10
Figure7
e)
If you are installing power management software, connect yourcomputer to one
of the communication ports or optional connectivity card. For the
communication ports, usean appropriate cable.
f)
If your rack has conductors for grounding or bonding of ungroundedmetal parts,
connect the ground cable (not supplied) to the groundbonding screw. See “Rear
Covers”for the location ofthe ground bonding screw for each model.
g)
If an emergency power-off (disconnect) switch is required by localcodes, see
“Remote Emergency Power-off” (REPO) to install the REPO switch before
powering onthe UPS.
h)
Continue to “UPS Startup”
.
Connecting the EBP(s)
(1)
To install the optional EBP(s) for a UPS
a)
Remove the front cover of each EBP and UPS (see Figure 8).
It is the same with the installation of the front cover. (Refer” To install the UPS“)
Figure8Removing the EBP Front Cover
b)
On the bottom of the UPS front cover, remove the EBP cableknockout (see Figure 9).
Figure9Removing the UPS Cable Knockout