Mini AS400 Specification   

Mini  AS400  card  provides  dry  contact  signal  only,  below  is  the  parameter

range.

Parameter 

SYMBOL 

MAX. 

UNIT 

Diode 

Reverse Voltage 

VR 

Forward Current 

IF 

80 

mA 

Peak Forward Current 

IF (peak) 

Relay 

DC Voltage 

VDC 

24 

DC Current 

IDC 

Pin definition.

Pin 

Signal definition 

Reason 

I/O 

Jumper location 

UPS Fault 

UPS Internal Fault 

Out 

NO:JP1 2-1 

NC:JP1 2-3 

11 

Summary Alarm 

1.

Utility Failure

Out 

NO:JP3 2-1 

2.

UPS Fault

3.

Bypass Mode

4.

Communication Error

NC:JP3 2-3 

1,3,6,10  External power ground 

In 

12 

Remote Shutdown / 

UPS Test 

Shutdown  in  battery  mode  / 

UPS Test (

3-10S signal length

In 

  UPS Test: 

JP8 2-1 

14 

UPS ON(SON)/   

UPS OFF(SOFF) 

Remote control UPS : 

Switch on / Switch off

 

In 

Common 

In 

13 

Pin 14,12 ground 

Bypass Active 

Bypass Active 

Out 

NO:JP5 2-1 

NC:JP5 2-3 