OFI1200A Series 
1200W Single output 
AC/DC Baseplate power supply 

 

www.prbx.com 

 

 

 

 

 

 

2022.07.21 

 

 

 

 

 

 

 

Specifications are subject to change without notice. 

 

1.2 Isolation from conductive enclosure 

There are dangerous voltages inside of the unit. Special attention 
needs to be considered when installing the open type of unit. 
 
Ensure proper isolation distances between the components and 
conductive enclosure. 
 
 

d1, d2 = 4mm min 

 
If sufficient isolation distances cannot be secured, an isolation sheet 
shall be added between a components and external surfaces.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 1.3 Isolation distance 

 
To optimize cooling airflow around the unit, ensure that the clearance 
between the unit and surrounding objects is as large as possible. 
 
Remarks: 
- In case without option -N (with cover) and the enclosure made by 
combustible material, the distance d2 shall be more than 13mm 
because Varistor is implemented inside of the unit. This requirement 
comes from the safety approvals. 

1.3 Installation to fulfil EMC requirement 

To ensure the best EMI-performance, the equipment should be 
mounted inside an earthed metal box. 
If it is not possible, an install power supply and a load on an earthed 
metal plate. 
 
Input cables should be twisted and places as close to the metal 
enclosure as possible. 
 
Output cables of positive (+) and negative (-) should be twisted and 
shall be separated from input cables as much as possible. 
 
If radiation from input or output cables are an issue, use appropriate 
EMC ferrite clamp on the cables. 
 
When function pins are connected to an user accessible point (i.e., 
panel switch, indicator circuit etc.), these must be protected from 
electrostatic discharging. 

2.  Derating 

2.1 Derating curve by input voltage 

 
 
 
 
 
 
 
 
 
 
 

Fig. 2.1 Derating curve by input voltage 

 
Remarks: 
- OFI1200A12 has no input voltage derating. 
- The over current protection will be activated as following Fig.2.1. 

2.2 Temperature measuring point 

For reliable and safe operation, make sure the maximum component 
temperature given in Table 2.1 are not exceeded. 
The temperature measuring points are shown in Fig. 2.2. 
Operating at the maximum temperature rating results in 3-years life 
expectancy. 
 
 

Table 2.1 Maximum operating temperature 

Point 

Part name 

Part 

Ref. 

Maximum Temperature [

°

C] 

Standard 

Optional: N 

Baseplate of Internal 
power supply module 

See Fig. 2.3 

See Fig. 2.3 

Line filter 

L102 

110 

100 

Aluminium 
Electrolytic Capacitor 

C405 

88 

88 

Aluminium 
Electrolytic Capacitor 

C501 

89 

89 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 2.2 Temperature measuring points

 

 

d1

d1

d2

(Side view) 

(Top view) 

Содержание OFI1200A Series

Страница 1: ...ranty 11 6 1 Life Expectancy 11 6 2 Warranty 11 7 Options 11 7 1 Option N with Metal cover 11 7 2 Option O with Active ORing 11 1 Assembling and Installation Method 1 1 Mounting method OFI1200A series...

Страница 2: ...a load on an earthed metal plate Input cables should be twisted and places as close to the metal enclosure as possible Output cables of positive and negative should be twisted and shall be separated f...

Страница 3: ...s section solid 0 2 mm2 6 mm2 Connector cross section flexible 0 2 mm2 4 mm2 Conductor cross section AWG AWG 24 10 Conductor cross section flexible with ferrule 0 25 mm2 4 mm2 Stripping length 8mm Tor...

Страница 4: ...ipple noise measurement The specified ripple and ripple noise are measured by the method shown in Fig 3 3 Fig 3 3 Method of Measuring Output ripple and ripple noise Remarks When the ambient temperatur...

Страница 5: ...tivated and shut down the output When the thermal protection is activated turn off the input voltage and eliminate all the overheating conditions To recover the output voltage let the unit cool down b...

Страница 6: ...SHORT 0 5V max 5 Output OFF SW SHORT 2mA min SW OPEN 0 1mA max Fig 4 3 The Internal circuit and function of X601 a Use external voltage source Positive logic External resistor Rrc value shall be deci...

Страница 7: ...usted by connecting external resistors to ITRM or by applying a voltage externally Meanwhile the Hiccup mode of the short circuit protection will be disabled 1 Constant current adjustment by potentiom...

Страница 8: ...eration Series operation is possible by connecting the output of two or more power supplies as shown in Fig 5 1 Fig 5 1 Example of Series operation Output current in series connection should be lower...

Страница 9: ...or parallel operation Remarks Make sure that the wiring impedance of a load from each unit becomes even A voltage drop from Vout of unit to the connected point of terminal S should be less than 0 5V f...

Страница 10: ...not necessary to connect the ITRM terminals together Examples of connecting constant current circuit in parallel operation are shown in Fig 5 8 and Fig 5 9 Refer to section 4 9 Adjustable constant cu...

Страница 11: ...oltage adjustment range by external voltage source with the option O is shown as below Model Output Output Number Voltage Voltage adj OFI1200A28 O 28VDC 5 33 6VDC OFI1200A48 O 48VDC 5 57 6VDC WARNING...

Отзывы: