ENGLISH
A – Press front panel from the bottom and pull
to remove it
B - Disconnect the battery block by
separating the two connectors (never pull
on the wires).
C - Remove the metal protection cover in front
of the battery (one screw).
D - Pull the plastic tab to remove
the battery block and replace it.
VI.
Technical Specification
Model
VI THID Series
INPUT
Voltage
220/230/240 VAC
Voltage Range
184~276 VAC
OUTPUT
Voltage
220/230/240 VAC
Voltage Regulation
-10%/+6% of nominal voltage range(Line mode)
Frequency Range
50/60Hz
Frequency Regulation
±1Hz (Battery mode)
Transfer Time
Typical 3-7ms
,
10ms max
Waveform
Pure Sine Wave
PROTECTION
Full protection
Discharge, overcharge and overload protection
ENVIRONMENT
Humidity
0-90 % RH @ 0° to 40° C (non-condensing)
Monitoring Software
WinPower
Model
VI 500 THID
VI 750 THID
VI 1000 THID
VI 1500 THID
POWER
500VA / 350W
750VA / 500W
1000VA / 700W
1500VA / 900W
Type & Number
12V/7Ah x1
12V/ 9Ah x1
12V/7Ah x2
12V/9Ah x2
Charging Time
3 hours recover to 90% Power
Backup Time
(Half SPS load)
10min
9min
11min
8min