19
EN
17: Constant charger voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust constant
charger voltage.
Parameter 3:
the voltage range is from
0V to 3.2V
, the default
value is 0V.
18: Charger maximum current setting
Interface
Setting
Parameter 3:
The maximum charging current could be adjusted.
Default value is 4A for long run model and 1A for standard
model.
The setting range is 0.5A~6A for long run model, and 0.5A~2A
for standard model
Note:
Any modification should be suitable to battery specifications.
If input voltage is below 200VAC, the UPS will reduce charging
current to 4A automatically even though the setting is 6A.
19: Battery capacity and groups setting
Interface
Setting
Parameter 2:
Set the battery capacity such as 7AH, 9AH, 10AH, 12AH, 17AH,
26AH, 40AH, 65AH, 100AH and so on.
The default value is 9AH.
Parameter 3:
Set battery group range from 1 to 6.
The default value is 1 group.
These parameters are for the battery backup time calculation
20: Backup time calibration
Interface
Setting
Parameter 3:
Calibrate the displayed backup time by adjusting this multiplier
factor. The formulation is listed below:
Displayed backup time=Original calculated backup time x
Multiplier factor
The default value of multiplier factor is 1.0, and the range is
from 0.5 to 2.