Ordering Information 

Typical Specification  

CALIFORNIA PROPOSITION 65 WARNING

WARNING:

This product contains chemicals known to the 

State of California to cause cancer and birth defects or other
reproductive harm. (California law requires this warning to be
given to customers in the State of California.)
For more information: www.wattsind.com/prop65

Engineering Approval

Project _____________________________

Contractor___________________________

Architect/Engineer ____________________

Model No.

Valve#

Inlet

Outlet

Order Code

(inches)

(inches)

1432/1434

1-1/2

2.0

1432DV

434/1432

1-1/2

2.0

1432HL

1434/1434

2.0

2-1/2

1434DV

434/1434

2.0

2-1/2

1434HL

Piping/Finish

Rough Bronze

A

Polished Chrome (Rough Chrome Piping/

B

Polished Chrome Valve)

Cabinets

Exposed, No Cabinet

M

Stainless Steel, Recessed

N

Stainless Steel, Wall Mount

Q

Painted Steel, Recessed

R

Painted Steel, Wall Mount

U

Alarm (not factory installed)*

None

0

AquaSentry2** for 1432DV or 1432HL

6

AquaSentry2** for 1434DV or 1434HL

7

* Mounting requirements varied based on individual installation.
** Includes control module, sensor, electrical box, transformer, solenoid, shock absorber, and 25 feet of station cable.

High capacity water temperature control system will be pre-assembled and pre-tested and mount-
ed on heavy-duty metal struts for stability. The system includes two thermostatic valves capable 
of maintaining water temperature within the performance requirements of ASSE 1017 and CSA
B125. Valves will be ASSE listed and CSA certified. Valves will feature paraffin-based actuation
technology with temperature adjustment from 40° F (4° C) - 160° F (71° C) with a 15° F (8° C)
approach temperataure. Temperature adjustment will be vandal resistant and feature a locking
mechanism.

Valves will be of bronze body construction and feature triple-duty check stops with screens to 
filter out debris. The system will include a PRV (“HL” series only), ball valves, pressure gauges and
thermometers. The system will be a Powers’ Series HydroGuard 1430HL or HydroGuard 1430DV.
Any alternate must have a written approval prior to bidding.

© 2004 Powers, a division of Watts Water Technologies, Inc.
USA Phone: 800-669-5430 • Fax: 847-824-0627   •   Canada Phone: 1.888.208.8927 • Fax: 1.888.882.1979

www.powerscontrols.com

Printed in U.S.A.

Form  PS/TI 2-Valve HCS 1430 v4  0530

EDP# 6512268

Содержание HydroGuard 1430 Series

Страница 1: ...Water Tempering Solutions to 225 GPM 1430 Series Two Valve Hi Lo ...

Страница 2: ... Tested To ASSE 1017 Standard 1 Form PS TI 2 Valve HCS Series 1430 v4 0530 Min Flow Model to ASSE Pressure Drop Across Valve 1017 5 psi 10 psi 20 psi 30 psi 45 psi 60 psi 34 kpa 69 kpa 138 kpa 207 kpa 310 kpa 414 kpa 1432DV 6 5 gpm 46 0 gpm 63 0 gpm 93 0 gpm 113 0 gpm 140 0 gpm 163 0 gpm 25 lpm 174 lpm 238 lpm 352 lpm 428 lpm 530 lpm 617 lpm 1432HL 1 5 gpm 54 0 gpm 73 0 gpm 109 0 gpm 134 0 gpm 165...

Страница 3: ...rm PS TI 2 Valve HCS Series 1430 v4 0530 Dual Valve System DV VALVE INLETS OUTLET PRV 1432DV 1 1 2 38 mm 2 51 mm 1432HL 1 1 2 38 mm 2 51 mm 2 51 mm 1434DV 2 51 mm 2 1 2 64 mm 1434HL 2 51 mm 2 1 2 64 mm 2 51 mm Hi Lo System HL ...

Страница 4: ... Diagram 1 Low temperature hot water recirculation diagram Diagram 2 Low temperature hot water recirculation diagram with separate high temperature hot water recirculation 3 Form PS TI 2 Valve HCS Series 1430 v4 0530 ...

Страница 5: ...pen sooner Turning the adjust ment nut counter clockwise will decrease outlet pressure increase the differential across the PRV allowing the PRV to open later 6 Close the ball valve at the discharge of the high flow valve 7 Open the ball valve on the outlet of the low flow valve 8 Open enough fixtures to meet the minimum flow requirement as per table 1 9 Set the temperature for the low flow valve ...

Страница 6: ...an check stops 3 The system pressure varies by more than 50 of the inlet supply pressure Outlet temperature cycles between hot and cold 1 The differential across the PRV is set too low so the high flow valve begins controlling the system too early and therefore cycles hunt for the set point Refer the set up procedure and increase the differential across PRV Refer the set up procedure and decrease ...

Страница 7: ...air Kits contain parts for one 1 pair Repair Kits containing O Rings include Silicone gel for use on O Rings during installation PART DESCRIPTION REPAIR KIT INCLUDES 1432 1434 Hi Lo Motor Replacement Kit 13 and 2 390 500 390 543 Strainer Replacement 7 8 9 and 10 230 134 230 136 Check stop Replacement 7 8 10 11 and 12 230 135 230 137 Gasket and Disc Replacement 1 4 6 7 8 10 and 12 390 298 390 306 M...

Страница 8: ... Includes control module sensor electrical box transformer solenoid shock absorber and 25 feet of station cable High capacity water temperature control system will be pre assembled and pre tested and mount ed on heavy duty metal struts for stability The system includes two thermostatic valves capable of maintaining water temperature within the performance requirements of ASSE 1017 and CSA B125 Val...

Отзывы: