21
4. Power cables connection & Startup
This section explains:
Access to terminal block
Common input sources connection
Separate input sources connection
Frequency converter connection
UPS initial startup
Use cable cross section and protective device specification
Model
6K
10K
Protective earthing conductor
Min cross section
4mm
2
(10AWG)
6mm
2
(8AWG)
Input L, N, G
Min conductor cross section
4mm
2
(10AWG)
6mm
2
(8AWG)
Input fuse
60A
80A
Output L,N,
Min conductor cross section
4mm
2
(10AWG)
6mm
2
(8AWG)
External Battery Cabinet
Positive Pole(+), Negative
pole(-), Neutral Pole
Min conductor cross section
4mm
2
(10AWG)
2.5mm
2
*2
(12AWG*2)
External Battery Cabinet Fuse
60A
80A
in Positive Pole(+), Negative
pole(-), Neutral Pole
The UPS does not have an automatic protection device against current
backfeed. It is suggested that install an external isolating device ,which
is shown in the following illustration. Check for hazardous voltage
between all terminals before operating on this circuit.
Содержание VFI 10000P/RT LCD
Страница 4: ......
Страница 31: ...27 Figure 4 5 a Parallel systerm wiring diagram of 6K 10K ...
Страница 32: ...28 Figure 4 5 b Parallel System Installation Diagram ...
Страница 43: ...39 Figure 5 14 Main menu tree ...
Страница 50: ...46 Example set rated output voltage value Figure 5 20 Set rated output voltage value ...