13
When selecting the NFB, the user can refer to below table for
detailed information when installation.
Model No.
UPS INPUT NFB
VOLTAGE
CURRENT
PowerWalker VFI 1000T LCD (L)
300Vac
10A
PowerWalker VFI 2000T LCD (L)
300Vac
20A
PowerWalker VFI 3000T LCD (L)
300Vac
32A
(2) UPS Output Connection
The output of the UPS is IEC socket-types. Simply plug the load
power cord to the output sockets to complete connection. Use one
cord for every 5A load.
Model No.
Output Socket (pcs)
PowerWalker VFI 1000T LCD (L)
3 IEC type
PowerWalker VFI 2000T LCD (L)
6 IEC type
PowerWalker VFI 3000T LCD (L)
4 IEC type+Terminal block
The wiring configuration is shown
as the following procedure:
a) Remove the small cover of the
terminal block
b) Use 2.5mm
2
wires for wiring
configuration
c) Upon completion of the wiring
configuration,
please
check
whether the wires are securely affixed
d) Put the small cover back to the rear panel
Caution!
Do not connect equipment which would overload the UPS
system (e.g. laser printers)
Connection diagram