1. Lighting the Module

NOTE:On initial lighting of the module, it may take

some time to purge the internal pipework of air.

If it is not possible to light the module after

several  attempts  contact  the  local  service

company.

1. To Start the Module

1.1 Follow the start up instructions for the duct heater

or air handling unit.

1.2 When all external and internal controls are calling

for  heat  the  burner  start-up  sequence  will

commence. The exhaust fan will run and after a

pre-purge period of approximately 30 seconds

an ignition spark will be generated at the burner.

The main gas valves will open and the burners

will be established

NOTE: 

If the burners fail to establish they will go

to lockout and the lockout  indicator / reset button

on the pcb will be illuminated. To restart the

burner  push  the  lockout  reset  button.

If the burners will not light after four or five

attempts then shut down the unit and call in a

service engineer.

NOTE: 

If there is loss of flame signal at the burners

during normal running the control box will

immediately initiate spark ignition. If the burners

fail  to  relight  they  will  go  to  lockout.

2. To Shut Down the Module

2.1 For Short Periods:

Follow the instructions provided with the duct

heater or air handling unit so that external and/or

internal  controls  are  not  calling  for  heat.

2.2 For Long Periods:

Complete 2.1 above, wait approximately 4-5

minutes for the exhaust fan of the module to stop

running and then turn OFF the gas and electric

supplies to the module.

3. Description of Operation

Important:

 All heaters must be controlled by the

fitted external controls and not by use of the main

switch  in  the  electrical  supply  to  the  heater.

The burner start up sequence will commence

each time that the external controls call for heat. The

exhaust fan will run and after a pre purge period off

approximately 30 seconds  an ignition spark will be

generated at the burners. The main gas valves will

be opened and the burners established. When the

external controls are satisfied the burners will be

turned off and approximately 4 - 5 minutes later the

exhaust  fan  will  be  automatically  stopped.

4. Limit Thermostat

The limit thermostat is mounted towards the top of

the conrtrol panel.

i) Limit Thermostat Reset

In the event of a fault that causes the temperature of

the air within the module to rise significantly e.g.

Blocked air inlets, the limit thermostat will operate

to shut down the burners. Remove the cause of the

fault, wait 10 minutes and then reset the thermostat

by  pushing  the  white  reset  button.  If  the  limit

thermostat continues to operate call a service engineer.

5. Maintenance

Regular servicing is essential to maintain efficient,

reliable and safe operation of the module. Users are

strongly recommended to have the module serviced

at least annually and preferably at the end of the

heating season.

6. IMPORTANT

Free access must be maintained to and around the

module for servicing purposes and the air supply to

the  heater  must  not  be  restricted  in  any  way.

Combustible materials must not be stored adjacent

to  the  module  or  the  unit  it  is  fitted  into.

If at any time a gas leak is suspected turn OFF the

gas supply - DO NOT USE A NAKED FLAME -

and contact the local gas undertaking immediately.

Gas Safety (Installation & Use)  Regulations

(Current Issue)

It is law that all gas appliances are installed, adjusted

(converted if necessary) and serviced by qualified

persons* in accordance with the current issue of the

above regulations.  Failure to install appliances

correctly can lead to prosecution.  It is in your own

interests and that of safety to ensure that the law is

complied with.

* e.g. Corgi Registered