Mini AS400 Specification
Mini AS400 card provides dry contact signal only, below is the parameter
range.
Parameter
SYMBOL
MAX.
UNIT
Diode
Reverse Voltage
VR
6
V
Forward Current
IF
80
mA
Peak Forward Current
IF (peak)
1
A
Relay
DC Voltage
VDC
24
V
DC Current
IDC
1
A
Pin definition.
Pin
Signal definition
Reason
I/O
Jumper location
9
UPS Fault
UPS Internal Fault
Out
NO:JP1 2-1
NC:JP1 2-3
11
Summary Alarm
1.
Utility Failure
Out
NO:JP3 2-1
2.
UPS Fault
3.
Bypass Mode
4.
Communication Error
NC:JP3 2-3
1,3,6,10 External power ground
In
12
Remote Shutdown /
UPS Test
Shutdown in battery mode /
UPS Test (
3-10S signal length
)
In
UPS Test:
JP8 2-1
14
UPS ON(SON)/
UPS OFF(SOFF)
Remote control UPS :
Switch on / Switch off
In
8
Common
In
13
Pin 14,12 ground
2
Bypass Active
Bypass Active
Out
NO:JP5 2-1
NC:JP5 2-3