81
第
十
章
Ch
ap
ter 9
Chapter 9 Options
1.Power cables
The dimension of input power cable and motor cable should meet the local provision:
Input power cable and motor cable should bear the related load current.
The maximum rated temperature margin conditions of the motor cable should not be sustained
below 70 degrees.
Conductivity of the PE conductor and phase conductor capacity are the same(same cross-
sectional area),
About EMC requirements, see "EMC Guidance Content"
To meet the CE EMC requirements, a symmetrical shielded motor cable must be used (see
figure below).For input cables can use four-core cable, but still recommended to use shielded
symmetrical cable. Compared to a four-core cable, shielded symmetrical cables can not only
reduce the loss and cost of the current flowing through the motor cable, but also can reduce the
electromagnetic radiation.
PE conductor
shield
conductor
Jacket
Insulation
shield
PE
Symmetrical shielded motor cables
Four-core cable
PE
conductor
conductor
Jacket
Jacket
Insulation
Insulation
Note: If conductivity of the cable shield can not meet the requirements, you must use a separate
PE conductor.
To play a protective role of conductor, when the shield wire and phase conductors using the
same material, the cross-sectional area of the shield wire and phase conductors cross-sectional area
must be the same, aims to reduce grounding resistance, impedance continuity better.
To effectively suppress RFI transmission and conduction, the shield conductivity must be at
least 1/10 of the phase conductor conductivity. For copper or aluminum shield, this requirement is
very easy to meet. Minimum requirements for the drive motor cable as shown below. Cable
comprising a layer of copper spiral. Shield tight as possible, that the more tightly the more we can
effectively suppress radiated electromagnetic interference.
Insulating layer
Shield
Cable cross section
2. Control Cable
All analog control cables and cables for the frequency input must be shielded. Analog signal
cable double-shielded twisted pair cable as shown in Figure 1. Each signal uses one pair
individually shielded twisted pair cable pair. Do not use the different analog signal with a ground
wire.