Parallel Configuration for Connection C & D
To use the SE350 Static Exciter Module in a parallel configuration either with another
generator or with a buss such as a utility, use the diagram below for proper hookup with
the SE350 configured for Connection C or D.
NOTE:
Power-Tronics products parallel using the Reactive Droop compensation method. This allows
our products to parallel with existing systems easily while also allowing islanded operation with the flip of
a switch. When initially installing the droop resistor, set it for approximately 7
Ω
before final adjustment
later. If the droop is excessive when load testing, reduce the resistance a bit at a time until satisfactory
droop is achieved.
CT should be sized at 25-35VA capacity!
XR or UVR Series
Voltage Regulator, or
UVR, XR, or PC series
Phase Controller
NOTE:
If using Connection D,
refer to Page 9 for a
diagram of how to
connect your second
SE350 Module!