background image

3

5 User Controls

5.1 Direct Control

If configured during the commissioning stage the User has the following direct control of the heater without using the menu.

  

-  If the Fault LED is on because the heater is at lockout, the user can reset the heater by pressing the Reset button.

-  The User can switch the heating ON or OFF  by pressing the Heat button.

-  The User can start or cancel extension time by pressing the Heat button longer than 3 seconds.

-  The User can run the fan without heating, by pressing the Fan button.

5.2 User Settings

5.2.1 General

The second line of the display shows what keypad buttons are active.
After changing settings press 

 to save the new setting. To return to the normal display press 

X

 or do not touch any keys for 15 

or more seconds.
Keys 

 and 

+

 will auto-repeat if held down longer than approximately half a second. The 

+

 key will automatically wrap 

round from the maximum value to the minimum value and the 

 key will wrap the other way.

5.2.2 Description of User Settings

Temperature

This shows the temperature set by the currently active programme, and it is the target temperature for thermostatic control.  

The user can increase or decrease the value to adjust comfort.  This will not alter the set temperature associated with the 

programme, but it will temporarily alter the target temperature for thermostatic control.  

The effect of altering the temperature lasts until the current programme expires or until another programme changes the set 

temperature requirement.

Note: the range of adjustment permitted may be limited during commissioning. Temperature adjustment can be disabled by a 

setting within the user menu.

Clock Set

Sets the current date and the time of day.  The correct date allows the MC300 to know the day of the week, allows for 

automatic BST-GMT changeovers, carries out the holiday shutdown function and permits override password entry.

Programme Settings

The MC300 has 14  programmes, each of which can be assigned to any day of the week.  Each programme can be given an ON 

time, an OFF time and a set temperature.  The user may organize the programmes in any way that suits.  The simplest would be 

one programme ON in the morning, OFF at the end of the afternoon, active Monday to Friday.

If two or more programmes are active at the same time, for instance one is ON all day and another is ON between 11:00 and 

13:00, then the set temperature of the second programme will apply between 11:00 and 13:00, and the set temperature of the 

first programme will apply during the rest of the working day. Programme times increment in 5 minute steps.

Extension time (if set) applies when all programmes have reached the end of their set period for that day.  

Optimum start applies at the beginning of the first programme to switch on and optimum stop applies at the end of the last 

programme to switch off.

Holiday date

A future date can be set so that the heating will not operate on that date, and remains “OFF” for a consecutive number of days 

from that date.  The date includes the year number, ensuring that the holiday shutdown date is not automatically repeated the 

following year.

During the holiday period the heater will only operate if the temperature falls below the frost temperature and if frost 

temperature operation is selected “ON” in the engineer menu. The night temperature setting is ignored during holidays.  

During the holiday period, manual operation of the fan or heater is permitted. Any manual operation still on at midnight will be 

automatically cancelled.

Run Mode

The MC300 has three Run modes: WINTER, SUMMER and OFF. 

Winter

 -  the heating operates when any programme is in a “HEAT ON” period.  The heating also operates to maintain the 

Night Temperature if this has been set. The heating also operates when the temperature drops below the frost 

temperature.

Note: Summer/Winter mode has no connection with the clock change from GMT to BST.

Summer

 - the fan operates to circulate air when switched on manually. With certain types of heater or certain types of 

installation, Fan-only operation may not be appropriate and the fan control circuit should not be used.

In SUMMER the heating never operates unless the temperature drops below the frost temperature. During 

commissioning the frost temperature operation will be set to be ON or OFF.  If the frost setting is OFF, the heater 

will not operate under frost conditions in any User mode.

OFF

 - 

the heater never operates unless the temperature drops below the frost temperature (see above).

User Button Permissions

This menu option facilitates the user to enable or disable the following controls separately if it is required to restrict 

unauthorised access to user controls. Note: User permissions are only effective when User access to the menu is protected by a 

password.

Reset

 - Allows operation of the reset button

Change temperature

 - 

Allows temporary adjustment of the current set temperature

Heat Override

 

Allows switching ON/OFF and extension of Heat ON time

Fan override

 - 

Allows switching ON/OFF of the fan

Set Password

The user may enter a 4-digit password here.  Once set, the password must be given before selected user controls may be 

accessed or changed. “Set password” cannot be entered unless the password has been  given.

As delivered, the MC300 has no User password restrictions, the user password being set to 0000. Entering  a password of 0000 

will remove all restrictions.

Extension time

A user can extend the heating to operate beyond the switch-off time of the last programme of the day, in 30minute increments, 

by pressing the Heat button.  This menu option allows a maximum extension period to be set, in units of 30minutes.  If set to 0 

minutes, extension is not permitted.  Factory default setting: 1hour. Maximum setting 3hours.

Cost Log

This option shows the total hours run and the total cost of running since the log was last cleared.  The display will show the 

date when it was last cleared. For this option to function it is necessary to enter the fuel cost and heater rating (see Engineer 

Menu for the latter). The cost log should be cleared whenever the heater type is changed.

For Hi/Lo heaters, there are two heater power entries and the MC300 will calculate the run cost according to the level of heat 

requested. In the case of modulating control heaters, the cost is an estimate based on half the full heater power.

Password

Once a password has been set, the password must be entered at this menu option to allow access to selected user controls.  

Once entered the password gives access to the User menu functions for 60 minutes. To re-apply the restrictions before the end

of the 60 minute period, select the ‘Enter password’ option and press 

 without entering any digits. The display will show 

‘Password CLOSED’.

Service Date

When the MC300 is installed the Commissioning Engineer may have entered a date for when the heating equipment requires 

servicing. When this date is reached the MC300 fault indicator will be illuminated and the display will alternate between the 

normal display and "Service due, call engineer". The Service Engineer can clear this display by entering a new service date 

when the heating equipment has been serviced.

4.4 Programming keypad (6 Buttons)

Back  Button

 - Press to enter User Menu, go 

back to previous screen.

Back

Decrease  Button

 - Press to decrease values.

Decrease

Increase  Button

 - Press to increase values.

Increase

Next  Button

 - Press to enter User Menu, go 

forward to next screen.

Next

Select Button

 - Press to accept changes.

Select

Quit  Button

 - Press to exit without saving 

changed values.

Quit

X

Note: 

 

may be shown as OK, 

X

 as Cancel

Отзывы: