TROUBLE SHOOTING 

TROUBLE SHOOTING 

TROUBLE SHOOTING 

 

Problem

 

Possible Cause 

Solution

 

Warning 

O/P Overload

 

Your equipment requires more power than the 

UPS can provide. If the UPS is in Line Mode, then 

it will transfer to Bypass Mode; if the UPS is in 

Battery Mode, it will shut down. 

Shut off non-essential equipment. If this solves 

the overload problem, the UPS will transfer to 

normal operation. 

Battery Mode 

UPS is operating on battery power. 

Save your data and perform a controlled- 

shutdown. 

Battery Low 

UPS is operating on battery power and will be 

shutting down soon due to extremely low battery 

voltage. 

UPS will restart automatically when acceptable 

utility power returns. 

BAT Disconnected/ 

Battery Replace   

Missing battery power. 

Check battery connector  when use battery 

packages.   

UPS has failed in Battery Test. 

Contact technical support to replace the battery. 

Charger Failure 

Charger has failed. 

1. Shut down UPS and turn off AC input. 

2. Contact the dealer for repair. 

EPO OFF 

Missing the EPO connection. 

Check the EPO connection. 

Fault

 

Over Temperature 

High ambient temperature. 

1. Shut down UPS. Restart UPS to Check the fan 

for operation and if the ventilation hole has been 

covered 

2. Contact the dealer for repair. 

Output Short 

Output short circuit. 

1. Shut down UPS   

2. Your attached equipment may have problems, 

please remove them and check again. 

High O/P V 

Output voltage is too high. 

1. Shut down UPS   

2. Contact the dealer for repair. 

Low O/P V

 

Output voltage is too low. 

Bus Fault 

Internal DC bus voltage is too high or too low. 

Other

 

Startup fail 

High temperature, or fan fail, or battery low, or 

EPO off. 

1. Restart UPS and 

press the “▼” button to

 view 

the warning event. Then refer to the solution for 

the warning. 

2. Contact the dealer for repair. 

 

 

 

 

 

 

 

Содержание 10121191

Страница 1: ...Manual PowerWalker VI RLP Series 1000 3000 ...

Страница 2: ...round insulation CAUTION To avoid electric shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cause damage to your equipment and cause fire hazards CAUTION Wiring must be done by qualified personnel CAUTION DO NOT USE FOR MEDICAL OR LI...

Страница 3: ...hich allows communication and control between the UPS and the connected computer It is recommended to install the Power master software on the PC Server connected with the USB cord 8 SNMP HTTP Network slot Slot to install the optional SNMP card 2 for remote network control and monitoring 9 Extended Runtime Battery Module Connector Connect to additional external battery modules 10 EPO Emergency Pow...

Страница 4: ...mputer and UPS through PowerMaster Management software The LCD display will show how much time is left before the UPS will turn back on or shut down FAULT This icon appears if there is a problem with the UPS Setting mode Bat mode When this icon is blinking the batteries need to be replaced Line mode Solid light Load capacity Battery capacity Bat mode battery capacity Line mode 1 Battery charging c...

Страница 5: ...ical Screen Mode BUTTON OPERATION Operation Description POWER Press this button to turn on UPS In line mode Battery mode press the button to turn off UPS SETUP Press this button simultaneously for 5 seconds to get into setting mode while in standby mode Press this button for long time to exit setting mode and saving changes UP DOWN In setting mode press this button to display next selection or pre...

Страница 6: ...e UPS on Standby mode connect utility power to UPS and do not turn on UPS 2 Press the UP DOWN button to scroll different page or the different parameters 3 Press the ENTER buttons to select the parameter you want Setting item Configure Submenu Available Settings Default Setting LCD Display 001 008 Output1 8 settings dEL on delay on dEL oFF delay off dEL rbt delay reboot iMM on immediately on iMM o...

Страница 7: ...Shutdown the ups and check the battery connect or replace them then restart the ups E12 Bat Volt Low A59 Bat Disconnect A62 Bat Bad A56 Bat Volt Low A64 Overload Warning Shut off the non essential equipment then UPS may be normal E14 Overload E18 Fan Fail Shutdown the ups and check the fan or replace then the UPS can work normally A69 Fan Lock E19 Over Temperature Environment or UPS temperature ma...

Страница 8: ...ge Time Typically 4 Hours inside batteries Sealed Maintenance Free Yes Status Indicators LCD Screen Graphic LCD Audible Alarms Battery Mode Battery Low Overload UPS Fault Replace Battery Bypass Mode Charger Failure Over Charged Fan failure EPO active over temperature etc Environment Operating Temperature 32 to 104 0 to 40 Operating Relative Humidity 10to 90 non Condensing Management On Device Feat...

Страница 9: ...hen use battery packages UPS has failed in Battery Test Contact technical support to replace the battery Charger Failure Charger has failed 1 Shut down UPS and turn off AC input 2 Contact the dealer for repair EPO OFF Missing the EPO connection Check the EPO connection Fault Over Temperature High ambient temperature 1 Shut down UPS Restart UPS to Check the fan for operation and if the ventilation ...

Страница 10: ...IVIDUAL OUTLET CONTROL Method 1 Through LCD setting Setting item 001 008 Method 2 Through PowerMaster Local UPS SETTING CONFIGURATION Method 3 Trough SNMP Card 2 Webpage UPS Outlet Action Outlet Management ...

Страница 11: ...ting action will be triggered on the outlet To utilize the function AutoPing configuration is based on different applications Auto Ping setting UPS Outlet Action Outlet AutoPing SOFTWARE DOWNLOAD Power Master management software provides a user friendly interface for your power systems The graphic user interface is intuitive and displays essential power information at a glance Please follow proced...

Отзывы: