WIRING DIAGRAM

3 HP 220/240 V 

Motor

Thermal Relay 
Overload Amp 
Adjustment  Dial:
 
Turn this dial to the 
motor manufacturer's 
thermal overload amp 
setting specification. 
Typically this setting 
is 100-110% of what 
is listed on the motor 
data plate as the 
MAX amp load.
IMPORTANT: 
Turning this dial 
has no effect on 
increasing motor 
horsepower. Turning 
this dial to a too high 
amp setting could 
cause the motor to 
overheat and become 
damaged before the 
relay trips.

Reset Button/OFF 
Button 
Reset Operation: 
If 
the thermal/phase loss 
relay has tripped, push 
this button to reset the 
relay.
OFF Operation: If 
the motor is operating 
normally, this button 
will also cut the current 
going to the magnetic 
field coil, which opens 
the contactor and kills 
power to the motor.

Manual 
Contactor 
Override Lug: 
When pushed, 
the contactor is 
manually closed 
for troubleshooting 
purposes only.

ON Button: When pushed, power is  sent to the 
magnetic field coil and the contactor closes and 
sends power to the motor.

Manual Trip Test Lever: If the thermal/
phase loss relay function is in question, use a 
wooden stick or dowel to slide the brown lever 
to the right. If the motor shuts off, the thermal 
relay has tripped and is functional. If the motor 
keeps running, the themal relay needs to 
be replaced.

220/240 3-Phase 

Power Source