lag C08 Speed Loop And High speed Switching Frequency C04 Max frequency Hz 30 00 Y It defines Integral time of speed loop high speed the parameter and switch...

Страница 124: ...external analogy giving8000 3 Keypad potentiometer giving 4 Multi step digital 5 Digital pulse set 6 10bit direction Direction uncontrolled 0 Direction controlled 1 C17 Torque set gain 0 0 300 0 200 0...

Страница 125: ...e both can control direction C15 0x14 C16 0x14 Potentiometer corresponding setting value A48 100 A49 100 Keyboard potentiometer set A47 100 C17 200 0 C13 forward upper torque 100 200 0 200 0 control d...

Страница 126: ...2 torque acceleration time turning moment deceleration torque control mode and effective Torque acceleration time torque accelerated from 0 to 300 hours Torque speed torque from 300 down to 0 C23 Low...

Страница 127: ...contact our company C31 PG dropped inspection time 0 0 10 0 s 1 0 N PG feedback signal is 0 exceed C31 set time system reports PG dropped fault Set speed to 0 or set C31 to 0 don t check PG dropped f...

Страница 128: ...culates and measuresautomatically b05 b09 is the motor s basic electric parameters these parameters is essential to achieve vector control calculation b10 Motor selection Motor 1 0 0 N Motor 2 1 The s...

Страница 129: ...et this parameter the motor parameters will be determined dynamically Be sure the motor is without load N load operation Before setting be sure to run well prepared the motor will run in high speed du...

Страница 130: ...alue When this parameter set valid all the function parameter reset to factory setting The parameters without factory setting will save the previous setting value y01 Parameter upload to keyboard No a...

Страница 131: ...OU Over voltage 5 E LU Under voltage 6 E OL Over load 7 E UL Under load warning 8 E PHI Power input Phase loss 9 E EEP EEPROM error 10 E ntC Over heat 11 E dAt Time limit fault 12 E Set External faul...

Страница 132: ...temperat y08 Fault record reset No action 0 0 Y Reset 1 0 No action the fault records retains 1 The fault records resets y09 Rated output current 0 1 1000 0 A N Inverter rated output current y10 Rate...

Страница 133: ...999 Set range Y No password or decode input is correct deco Display info Parameter lock in code The parameter sets the password and the range is 0 9999 After setting the password parameter locks and k...

Страница 134: ...start after powering down or free run Remember the set operating state Too much load on the motor Check the load condtion and confirm the model selection is right Over current E OC Fault display E OC...

Страница 135: ...line has too small capacity or great rush current exists on the lines Make renovation on power supply system Over heat E OHt Too high ambient temperature Improve ambient conditions Cooling fans do no...

Страница 136: ...rter type Light Load F Standard Load G Structure item PF kW IF A PG kW IG A Single phase voltage 220V 50 60Hz PI8600 1 0 75 4 0 4 2 5 7N1 PI8600 1 1 5 7 0 75 4 7N1 PI8600 1 1 5 7 7N1 7 1 2 Table of ra...

Страница 137: ...rate decelerate control Sub set S curve acceleration and deceleration mode maximum acceleration and deceleration time is 3200 days Long running time control 16 segments speed run maximum running time...

Страница 138: ...inds of functions to achieve forward reverse forward jog and reverse jog emergency stop reset speed acceleration speed run time switch and pulse counting 1 way analog inputs Can be defined as a switch...

Страница 139: ...wayl analog input pulse input digital potentiometers Motor 2 goups of motor parameters With the motor parameters parameter can be selected parameter identification automatic storage 3 identification...

Страница 140: ...djust or inspect High voltage inside Maintained by the well trained personnel Confirm the input and output dc control cables are well connected Adjust or inspect the inner circuits after power down an...

Страница 141: ...Section VII Standard Specifications 139 Section VII 7 3 2 Keyboard Size JP6C8000 Size...

Страница 142: ...rd specifications Main circuit Body Input output terminal Main circuit Overall conditions If the fastenings come loose if any signs show overheat discharging or too high dust content or the air piping...

Страница 143: ...ately after delivery to the user and need to keep well for the time being or stored for a long time Stored in a dry and adequately ventilated place without dust and metal powder at the temperature spe...

Страница 144: ...face methods Asynchronism communication methods semi duplex the previous high byte low byte in the post and low effective bit pre emptive Data fumula 1 start bit 8 data bits 1 stop bit invalid parity...

Страница 145: ...ight set communication parameters as following A29 baud rate 0 1200 1 2400 2 4800 3 9600 4 19200 5 38400 A28 current inverter communication address 1 127 If there are more than 1 inverters don t use t...

Страница 146: ...ble and is linked to the signal terminal SH of RS485 Data packet using CRC vertical lengthy test frame detection to ensure data reliability Completely isolated RS485communication module to ensure reli...

Страница 147: ...tart address Slave Address Function code Registers address Register number CRC Checksum Frame end address 3 5 bytes 1 bytes 1 bytes 2 bytes 2 bytes 2 bytes 3 5 bytes Slave response Frame Start address...

Страница 148: ...ave address Function code Read byte number switch state CRC checksum frame end address 3 5bytes 1 byte 1 byte 1byte data N N bytes 2 bytes 3 5bytes Note read byte number N output quanlity 8 if the rem...

Страница 149: ...0 71 H 0x03 0 55 U 0x04 0 15 P 0x05 0 15 E 0x06 0 23 C 0x07 0 47 b 0x08 0 23 yNOTE 1 0x09 0 23 S 0x0B 0 15 0x03 read inverter status Status Status number R 0x10 0x00 Running status NOTE 2 0x01 Reserve...

Страница 150: ...and 2 0x03 Reserved command 3 Function parameter write EEPROM register address high byte original register address high byte 0x80 0x06 write inverter single function code parameter 0x10 write inverter...

Страница 151: ...ower frequency 0 Lower frequency 1 Arrive 8 JOG running 0 No JOG running 1 JOG running 9 Reserved 10 Reserved 11 Reserved 12 Fault confirm 0 Confirmed fault 1 Unconfirmed fault 13 Direction status 0 N...

Страница 152: ...Valid 10 AI3 input8000 0 Invalid 1 Valid Output terminal function 0x02 0 O1 input 0 Invalid 1 Valid 1 O2 input 0 Invalid 1 Valid 2 O3 input 0 Invalid 1 Valid 3 O4 input 0 Invalid 1 Valid Fault type 0x...

Страница 153: ...or over load fault 19 E PG PG error 20 E PHo Inverter output phase loss 21 E COA Rs485 communication port A fault 22 E COb Rs485 communication port B fault 23 E CAL Parameter indentification fault 0x0...

Страница 154: ...d 1 DI2 input 0 Invalid 1 Valid 2 DI3 input 0 Invalid 1 Valid 3 DI4 input 0 Invalid 1 Valid 4 DI5 input8000 0 Invalid 1 Valid 5 DI6 input8000 0 Invalid 1 Valid 6 DI7 input8000 0 Invalid 1 Valid 7 DI8...

Страница 155: ...ltage Valid operation Invalid operation y11 products series 80 0 3 Invalid operation Family serial products series Input voltage level The number should be decimalization y12 soft ware version Valid o...

Страница 156: ...e Reserve Reserve bit 7 bit 6 bit 5 bit 4 bit Meaning 0 No free stop 1 Free stop command Reserve 0 JOG stopping 1 JOG running Reserve bit 3 bit 2 bit 1 bit 0 bit Meaning Reserve 0 Reverse command 1 Fo...

Страница 157: ...bit7 bit4 bit3 bit0 F 0 Forward command F 0 Forward status 0 Separative sign A 1 Accelerating running R 1 Reverse command R 1 Reverse status D 2 Decelerating running S 2 Stop command S 2 Stop status...

Страница 158: ...yboard set frequency orRS485 Slave address Function code Read byte number Read content CRC checksum 0x08 0x03 0x04 0x1388 0x0000 0xE79D Read byte number 2byte register number 0x06 write inverter singl...

Страница 159: ...number CRC checksum 0x08 0x01 0x0300 0x0020 0x3D0F Salve response inverter low voltage E LU switch address 0x0305 Slave address Function code Read byte number Switch state CRC checksum 0x08 0x01 0x04...

Страница 160: ...ning and it can realize forced stopping by terminal or keyboard if need For this function the host computer should be set with the following parameters A28 Local communication address 128 For this fun...

Страница 161: ...e and desist commands then the slave will respond the command again to run A28 communication address 1 127 A29 Baud rate Same as host A30 Communication format Same as host A55 Proportional linkage fac...

Страница 162: ...he frequency or Rs485 0 F03 Auxiliary setting mode of frequency set AI2 external analog setting 1 F04 relationship between main and auxiliary frequencies main Auxiliary 2 F05 Running control mode Prop...

Страница 163: ...Appendix II 161 Appendix II System wire connections...

Страница 164: ......

Страница 165: ...me time When speed up When speed down Failure Type OC OC P OC C OC FA OC 2 Abnorma l voltage OU LU OL UL Other display fault OH E FL PH O PID PG PG Error DATE use date expired EEPR EEPROM Board Failur...

Страница 166: ...rvice faster and more convenient please visit our company web site http www powtran com and refer to column technologies and services and Download for feedback 1 download the updated manual for your p...