Interconnection Diagram, 120/240 V Nominal, 1-Phase, 3-Wire
Operational Test
Страница 1: ...e amplitude at 27 to 52 Hz and 5 Gs at 53 to 1000 Hz Shock Withstands up to 20 Gs in each of three mutually perpendicular axes Weight 10 oz 0 28 kg Net FUSES Although the AVC63 4A has an internal fuse it is recommended that fuses with high interruption capability be installed per the interconnection diagram to protect wiring from faults before the regulator A spare fuse is included with the AVC63 ...
Страница 2: ... preliminary setup as described in the above paragraphs NOTE All voltage readings are to be taken with an average reading voltmeter 2 Start the prime mover and bring it up to its rated speed RESULT Voltage should build up If not per form field flashing 3 Slowly adjust the regulator Var CW until the generator output voltage reaches the nominal value If used adjust the remote Var to set the generato...
Страница 3: ...Interconnection Diagram 120 240 V Nominal 1 Phase 3 Wire Operational Test ...