Appendix II
75
A
p
p
en
d
ix
II
the RAM value.
If F group parameters need to achieve the function, as long as change high order F of the
function code address to 0. If E group parameters need to achieve the function, as long as change
high order F of the function code address to 4. The corresponding function code addresses are
indicated below: high byte: 00 to 0F(F group), 40 to 4F (E group), 50 to 5F(B group),60 to 67(Y
group)low byte:00 to FF
For example:
Function code F3.12 can not be stored into EEPROM, address indicates as 030C; function
code E3.05 can not be stored into EEPROM, address indicates as 4305; the address indicates that
only writing RAM can be done and reading can not be done, when reading, it is invalid address.
For all parameters, you can also use the command code 07H to achieve the function.
Stop/Run parameters section:
Parameter address
Parameter description
1000
*Communication set value(-10000 to10000)(Decimal)
1001
Running frequency
1002
Bus voltage
1003
Output voltage
1004
Output current
1005
Output power
1006
Output torque
1007
Operating speed
1008
DI input flag
1009
DO output flag
100A
AI1 voltage
100B
AI2 voltage
100C
Reserve
100D
Reserve
100E
Reserve
100F
Load speed
1010
PID setting
1011
PID feedback
1012
PLC step
1013
High-speed pulse input frequency, unit: 0.01kHz
1014
Reserve
1015
Remaining run time
1016
AI1 voltage before correction
1017
AI2 voltage before correction
1018
Reserve
1019
Linear speed
101A
Current power-on time
101B
Current run time
101C
High-speed pulse input frequency, unit: 1Hz
101D
Communication set value
101E
Reserve
101F
Master frequency display
1020
Auxiliary frequency display
Note:
There is two ways to modify the settings frequencies through communication mode: