GENERATOR ASSEMBLY INFORMATION 

 

EXCITER TYPE GENERATOR 

The exciter pole pieces contain residual magnetism, which sets up lines of force 

across the air gap to the exciter armature.  When the exciter begins to rotate a voltage 
is induced and current flow is initiated in the exciter armature AC windings.  This voltage 
is fed to the rotating rectifier assembly, rectified and fed to the alternator field, which 
sets up lines of force across the air gap to the alternator stator windings and to the 
output circuit. A static voltage regulator is connected to the generator output.  The 
regulator will rectify part of the output voltage to provide a DC voltage to the exciter field 
coils.  This will increase the density of the lines of force in the exciter, increasing the 
voltage induced into the exciter armature windings, and therefore, to the rotating 
rectifiers. The rotating rectifier output will be increased which increase the alternator 
field strength and generator output will build up its rated voltage.  Adjustment of the 
generator output to the rated voltage level is accomplished by controlling the current fed 
to the exciter field coils. Regulation is automatic with the static type voltage regulator.  
An additional voltage adjustment range is provided if desired by turning the Voltage 
Adjust Rheostat. 

 

ELECTRONIC VOLTAGE REGULATION 

Electronic Voltage Regulator (EVR) also referred to, as an Automatic Voltage 

Regulator (AVR) is a very reliable device, which uses solid-state electronics to maintain 
voltage accuracy at ±2% of the regulated voltage.  The Voltage Regulator is designed to 
automatically regulate and maintain the generated AC voltage throughout the load 
range that is from no load to full load.  

 

VOLTAGE CONNECTION 

The generator may be connected at the terminal board to deliver 120/240 volts to 

a 3 wire grounded neutral system.  
  If all equipment requires 120-volts then the 120-volt connection is preferred, even if 
two lines leave the same switch box. The two lines at the inputs to the switch box are 
both connected to the un-grounded 120-volt lines from the generator.   
The 120-volt connection enables the Electronic Voltage Regulator (EVR) to hold the 
voltage very close to the 115 or 120 volts, as initially adjusted, regardless of the power 
distribution amount the different distribution lines.  The 120-volt connection is 
recommended if the entire electrical load requires only 115 or 120 volts. Although the 
120/240-volt connection may also be used when all loads requires only 110 volts, it 
should be pointed out that this connection, the 240-volts, is regulated and the lightly 
loaded phase, or line, will deliver a high line to neutral voltage and the heavily loaded 
phase will deliver a low line to neutral voltage.  The heavily loaded line may have such a 

Содержание PTI-15-T4F

Страница 1: ...Generating Power to the World Page 1 of 25 PTI 15 20 T4F Operators Manual Power Technology Southeast 634 State Road 44 Leesburg FL 34748 8103 Phone 352 365 2777 Fax 352 787 5545...

Страница 2: ...des Starting and Stopping Methods 15 Engine Specifications 16 Engine Maintenance Schedule 17 Engine Oil Maintenance 18 Lubricating Oil Specifications 18 LUBRICATING OIL VISCOSITY 18 RECOMMENDATIONS 18...

Страница 3: ...Generating Power to the World Page 3 of 25 PTI 15 20 T4F Operators Manual FIELD COIL 23 BALANCE 23 BEARING 24 STATOR ASSEMBLY 24 TROUBLESHOOTING 25 TROUBLE 25 POSSIBLE CAUSE 25 SUGGESTED ACTION 25...

Страница 4: ...enerator This manual was up to date at time of printing downloading there may be changes not reflected in your manual If there is any questions please contact Power Technology s customer service dept...

Страница 5: ...hich have been subjected to alteration modification neglect or unauthorized repairs D Troubleshooting routine service tune ups replacement of filters belts coolant lubricants hoses clamps exhaust syst...

Страница 6: ...bligation to change units or parts previously manufactured Warranty registration card must be completed and mailed to Power Tech at the above address to validate the Warranty This is the only express...

Страница 7: ...ty regulations before you attempt to assemble or use this unit WARNING Indicates a potentially hazardous situation which may possibly result in serious injury or possible death CAUTION Indicates a pot...

Страница 8: ...torn or bulky clothing around machinery Entanglement in rotating parts controls or projections may cause persona injury Use additional safety items e g hardhat eye protection gloves etc as appropriate...

Страница 9: ...rly dispose of DO NOT mix gasoline or alcohol with diesel fuel The mixture can cause a fire EXHAUST GASES AND FIRE PREVENTION Engine exhaust fumes can be very harmful if allowed to accumulate Be sure...

Страница 10: ...ants engine oil etc DO NOT remove the radiator cap while the engine is running or immediately after stopping Wait approximately ten minutes for the radiator to cool before removing the cap Be sure the...

Страница 11: ...ing in the formation of harmful substances Only use anti freeze that is recommended and approved by Engine Manufacturer Be mindful of the environment Before draining any fluids be prepared to dispose...

Страница 12: ...aintenance after the engine radiator muffler or muffler cover has cooled off completely Always use the appropriate tools and jig fixture when performing any service work Be sure to understand and foll...

Страница 13: ...vel for proper Fill add if necessary Check for absence of water in fuel drain if necessary Check for absence of DTC or failures Check for absence of excessive fan belt looseness Using the PTG Series C...

Страница 14: ...ving around in the menu changing a settings value or changing the currently displayed parameter page Generator LED Green Engine running with no issues Amber Engine running with warnings Red Engine shu...

Страница 15: ...e remotely started Auto When in the Auto mode the engine waits to receive a start command Running When engine is Running the controller monitors engine parameters and waits to receive a stop command F...

Страница 16: ...1800rpm 30 Oil type SAE 10W 40 API Class Oil capacity 8 4 Qts 8L Cooling System Capacity 11 25 Qts 10 6L Air Filter P N 04FA2768 Primary Fuel filter P N 08FF4LE P Secondary Fuel Filter P N 08FF4LE S...

Страница 17: ...air fuel filters need to be changed Maintenance Service Item See notes Daily 150 Hour Interval 500 Hour Interval 1000 Hour Interval Remarks Engine Oil Level deterioration Leakage x Engine Oil Change...

Страница 18: ...Specifications API Class CJ 4 Engine Oil LUBRICATING OIL VISCOSITY RECOMMENDATIONS The minimum ambient temperature during cold engine start up and the maximum ambient temperature during engine operat...

Страница 19: ...zing and boiling See the tables below ETHYLENE GLYCOL Freeze Boil Concentration Protection Protection 50 Percent 36 C 33 F 106 C 223 F 60 Percent 51 C 60 F 111 C 232 F PROPYLENE GLYCOL Freeze Boil Con...

Страница 20: ...cations CHECKING RESERVOIR TANK COOLANT LEVEL At a Minimum of 25 Hours of Operation Ensure that the coolant level of the radiator reservoir tank is between the upper limit FULL and the lower limit LOW...

Страница 21: ...HOURS and SERVICE LOG THIS SERVICE LOG IS PROVIDED TO HELP YOU KEEP AN ACCUMULATIVE RECORD OF OPERATION HOURS ON YOUR GENERATOR SET AND THE DATES REQUIRED SERVICES WERE PERFORMED ENTER TIME TO THE NEA...

Страница 22: ...provided if desired by turning the Voltage Adjust Rheostat ELECTRONIC VOLTAGE REGULATION Electronic Voltage Regulator EVR also referred to as an Automatic Voltage Regulator AVR is a very reliable devi...

Страница 23: ...adjustment of the regulator sensing circuit ROTATING FIELD ASSEMBLY ROTOR The rotating field assembly consists basically of four members 1 the shaft assembly 2 the core assembly 3 the field coil damp...

Страница 24: ...nspection of the bearing is recommended at typical service intervals If signs of abnormal wear or leakage are observed the bearing should be replaced Never use liquids of any kind to clean the generat...

Страница 25: ...rol wiring and check crank connections Cranking fuse blown Replace fuse with new of identical size Engine cranks but doesn t start Out of fuel Check fuel level add fuel if necessary Fuse Blown Replace...

Отзывы: