6. Specifications
MODEL
6000
6000R
10000
10000R
CAPACITY*
6000 VA / 4800 W
10000 VA / 8000 W
INPUT
Voltage
Range
Low Line Loss
110 VAC ± 3 % at 50% Load; 176 VAC ± 3 % at 100% Load
Low Line Comeback
Low Line Loss V 10V
High Line Loss
300 VAC ± 3 %
High Line Comeback
High Line Loss Voltage - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Phase
Single phase with ground
Power Factor
≧
0.99 at 100% Load
OUTPUT
Output voltage
208/220/230/240VAC
AC Voltage Regulation
± 1%
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
100%~110%: 10min
110%~130%: 1min
>130% : 1sec
Battery mode
100%~110%: 30sec
110%~130%: 10sec
>130% : 1sec
Current Crest Ratio
3:1 max
Harmonic Distortion
≦
3 % @ 100% Linear Load;
≦
6 % @ 100% Non-linear Load
Transfer
Time
Line
Battery
0 ms
Inversor
Bypass
0 ms
Inversor
ECO
<10 ms
EFFICIENCY
AC mode
> 89%
Battery Mode
> 88%
BATTERY
Standard
Model
Type & Numbers
12 V / 7 Ah x 20
12 V / 9 Ah x 20
Recharge Time
7 hours recover to
90% capacity
3 hours recover to
90% capacity
9 hours recover to 90%
capacity
4 hours recover to 90%
capacity
Charging Current
1 A ± 10% (max.)
2 A ± 10% (max.)
1 A ± 10% (max.)
2 A ± 10% (max.)
Charging Voltage
14.4 V ± 1%
Long-run
Model
Type
Depending on applications
Numbers
18 - 20
Charging Current
4 A ± 10% (max.)
2 A ± 10% (max.)
4 A ± 10% (max.)
2 A ± 10% (max.)
Charging Voltage
14.4 V ± 1%
PHYSICAL
Standard
Model
Dimension, D X W X H
592X250X576
UPS unit:
580X438X133
Battery pack: 580X438
X133
592 X250 X576
UPS unit:
668X438X133
Battery pack: 580X438
X133
Net Weight (kgs)
81
UPS unit: 17
Battery pack: 57
83
UPS unit: 20
Battery pack: 63
Long-run
Model
Dimension, D X W X H
592 X250 X576
580 X 438 X 133
592 X250 X576
668 X 438 X 133
Net Weight (kgs)
25
17
27
20
ENVIRONMENT
Operation Temperature
0 ~ 40°C (the battery life will down when > 25°C)
Operation Humidity
<95 % and non-condensing
Operation Altitude**
<1000m
Acoustic Noise Level
Less than 55dB @ 1 Meter
Less than 58dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows®2000/2003/XP/Vista/2008/7, Linux, Unix and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.