TERM I NAL DESCRI PTI O NS - M O DEL 1000AR
T B 1
C u r r e n t C o n t r o l l e r B o a r d ( 1 4 1 - 1 0 8 )
1
Dedicated Shields and Ground connection
2
HS1 position encoder
3
HS3 position encoder
4
HS2 position encoder
5
HS4 speed encoder
6
HS5 speed encoder
7
Encoder Common
for encoder ONLY
8
E5 VDC
for encoder ONLY
9
Isolated Common
for terminals 10 and 11
10
Auto/Manual Selection
+24 VDC for Digital Mode
11
External Frequency Input
+24 VDC Square Wave
12
Collector of FAULT transistor
13
Emitter of FAULT transistor
14
Drive Load output
-2VDC = 150%
15
Auxiliary Supply output
+15VDC for extra encoder
16
Power Supplies Common
T B 2
S p e e d C o n t r o l l e r B o a r d ( 1 4 7 - 1 0 1 )
1
ON at zero speed (open collector)
30VDC 50 mA maximums
2
ON when enabled (open collector)
30VDC 50 mA maximums
3
Speed Output (open collector)
30VDC 50 mA maximums
4
-10VDC Reference Source
5 mA maximum
5
Speed Reference Input
-10VDC to +10VDC
6
+10VDC Reference Source
5 mA maximum
7
RUN output contact
N/O 125VAC
8
RUN output contact
N/O 1A Resistive
9
-24VDC supply
50 mA maximum
10
+24VDC supply
50 mA maximum
11
EMERGENCY STOP Input
+24VDC to activate
12
RAMP STOP Input
+24VDC to activate
13
RUN/START Input
+24VDC to activate
14
JOG Input
-24VDC to activate
15
HOLD Input
-24VDC to activate
16
Signal Common
T B 3
C a p a c i t o r B o a r d ( 1 4 1 - 1 0 6 )
1
Horsepower calibration resistor
2
No
connection
3
Horsepower calibration resistor
T B 5
B u s L o a d e r ( I n t e g r a l u n i t c o n n e c t e d t o D r i v e r b o a r d )
1
Bus loader Interlock
N/O 125VAC
2
No
connection
3
Bus loader Interlock
N/O 1A Resistive
HO W DO I …
GET RUN, ZERO SPEED, FAULT AND ENABLE INFORMATION?