background image

 

INFORMATION All -UPS 1400, 2200, 3000, and XL models have cooling 

fans. Fan cooling runs during four normal, though in most cases infrequent, 

modes of operation. These modes are listed as follows: 

 

1 ) The fan is on whenever the UPS is operating on-battery. 

 

2 ) The fan is on when the UPS' internal ambient temperature exceeds 60

!

(140

!

F). When cooled to below 50

!

C (122

!

F), the fan is shut off. 

 

3 ) The fan is on when the output load rises to above 75% of full rated 

load. When the load is reduced to below 70% of full rated load, the fan is 

shut off. 

 

4 ) The fan is on when the battery charger is delivering power subsequent 

to a utility outage. 

Note: -UPS must be allowed 1" (2.5 cm) of clearance on all sides for 

proper ventilation. 

 

For information on heat dissipation (BTUs), please reference the Knowledge 

Base document entitled "Thermal Dissipation Ratings for -UPS 3G 

Models" => [Image]. 

 

PS-1501VI  

     

 

6. General Receptacle Wiring Practices

 

 

INFORMATION: This document explains which voltages can be derived at the electrical outlet receptacle from the existing wiring found in common electrical 

boxes for both residential and commercial applications. This information is applicable to the United States only, although Canadian applications will be similar. 

The examples provided below are for information only. 

Residential Applications: 

Generally a 120 / 240 volt, three-wire system is used in residential  

applications.  

- 120 Volt Applications 

For 120 volt applications, there should be three wires in the box. The expected color of the wires should be green (the green wire is ground, but it could also be a 

bare wire rather than green), white (neutral), and black (phase also known as hot). Voltage between the phase and neutral conductors will be 115 volts nominal. 

When connecting a receptacle (usually a NEMA X5-XX), the ground wire bonds to the green terminal, neutral bonds to the silver terminal, and hot bonds to the 

copper-colored terminal. A qualified person can change a 120 volt dedicated box to a 240 volt box by connecting the neutral wire to a suitable dual-pole circuit 

breaker on the opposite phase leg. This conductor shall bewrapped with black tape. A suitable 240 volt receptacle will be installed in the box.  

 

- 240 Volt Applications 

If the box is being used for a 240 volt application, there should be three wires  

in the box. The expected colors of the wires should be green (the green wire is  

ground, but it could also be a bare wire rather than green) and two black wires  

(phase conductors). Voltage between the two phase conductors should be 240  

Volts. When connecting a receptacle (usually a NEMA X6-XX), the green (or bare)  

wire bonds to the ground lug and the phase conductors bond to the X and Y lugs  

(either phase conductor can go to either lug). A qualified person can change a  

240 volt box to a 120 volt box by taking one of the phase conductors and  

connecting it to the neutral bus in the circuit breaker panel. This conductor  

shall be wrapped with white tape. A suitable 120 volt receptacle will be  

installed in the box.  

Commercial Applications: 

Generally a 120 / 208 volt, five wire system derived from a transformer with a  

wye secondary is used in commercial applications. There are three hot phase  

conductors (colored red, blue, and yellow), a neutral conductor (colored white),  

and a ground wire (colored green). Some or all of these wires may show up in the  

box.  

- 120 Volt Applications 

For 120 volt applications, any one of the hot phase conductors will be connected  

to the copper-colored terminal on a suitable NEMA X5-XX receptacle. The neutral  

conductor will be connected to the silver terminal. The ground wire shall  

connect to the green terminal.  

Содержание GLUPS PS-1501VI

Страница 1: ...USERS MANUAL Rev3 Powerstar Inc 301 948 0713 9073 Shady Grove Ct Gaithersburg Maryland copyright 2013 www powerstarinc com The Glups copyright to holders such as Powerstar APC Powerschute THE GLUPS Gl...

Страница 2: ...itchover time from main power is 250 1500va 0 to 4ms All metal shell for rugged operation shielded connectors Front panel selftest of UPS batteries main board lights load battery level Audible adjusta...

Страница 3: ...PowerStar Inc Mission Critical Power 9073 Shady Grove Gaithersburg Maryland 20877 800 209 5556 301 948 0713 http www powerstarinc com power html...

Страница 4: ...er than the actual power This difference between the apparent power and the actual power gives rise to the power factor The power factor is equal to the ratio of the actual power to the apparent power...

Страница 5: ...ed that the crest factor is an inherent characteristic of a computer load when in fact crest factor results from an interaction between the load and the AC source The crest factor required by a comput...

Страница 6: ...le value of 100 C The temperature rise inside the unit is dependent upon several factors including both the outside ambient temperature regardless of whether the unit is on line or on battery and the...

Страница 7: ...b The power quality may be poor due to local cyclic heavy load switching manufacturing environment laser printers or photo copiers on same circuit branch or unit is running off a generator b Set optio...

Страница 8: ...volts nominal When connecting a receptacle usually a NEMA X5 XX the ground wire bonds to the green terminal neutral bonds to the silver terminal and hot bonds to the copper colored terminal A qualifie...

Страница 9: ...h is needed in order for the UPS to remember if it is supposed to restart automatically when the AC power is restored However if the UPS is switched off with the front touch switch then the self disch...

Страница 10: ...faces with baking soda and water to neutralize and remaining acidity UPS consumed in local fire A fire at the UPS installation or storage site burns the UPS Hazard 1 Materials within the UPS are burne...

Страница 11: ...0 hz input using the supplied Euro cord The input is then connected internally to the stepdown transformer which correctly plugged in converts the power down to 120v 50 hz power This power is sent out...

Страница 12: ...SUPPLY 220 240V 10 RATED PRIMARY CURRENT 7 2 6 6A RATED FREQUENCY 50 60 Hz TEMP RISE AT RATED LOAD 65 C DIMENSIONS WEIGHT MOUNTING CORE DATA OD MAX 6 25 POTTED CENTER CORE 900693 H MAX 5 0 CONCAVE BO...

Страница 13: ...reactive or harmonic current that the UPS will actually be required to supply during service Many UPS manufacturers do not include both Watt and VA specifications for their UPS products When the VA ra...

Страница 14: ...e being supplied to the load which is equivalent to a brownout condition The UPS or line conditioner must be designed to maintain the proper peak voltage sine wave UPS systems have a very high crest f...

Страница 15: ...t cases customers utilize this function in combination with APC s Powerchute PLUS software for their server s operating system However it is NOT necessary to make a serial connection to place one of t...

Страница 16: ...e UPS exceed the UPS s power capacity The SmartBoost and SmartTrim indicators light when the UPS is correcting either a low or high utility voltage 2 2 Diagnostic features On startup the UPS by defaul...

Страница 17: ...nal to the remaining available run time When these LEDs flash the battery capacity is low and can supply less than two minutes default of run time for the load 6 1 8 Utility Voltage Indicators The PS6...

Страница 18: ...absolutley corrected the cause of overvoltage then plug in power source with great care do not turn on yet 10 If corrected you can now turn on master circuit braker in back 11 Then turn on UPS from th...

Страница 19: ...owerstar Inc All rights reserved This document is confidential and is covered by the copywrite law s of the USA Powerstar Inc Gaithersburg Maryland 301 948 0713 http www powerstarinc com Price of this...

Отзывы: