Powtier Controls MAXIWAT TC230E Series Скачать руководство пользователя страница 3

Powtier Controls Limited 

TC230E Instruction Manual 

230E\IM 

- 3 - 

20 June 1998

 

 

Issue 1.0 

Under  normal  operating  conditions  it  is  important 
that  the  TC230E  power  switching  unit  should  be 

mounted 

VERTICALLY   (as  shown  in  figure  1 

and  2),  with  the  FAN  end  facing  DOWNWARDS. 
Also  the  ambient  temperature  should  not  exceed 
50ºC. 
 
If the TC230E cannot be mounted vertically or if the 
ambient  temperature  is  higher  than  50ºC,  please 
contact your supplier or Tactical Controls directly to 
determine   suitability   and   possible   operating 
constraints. 
 

PROTECTION FUSE 

 
The  integral  fuse  in  a  MAXIWAT  thyristor  unit  is 
designed primarily to protect the thyristors from any 
excessive  over  current  condition.  In  the  event  of  a 
fuse   blowing,   the   replacement   must   be   a   high 
speed   H.R.C.   fuse   of   an   approved   type. 
Replacement  fuses  can  be  ordered  directly  from 
Tactical Controls or an equivalent type can be used. 
Fuse  types  for  different  current  ratings  are  given  in 
Table 1. 
 

WIRING 

 
There   are   four   basic   load   configurations   to   the 
three-phase  zero-voltage  thyristor  switching  units; 
and these are:- 
 
Figure 1b. 3-phase, star connected load. 
 
Figure  1c.  3-phase,  3-wire,  closed  delta  connected 
load. 
 
Figure 2b. 3-phase, 4-wire, star connected load. 
 
Figure 2c. 3-phase, open-delta connected load. 
 
The  basic  wiring  is  as  follow:  the  (LINE)  terminal 
must be connected to the load supply L1, L2 or L3. 
One  end  of  the  load  must  be  connected  to  the 
(LOAD)  terminal  LOAD1,  LOAD2  or  LOAD3.  The 
loads can be connected in star or delta as shown in 
figure 1 and 2. 
 
When   connecting   the   LINE   and   LOAD   to   the 
TC230E, it is important to have the user connection 
and  internal  connection  right  next  to  each  other  so 
that  the  two  crimps  make  direct  contact.  This  is  to 
minimise contact resistance. 
 
The input  logic signal supply must be connected to 
the   terminals   marked   with   `I/P+'   and   `I/P-',   and 

these   can   be   connected   in   parallel.   The 
recommended  minimum  input  cable  size  is  0.5mm 

square. 
 

Table  1.  Fuses  and  fuse  ratings  for  the  TC230E 
MAXIWAT range. 
 
Current Voltage  Tactical 

Equivalent 

Rating  Rating  Part no. 

Type 

(Arms)  (Vrms) 
 
40A 

240V 

FUS-50LET 

BRUSH-50LET 

 

440V 

FUS-45ET 

BRUSH-45ET 

55A 

240V 

FUS-63LET 

BRUSH-63LET 

 

440V 

FUS-80ET 

BRUSH-80ET 

75A 

240V 

FUS-80LET 

BRUSH-80LET 

 

440V 

FUS-90EET 

BRUSH-90EET 

100A 

240V 

FUS-140EET  BRUSH-140EET 

 

440V 

FUS-140EET  BRUSH-140EET 

125A 

240V 

FUS-160EET  BRUSH-160EET 

 

440V 

FUS-160EET  BRUSH-160EET 

INSTALLATION

 

M6 SCREW

SPRING WASHER

PLAIN WASHER

M6 NUT

PCB

USER CONNECTION

INTERNAL CONNECTION

User connection for LOAD and LINE. 

Содержание MAXIWAT TC230E Series

Страница 1: ...nstruction Manual 230E IM 1 20 June 1998 Issue 1 0 TC230E MAXIWAT RANGE OF THYRISTOR SWITCHING UNITS INSTRUCTION MANUAL DESCRIPTION 2 EMC COMPLIANCE 2 INSTALLATION 3 DIAGNOSTIC AID LEDs 6 SPECIFICATION 7 ORDERING INFORMATION 7 CONTENTS ...

Страница 2: ...Each assembly is fully isolated and incorporates high speed fuse excess voltage protection and an over temperature thermal cutout A standard feature of MAXIWAT TC230E units is the clear visual indication by two LEDs of input logic signal and fuse load thyristor integrity The combination of the states of these two LEDs aids system fault finding DESCRIPTION EMC COMPLIANCE Emission The TC230E complie...

Страница 3: ...d delta connected load Figure 2b 3 phase 4 wire star connected load Figure 2c 3 phase open delta connected load The basic wiring is as follow the LINE terminal must be connected to the load supply L1 L2 or L3 One end of the load must be connected to the LOAD terminal LOAD1 LOAD2 or LOAD3 The loads can be connected in star or delta as shown in figure 1 and 2 When connecting the LINE and LOAD to the...

Страница 4: ...2 L3 LOAD LOAD Figure 1c 3 phase 3 wire closed delta connected load FAN LED1 LED1 GREEN INPUT INDICATOR LED1 I P N L FAN SUPPLY 115 OR 240 Vrms TEMPERATURE CONTROLLER LOGIC SIGNAL LED2 RED FUSE LOAD THYRISTOR INDICATOR MUST BE MOUNTED VERTICALLY LED2 LED2 FUSE FUSE TC230E 1 TC230E 2 FAN LOAD L LINE LINE L LOAD FAN LINE L1 LOAD1 LOAD2 LINE L2 AIR FLOW VERTICALLY UPWARD Figure 1a 3 phase 3 wire star...

Страница 5: ...D Figure 2c 3 phase 3 wire open delta connected load LED1 LED1 GREEN INPUT INDICATOR LED1 LED1 FAN I P TEMPERATURE CONTROLLER LOGIC SIGNAL N L FAN SUPPLY 115 OR 240 Vrms LED2 RED FUSE LOAD THYRISTOR INDICATOR MUST BE MOUNTED VERTICALLY LED2 LED2 LED2 FUSE FUSE FUSE TC230E 1 TC230E 2 TC230E 3 FAN LOAD L LINE LINE L LOAD FAN FAN LOAD L LINE LINE L1 LOAD1 LOAD3 LINE L3 LINE L2 LOAD2 VERTICALLY AIR FL...

Страница 6: ...s and effects is given in Table 2 A block diagram showing the diagnostic LEDs 1 and 2 is given in figure 3 Note 1 With the load supply ON the possible faults are a fuse blown or b open circuited load or c short circuited thyristor power to load permanently ON Note 2 Thyristor fails to switch on indicated by LED 2 permanently ON The possible faults are a insufficient input logic drive signal must b...

Страница 7: ...wire star figure 3 1 3 wire closed delta or star 2 figure 1 and 2 3 wire open delta figure 4 3 End of code 00 For applications other than constant resistive loads or any other currents and voltage ratings not listed above please contact our sales office INPUT Logic 5 30 Vdc Must operate at 4 5 Vdc Must release at 1 5 Vdc Constant current 12 mA typical OUTPUT Supply voltage 100 to 440 Vrms 10 15 Cu...

Страница 8: ...B holes C For configurations in figure 1 40 55A 280 165 250 260 80 6 75 155A 380 160 280 260 110 6 For configurations in figure 2 40 55A 280 165 250 260 80 6 75 155A 400 160 280 380 110 6 All dimensions are in mm SUPPLIER INFORMATION Powtier Controls Limited Unit 4 Parkland Business Centre Chartwell Road Lancing West Sussex BN15 8UE England Tel 01903 750800 Fax 01903 750678 Email Email PowtierCont...

Отзывы: