www.powersolve.co.uk
Powersolve Electronics Ltd, Units 8, 9 and 12 The Paddock, Hambridge Road, Newbury, Berks RG14 5TQ
Tel: 01635 521858 Fax: 01635 523771 Email: [email protected]
Input:
85-264 VAC, 47-66Hz
Input Current:
4.4A max 300W models
8.4A max 600W models
22A max 1500W models
Inrush Current:
40A 300W, 60A 600W & 40A 1500W
Earth Leakage Current:
0.38mA 300W, 0.75mA 600W, 1.6mA 1500W
Power Factor:
0.99 typical
Efficiency:
See table
DC Output:
See table
Output Voltage Adjust:
See table
Overvoltage Protection:
Voltage shutdown type, tracking V out
Over Current Protection:
Rectangular type, recovers on reset
Line Regulation:
0.2% max
Load Regulation:
0.6% max
Ripple & Noise (pk-pk):
3.3V& 5V 120mV max, 12V-15V 150mV max
24V-28V 200mV max & 48V 300mV max
Start Up Time:
500mS max
Hold Up Time:
20mS minimum
Indicator:
LED Indicator indicates V out present
Remote On/Off:
Standard
Remote Sense:
Standard
Fan Alarm:
Voltage shut-down type
Overtemperature Protection:
Voltage shut-down type
Current Sharing:
Standard
Output Voltage Programming:
Continuously variable 0-120% by voltage input (48V 0-110%)
Master Slave Operation:
Standard
Safety Approvals:
UL,cUL60950, TUV(EN60950)
EMC:
FCC Class’B’, VCCI Class’B’,
EN55011’B’, EN55022’B’
Immunity:
EN50082-2, EN61000-4-2,3,4,5,6,8,11
Operating Temperature:
-20 to +71 °C, see derating curve
Humidity:
10-95% non condensing
Withstand Voltage:
Input to Case 2.0kV AC
Input to Output 3.0kV AC
Output to Case 500V AC
Mechanical:
Fully enclosed with integral cooling fan
Warranty:
Standard 5 years, 10 years with long life fan ‘F’ prefix.
Electrical Specification
AC-DC Converters
RKW 300 to 1500W Series
300/600/1500 Watts Single Output
Power Factor Correction
Voltage Programmable
Features
•
85-264 VAC Universal Input
•
DC output continuously variable 0-120% V out
•
High Quality Industrial Grade Product
•
Optional conformal coating
•
5 years warranty (optional 10 year with long life fan)
•
Full safety approvals
•
EMC meets FCC ‘B’ & EN55011 & EN55022 ‘B’
•
Immunity meets EN50082-2, EN61000-4-2,3,4,5,6,8,11
•
Conforms to EN61000-3-2 for Harmonic Distortion