POWER ELECTRONICS
SDRIVE 700
COMMONLY USED CONFIGURATIONS
105
12.
12.1.
Start / Stop Commands and Speed Reference by Keypad
12.1.1.
Parameters Configuration
Parameter
Name / Description
Value
G1: Options Menu.
4 LANG=ENGLISH
G1.4
/ Language selection
ENGLISH
7 PROG = STANDAR
G1.7
/ Program activation
STANDAR
G2: Motor Nameplate.
1 MTR CURR=00.00A
G2.1
/ Motor rated current
__A (Set according to motor nameplate).
2 MTR VOLT=400V
G2.2
/ Motor rated voltage
__V (Set according to motor nameplate).
3 MTR PWR=00.0kW
G2.3
/ Motor rated power
__kW (Set according to motor nameplate).
4 MTR RPM=1485
G2.4
/ Motor rpm
__rpm (Set according to motor nameplate).
5 MTR PFA=0.85
G2.5
/ Cosine Phi
__ (Set according to motor nameplate).
6 MTR FRQ=50Hz
G2.6
/ Motor frequency
__Hz (Set according to motor nameplate).
7 MTR COOL=40%
G2.7
/ Motor cooling at zero speed
Use the following values as a reference:
Submersible pumps
Î
20%
Self-cool motor
Î
40%
Force-cooled motor
Î
100%
G3: References.
1 REF1 SPD=LOCAL
G3.1
/ Speed reference source 1
LOCAL
Î
Reference will be determined by keypad and is set in
G3.3 'Local Speed Reference'.
3 LOCAL SPD=+100%
G3.3
/ Local Speed Reference
100%
G4: Inputs – S4.1: Digital Inputs.
1 CNTROL MODE1=1
G4.1.1
/ Main Control Mode
1
Î
LOCAL (Drive control is done by keypad).
3 RESET MODE=Y
G4.1.3
/ Reset by keypad
Y
Î
YES (Enables reset by keypad).
12.2.
Start / Stop Commands by Terminals and Speed
Reference by Analogue Input
12.2.1.
Parameters Configuration
Parameter
Name / Description
Value
G1: Options Menu.
4 LANG=ENGLISH
G1.4
/ Language selection
ENGLISH
7 PROG = STANDAR
G1.7
/ Program activation
STANDAR
G2: Motor Nameplate.
1 MTR CURR=00.00A
G2.1
/ Motor rated current
__A (Set according to motor nameplate).
2 MTR VOLT=400V
G2.2
/ Motor rated voltage
__V (Set according to motor nameplate).
3 MTR PWR=00.0kW
G2.3
/ Motor rated power
__kW (Set according to motor nameplate).
4 MTR RPM=1485
G2.4
/ Motor rpm
__rpm (Set according to motor nameplate).
5 MTR PFA=0.85
G2.5
/ Cosine Phi
__ (Set according to motor nameplate).
6 MTR FRQ=50Hz
G2.6
/ Motor frequency
__Hz (Set according to motor nameplate).
7 MTR COOL=40%
G2.7
/ Motor cooling at zero speed
Use the following values as a reference:
Submersible pumps
Î
20%
Self-cool motor
Î
40%
Force-cooled motor
Î
100%
G3: References.
1 REF1 SPD=LOCAL
G3.1
/ Speed reference source 1
LOCAL
Î
Reference will be introduced by keypad and is set in
G3.3 'Local Speed Reference'.
2 REF2 SPD=LOCAL
G3.2
/ Speed reference source 2
AI1
Î
Reference will be introduced by Analogue Input 1.
3 LOCAL SPD=+100%
G3.3
/ Local Speed Reference
+100%