Note about Field Resistance: 

• 

When measuring field resistance on a brushless generator, simply measure the resistance of the 
exciter field through your field leads with a multimeter. 

• 

When measuring field resistance on a brush-type generator, measure the resistance through both 
the field leads as well as directly on the slip rings themselves.  

The readings you obtain should 

ideally be the same, but 

no more than 1% difference.

 

 If you show more than 1% difference in 

reading your generator has brush and ring contact problems and will need cleaning or 
maintenance before installing the XC15.  

Failure to correct brush and ring contact problems 

will result in severe damage to the voltage regulator as well as possible PERMANENT 
damage to the slip rings themselves!

  

NEVER

 

use emery cloth, carborundum stones, 

“comm sticks”, or Tuner cleaner to dress or clean slip rings

.  They will make a bad problem 

much, much worse!  Only use Garnet or Flint sandpaper and clean with a clean rag soaked with 
Acetone for best results! 

 
 

If you do not have any of the specifications of your generator’s exciter, or if you 

don’t know where to start when trying to determine your exciter specs, please see 

the section below for instructions on measuring and calculating your exciter 

specifications. 

 

•   Measure your exciter field resistance using a multimeter on your field leads.  

Record this value.  If you have a brush-type generator, also take a resistance 
reading on your slip rings:  the value you obtain on the slip rings should be no 
more than 1% difference from the value you obtained through the field leads.   

 
•   Next, start and run the generator and apply 12V from a battery through your 

field leads and record the AC voltage produced by the generator.  To 
determine your full load exciter field voltage, use the following formula: 

E

Exc.

 =

 

   

 

Where 

E

Gen.Conf

.

 is your Generator’s configured voltage (e.g.: 120, 208, 240, 

480V, etc.), 

E

Gen.Output

 is your recorded output voltage, and 

E

Battery

 

is your battery 

voltage (12V usually).   
 

•   Next, calculate your maximum exciter field amperage using your measured 

field resistance and your calculated exciter voltage using the following formula: 

 

Where 

I

 is your maximum exciter field current, 

E

 is your calculated field 

voltage from the above formula, and 

R

 is your measured field resistance.   

 

 

Using the values you just measured and calculated, see the 

specifications on the previous page to determine whether the XC15

 

is 

the correct product for your application. 

 
 

 

E

Gen

.

Conf

.

E

Gen

.

Output

E

Battery

"

 

#

 

$

 

$

 

%

 

&

 

'

 

'

 

* 2

I

=

E

R

Содержание C15

Страница 1: ...uilt to minimize failures and potential downtime The XC15 are capable of parallel operation with other generators or with a utility buss The integrated 0 10VDC or 4 20mA interface allows a wide variety of VAR PF or other PLC controls to remotely control the unit for extreme accuracy and unattended installations A heavy duty rectifier section oversized heatsink and flexible hookup design makes the ...

Страница 2: ...put Power Field Connection Diagram 9 277V Input Power Field Connection Diagram Line Neutral 10 Current Transformer Wiring Diagram Paralleled Generators 11 Fully Automatic Remote Adjustment Wiring Diagram 12 Automatic Manual Selectable Remote Adjustment Wiring Diagram 13 Integrated Battery Flash Wiring Diagram 14 Initial Setup and Commissioning 15 Application Troubleshooting 16 Bench Check Procedur...

Страница 3: ...e result of over 30 years of engineering efforts and offers high demand features at a competitive price point The XC15 is a time and field proven design based upon the Power Tronics XR8 and SEM250A and is engineered to greatly simplify setup while offering extreme reliability When properly installed the XC15 Voltage regulator is designed to provide a lifetime of service A Generator voltage regulat...

Страница 4: ...ained from your generator exciter verify that your generator fits the specifications below Exciter Field Resistance 2 5Ω Exciter Full Load Voltage 32VDC Use 120V Connection See Page 8 Exciter Field Resistance 5Ω Exciter Full Load Voltage 63VDC Use 240V Connection See Page 9 or 277V Connection See Page 10 WARNING BRUSH AND SLIP RING CONNECTION PROBLEMS ARE THE 1 SOURCE OF VOLTAGE CONTROL PROBLEMS A...

Страница 5: ...ng to determine your exciter specs please see the section below for instructions on measuring and calculating your exciter specifications Measure your exciter field resistance using a multimeter on your field leads Record this value If you have a brush type generator also take a resistance reading on your slip rings the value you obtain on the slip rings should be no more than 1 difference from th...

Страница 6: ...tage L L 208 240V Voltage L N 120 139V NOTE 208V is Standard Voltage Series Delta 240V 3ø Voltage L L 240V Voltage L1 L2 N 120V Voltage L3 N 208V NOTE L3 N is a High Leg 208V instead of 120V Double Delta 120 240V 1ø Voltage L L 240V Voltage L N 120V Preferred Single Phase Connection Don t Use Zig Zag if Possible NOTE Derate generator by 1 3 rated capacity when using this connection ...

Страница 7: ... Voltage U W 208 240V Voltage U N 120 139V NOTE 208V is Standard Voltage Series Delta 240V 3ø Voltage U W 240V Voltage U W N 120V Voltage V N 208V NOTE V N is a High Leg 208V instead of 120V Double Delta 120 240V 1ø Voltage U W 240V Voltage U W N 120V Preferred Single Phase Connection Don t Use Zig Zag if Possible NOTE Derate generator by 1 3 rated capacity when using this connection ...

Страница 8: ...ing center taps T7 and T0 See Pages 6 and 7 Using a transformer to connect the input of the XC15 to 2 different phases of the generator will result in greater regulation accuracy than when connecting line neutral Diagram Assumes a 208 240V Generator For 480V Generators use a 1KVA or larger Transformer with a 120V Secondary OR Connect to the Generator winding center taps at T7 and T0 NEVER install ...

Страница 9: ...the winding center taps T7 and T9 See Pages 6 and 7 Connecting the input of the XC15 to 2 different phases of the generator will result in greater regulation accuracy than when connecting line neutral Diagram Assumes a 208 240V Generator For 480V Generators use a 1 5KVA or larger Transformer with a 240V Secondary OR Connect to the Generator winding center taps at T7 and T9 NEVER install a switch o...

Страница 10: ...connection Regulation problems or damage to the unit may result For use on 480V systems connect the regulator from Line to Neutral T7 and T0 See Pages 6 and 7 or use a 480 240V step down transformer rated at 1KVA Diagram Assumes a 480V Generator For other voltages use a 1KVA or larger Transformer with a 240V Secondary NEVER install a switch or breaker on the DC or Exciter side of the voltage regul...

Страница 11: ...ve Droop compensation method This allows our products to parallel with existing systems easily while also allowing islanded operation with the flip of a switch When initially installing the droop resistor set it for approximately 7Ω before final adjustment later If the droop is excessive when load testing reduce the resistance a bit at a time until satisfactory droop is achieved CT should be sized...

Страница 12: ...am This wiring diagram shows ONLY the control wiring configuration for fully automatic Remote Control of the XC15 Power wiring is shown on Pages 8 10 0 10VDC or 4 20mA Control Signal NOTE Colored Wires are for ease of identification in this drawing only they are not required ...

Страница 13: ... ONLY the control wiring configuration for fully automatic Remote Control of the XC15 Power wiring is shown on Pages 8 10 0 10VDC or 4 20mA Control Signal NOTE Colored Wires are for ease of identification in this drawing only they are not required 100KΩ 2w DPDT Switch or Relay Switch Position Automatic é Manual ê ...

Страница 14: ...from 3 5VAC at terminals AC1 and AC2 Connecting the battery flash is not required if sufficient residual voltage is present the regulator will build itself up NOTE Connect to 12 or 24 terminal based on 12V or 24V battery voltage NOTE Pushbutton Momentary Toggle Switch Relay Contact Switched B or Oil Pressure Switch Do Not Omit Switch Battery Will Drain with Engine Stopped NOTE 2 nd Circuit of Doub...

Страница 15: ...e this issue If connected in 240V connection consider reconnecting to 277V connection 8 Set the internal voltage adjustment to the desired voltage setting for the generator output by turning the adjustment screw clockwise right Note that the voltage adjustment is a 25 turn pot 9 Place the generator on line and observe the frequency and voltage 10 If the generator is being paralleled measure the dr...

Страница 16: ... voltage regulator 7 Loose wiring connections 8 Input voltage to regulator is too low 9 Exciter field is grounded 10 Non linear load or wrong selection for regulator hookup 11 Exciter fields are reversed 12 Wrong selection of regulator wiring configuration 13 Defective voltage regulator 14 SCR or Inverter drive effecting generator waveform 15 Regulator needs battery flashing circuit 16 Isolation t...

Страница 17: ...F Brightness NOTE It may take several turns of the adjustment screw before the lights illuminate 8 Slowly turn the internal voltage adjustment Counter Clockwise Left until the lights go dark The test light should be OFF NOTE It may take several turns of the adjustment screw before the lights go dark 9 Turn off AC power and disconnect the XC15 from your AC power source After roughly 1 second the te...

Страница 18: ...blem Description History Please be detailed Ship To Address City State Zip Country Company Name Contact Person Telephone Number Email Address Primary Load Please Explain Repair Warranty Request Information Generator Leads Check One 12 10 6 4 3ø 4 1ø 3 Generator Wiring Mode Check One High Wye Low Wye Series Delta Zig Zag Double Delta Single Phase Other Terminal Voltage Residual AC Voltage Rated KW ...

Страница 19: ...e part A repair request form must be sent in with the product before repairs will begin You can obtain this form by contacting Power Tronics Inc Send repairs to Power Tronics Inc 2802 Cobbler Ln Kerrville Texas USA 78028 Send in repairs only by UPS or FedEx USPS will NOT deliver to our facility Any one of the following conditions will void the warranty v Overheating of the power supply resistor on...

Отзывы: