page no. 33 of 36
NVS Range Users, Installation & Servicing Instructions Doc Ref M102 issue 2.4 May 2018.
Natural Gas to Propane (LPG) Conversion Data
Nominal Inlet Pressure = 37mbar, Minimum Inlet Pressure = 37mbar
High Fire
Low Fire
Injectors
Burner
Pressure
Burner
Pressure
MODEL
Conversion Kit
part number
No.
Size (mm)
Marked
Injector part
number
mbar
mbar
NVS30
NV30LPG
6
1.25
125
142401673
26.5
7.6
NVS60
NV60LPG
8
1.55
155
142401675
20.0
7.4
NVS90
NV90LPG
6
2.10
210
142401676
24.0
8.4
NVS140
NV140LPG
10
2.10
210
142401676
22.6
6.9
Propane (LPG) to Natural Gas Conversion Data
Nominal Inlet Pressure = 20mbar, Minimum Inlet Pressure = 17.5mbar
High Fire
Low Fire
Injectors
Burner
Pressure
Burner
Pressure
MODEL
Conversion Kit
part number
No.
Size (mm)
Marked
Injector part
number
mbar
mbar
NVS30
NV30NG
6
1.94
194
142401664
10.0
3.3
NVS60
NV60NG
8
2.54
254
142401665
8.3
2.6
NVS90
NV90NG
6
3.5
350
142401666
8.2
2.8
NVS140
NV140NG
10
3.5
350
142401666
7..9
2.3