background image

PM

4025

Gaseous Fueled Stationary Standby

25

kW

60

Hz

Page 4 of 4

Alternator Data

Type

Brushless Revolving Field, Drip Proof Construction
W/Tropicallized Windings

# Poles

4

Coupling Method

Direct, Flex Disc

Insulation Class

H, UL 1446 Recognized

Voltage Regulation

Externally Regulated, Solid State AVR 

±

 1.5%

Total Harmonic Distortion

<3.5%

Waveform Deviation Factor

<5%

Circuit Breaker Data

Type

Molded Case

Withstand Rating

10kA AC @ 240v, 18kA @ 480v

Agency Listing

UL 489 Listed

Control Panel Functions

 

Automatic Remote Start (2-wire)

 

Generator Voltage Metering

 

Generator Frequency Metering

 

Generator Current Metering

 

Engine Coolant Temperature Metering

 

Engine Coolant Temperature Protection

 

Engine Oil Pressure Monitoring

 

Engine Oil Pressure Protection

 

Overspeed Protection

 

Overcrank Protection

 

Emergency Stop Input

 

Engine Cooldown

 

Watt Metering

 

VA Metering

 

Engine RPM Metering

 

Power Factor Metering

 

Watt-hour Metering

 

Engine Run Time Metering

 

Battery Voltage Metering

 

Battery Condition Monitoring

 

Maintenance Interval Timer

 

On-Off-Auto Selector Switch

 

Low Coolant Level Detection*

 

Battery Charger Failure Monitoring*

Options

LP Liquid Withdrawal System
Remote Annunciation Panel – RDP110
Digital (CP1000) Panel Upgrade

Allows For:
Additional I/O Contacts
Modem Capability

Dimensions & Weight

Weight
1400 lbs.

All Specifications Subject to Change Without Notice
101-2931-0602

©2002 Coleman Powermate, Inc.

Coleman® is a registered trademark of the Coleman Company, Inc. used under license.

* Generator Set Must Be Equipped With Appropriate Hardware

Содержание PM4025

Страница 1: ...t Motor Starting Tropicallized Windings Weather Enclosure 16 Gauge Steel Enclosure With Sound Material Installed Powder Painted Almond Color Finish Lockable keyed alike Doors With Sound Baffles Vertical Air Discharge For Optimal Sound Control Critical Grade Muffler Integral To Enclosure No Exterior Fasteners Fuel System Operates On Liquefied Petroleum Gas Or Natural Gas Simple Field Conversion Bet...

Страница 2: ...ystem Capacity 2 8 Gallons Coolant Flow Rate 17 4 GPM Coolant Heater 120v 500 Watt Thermostatically Controlled Circulation Type Electrical Starting Voltage 12v negative ground Battery Size Required BCI Group 26 Battery Rack 2 0 Cables Included Cranking Current 550cca 0 F Battery Charging Alternator 90 amps Battery Charger 120v AC Bulk 6A 12vdc Absorption 5 5A Taper To 1 5A Between 13 14 4vdc Float...

Страница 3: ...0 CFM Total Airflow 4550 CFM Heat Rejected To Coolant 70000 BTU HR Heat Rejected To Exhaust 195000 BTU HR Maximum Exhaust Flow 206 CFM Maximum Exhaust Backpressure 1 1 PSI Exhaust Temperature 1200 F Sound Data 66 66 66 66 dB A Average 23 7m Full Load dB A Average 23 7m Full Load dB A Average 23 7m Full Load dB A Average 23 7m Full Load 2002 Coleman Powermate Inc Coleman is a registered trademark o...

Страница 4: ...erature Protection Engine Oil Pressure Monitoring Engine Oil Pressure Protection Overspeed Protection Overcrank Protection Emergency Stop Input Engine Cooldown Watt Metering VA Metering Engine RPM Metering Power Factor Metering Watt hour Metering Engine Run Time Metering Battery Voltage Metering Battery Condition Monitoring Maintenance Interval Timer On Off Auto Selector Switch Low Coolant Level D...

Отзывы: