5
For Technical Support:
Visit our website at:
www.power-tronics.com
Call Us at:
(830) 895-4700
If you do not have any of the specifications of your generator’s
exciter, or if you don’t know where to start when trying to determine
your exciter specs, please see the section below for instructions on
measuring and calculating your exciter specifications.
• Measure your exciter field resistance using a multimeter on your field leads.
Record this value. If you have a brush-type generator, also take a resistance
reading on your slip rings: the value you obtain on the slip rings should be no
more than 1% difference from the value you obtained through the field leads.
• Next, start and run the generator and apply 12V from a battery through your
field leads and record the AC voltage produced by the generator. To
determine your full load exciter field voltage, use the following formula:
E
Exc.
=
€
E
Gen
.
Conf
.
E
Gen
.
Output
E
Battery
"
#
$
$
%
&
'
'
* 2
Where
E
Gen.Conf
.
is your Generator’s configured voltage (e.g.: 120, 208, 240,
480V, etc.),
E
Gen.Output
is your recorded output voltage, and
E
Battery
is your battery
voltage (12V usually).
• Next, calculate your maximum exciter field amperage using your measured
field resistance and your calculated exciter voltage using the following formula:
I
=
E
R
Where
I
is your maximum exciter field current,
E
is your calculated field
voltage from the above formula, and
R
is your measured field resistance.
Using the values you just measured and calculated, see the chart on
the previous page to determine which connection you should use to
connect the XR5C to your generator.
For Example:
Measured Field Resistance: 18Ω
Battery Voltage: 12V
Generator Configuration: 480V Wye
12V applied to the field yields 189VAC L1-L3.
E
Exc.
=
480
$%&
$'
∗ 2 = 60.95
E
Exc.
=
60.95VDC (Full-Load Voltage)
This generator would use
Connection B
.